Pressure , Differential Pressure and Temperature Transmitter

advertisement
 Pressure , Differential
Pressure and Temperature
Transmitter
Table of Contents
Chapter1: Presentation of Pressure , Differential Pressure
Transmitters
1.1
2.1
3.1
4.1
5.1
6.1
7.1
8.1
Definitions
Transmitter Parts
Sensors
Types of transmitters
Process Connections
Manifolds
Applications
Extra Information
Chapter 2: Presentation of Temperature Transmitters
1.2 Transmitter Types
2.2 Sensors
3.2 Thermowells
Page 1 of 152
Chapter 3: Standards
Chapter 4: Sample Spec
Chapter 5: Sample Datasheet
Page 2 of 152
Chapter 1
Presentation of Pressure and
Differential Pressure
Transmitters
Page 3 of 152
Pressure Transmitter
Pressure Transmitter Page 4 of 152
T bl f C t t
Table of Contents
¾Definitions ¾T
¾Transmitters Parts itt
P t
¾Sensors
¾Types of Transmitters ¾Process Connections ¾Manifolds ¾Manifolds
¾Applications ¾Extra Information
Page 5 of 152
D fi iti
Definitions • Pressure Definition from Physic
Pressure is force distributed over, a surface. The pressure P
/
of a force F distributed over an area A is defined as: P = F/A
• Atmospheric Pressure
Atmospheric Press re
pressure is the force of pressure exerted by the earth's
atmosphere. Atmospheric pressure at sea level is
equivalent to 14.695 psia. The value of atmospheric
pressure decreases with increasing altitude.
Page 6 of 152
• Barometric Pressure
Barometric pressure is the same as atmospheric pressure.
• Hydrostatic Pressure
y
Hydrostatic, pressure is encountered in liquid level applications.
Hydrostatic pressure is the pressure below the liquid surface
exerted by the liquid above.
• Line Pressure
Line pressure is simply the amount of pressure, or the force per
unit area, exerted on a surface by the flow parallel to a pipe wall.
• Static Pressure
Static pressure is the same as line pressure
Static pressure is the same as line pressure.
• Working Pressure
Working
k
pressure is also
l referred
f
d to as line
l
or static pressure.
Page 7 of 152
• Absolute Pressure
Absolute pressure is a single pressure measurement with a
reference to a full, or p
perfect vacuum. Absolute p
pressure is the
measurement of the process pressure in excess of full vacuum or
0 psia. Zero absolute pressure (0 psia) represents a total lack of
pressure‐ For example, space is considered to be a full vacuum.
• Gauge Pressure
g
Gauge pressure is a single pressure measurement that indicates
atmosphere Gauge pressure represents the positive difference
atmosphere.
between atmospheric pressure. You can convert gauge pressure
to actual atmospheric pressure value to the gauge pressure
equivalent to 24‐7 psia 0 psig is equivalent to 14.7 psia.
Page 8 of 152
• Vacuum
Vacuum pressure is a single pressure measurement, which also
h a reference
has
f
t atmospheric
to
t
h i pressure.
Vacuum pressure is the measure of the depression of process
pressure below atmospheric pressure.
pressure
Vacuum pressure is generally measured in cm or inches of H20.
For example,
example 14.7
14 7 psia is equivalent to 407.5
407 5 inches of H2O.
H2O
Therefore, a pressure of 10 inches of H2O vacuum implies
process pressure is depressed 10 inches below atmosphere. Or
10 inches of H2O vacuum is equivalent to 397.5 inches of H20
absolute. Vacuum pressure is typically measured using a gauge
pressure transmitter with an elevated zero calibration.
Page 9 of 152
Page 10 of 152
Page 11 of 152
T
Transmitters Parts itt
P t
Page 12 of 152
T
Transmitters Parts itt
P t
Primary Electronic
Process Connections
Top Housings
Secondary Electronic
Page 13 of 152
Sensors •
Electromechanical Strain Gage
Electromechanical Strain Gage Strain gage sensors convert pressure into
relatively small resistivity changes. The change in resistance typically affects
the four legs of a Wheatstone bridge circuit, Figure 7‐1. When all the resistive
legs of the bridge circuit are balanced,
balanced and when the circuit is energized,
energized the
voltages read at test points 2 and 3 are equal. Strain gage sensors located in the
primary sensor usually take the place of two of the resistor legs in a
g circuit. Fixed resistor networks in the transmitter
Wheatstone bridge
electronics take the place of the other two legs. When there is zero pressure
applied to the transmitter, the resistance of the strain gages balances the fixed
resistors in the transmitter electronics and there is no voltage differential
across the
th test
t t points.
i t However,
H
when
h a pressure is
i applied
li d to
t the
th transmitter,
t
itt
the resistance of the strain gages changes, unbalancing the bridge, and creating
a proportional differential voltage across the test points. The transmitter
electronics converts this voltage signal into a 4
4‐20
20 mA signal for transmission.
