Building Consistency Meeting Commercial Date 10/05/2011 Recorder and minutes prepared by Danny Wooten/Lon McSwain Staff present: On File Public present: None Topics/Subject Decisions/Conclusions/Actions Old Business None New Business Section 603.1 Section 303.1 Exception 1 Floor Ratings Guards Green Vegetated Wall IGCC NC 2012 Codes FRT is not acceptable as a structural floor in Type I and II buildings. FRT plywood over metal deck is acceptable. Any tenant space or building used as an A occupancy with an occupant content of less than 50 shall be considered a B occupancy. A floor supporting a shaft wall shall have the same fire rating as required for the shaft wall. Guards are not required on green roofs that are accessed only for maintenance. This would be covered by OSHA. It recommended that this type walls have a secondary water supply to the irrigation system by the IGCC (Alternate Method) Final hearings to he held in Phoenix in Nov. NC not to adopt at this time. The use of these codes was permitted as of Sept. 1, 2012 with a mandatory date of March 1, 2012. . Approved By ___Lon McSwain_________ Date _______10/26/2011