Strain gage transducers are extremely sensitive to temperature effects. This is
because the resistance of the strain gage element can be affected by
temperature as well as applied stress. Extreme care must be taken in the design
off the
th primary
i
element
l
t to
t minimize
i i i the
th ambient
bi t temperature
t
t
effects
ff t or process
temperature effects on the sensor. It is also essential to be able to compensate
the sensor output for temperature changes, otherwise stability problems will
occur.
Page 14 of 152
Page 15 of 152
• Variable Capacitance
Variable capacitance transducers sensor operates as follows. An increase in pressure on
the process diaphragm is transmitted through the fill fluid to the ceramic diaphragm in
the capacitance sensor. The pressure increase causes the diaphragm to bulge, thus
changing the distance between the diaphragm and the reference plate.
plate This change in
distance is very small. The change in the ratio of the C‐ and C+ capacitance feeds the logic
circuit of the transmitter. Increased output from the logic circuit is converted to dc
voltage and amplified by the gain and summation circuit. The signal from the gain and
summation circuit is applied to the output current regulator through the zero and
span circuit. The output current regulator
produces an increase in transmitter output current, which is proportional to
the increase in process pressure.
pressure
The advantages of capacitance sensing for pressure measurement include:
‐ good accuracy, linearity, hysteresis, repeatability and stability
‐ excellent resolution
The disadvantages of capacitance sensor technology can be:
‐ potentially high impedance output
‐ sensitivity to temperature changes;
h
requires ambient
b
temperature
compensation
‐ requires custom electronics to produce a stable output
‐ since it is an analog sensor design, it may be susceptible to long term drift.
Page 16 of 152
Page 17 of 152
• Variable Reluctance
Variable reluctance elements are being employed to detect small
displacements of capsules or other sensors for direct coupling between
pressure sensitive elements and amplifier circuits, Figure 7‐3. The
variable reluctance pressure sensor, the inductance in a pair of coils is
affected by changes in the magnetic coupling of the diaphragm, which
is mounted between the two coils. With applied pressure, the sensing
di h
diaphragm
will
ill deflect
d fl t towards
t
d one coilil and
d away from
f
th other.
the
th The
Th
position of the sensing diaphragm enhances the magnetic flux density
of the closest coil, while decreasing the flux density of the furthest coil.
Increasing the magnetic flux density of a coil will increase the induction
and impedance of the coil.
yp
advantages
g of variable reluctance technology
gy are:
Typical
‐ Very low or very high pressure ranges.
‐ High output signal level.
‐ Fairly rugged construction
Disadvantages of this type of sensor include:
p
capability.
p
y
‐ Limited overpressure
‐ Since it is an analog sensor, it may be susceptible to long term drift.
Page 18 of 152
F i Cores
Ferrite
C
Diaphragm
Coils
Page 19 of 152
•
Piezoresistive
Piezoresistive sensors have come into wide use in recent years, they can be considered the
semiconductor technology version of the Electromechanical Strain Gauge that we have already
described. The Piezoresistive sensor consists of a semiconductor element that has been doped to
obtain a Piezoresistive effect. Its Conductivity is influenced by a change (compression or stretching of
the crystal grid) that can be produced by an extremely small mechanical deformation.
deformation As a result,
result the
sensitivity of monocrystalline sensors is higher than that of most other types. In particular higher than
the standard strain gauges, whose resistance changes only with geometrical changes in the structure.
Therefore Piezoresistive sensors are 10 to 100 times more sensitive than metal strain gauges. A
semiconductor element in a wafer format provides very high mechanical strength and elastic
behaviour up to the point of mechanical breakdown, yielding sensors that exhibit only
minor response to mechanical aging and hysteresis. But strain sensitivity in semiconductors is
temperature dependent and they must be compensated accordingly. Specific advantages are:
‐ High sensitivity, >10mV/V
‐ Good linearity at constant temperature
‐ Ability to track pressure changes without signal hysteresis, up to the destructive limit
Disadvantages are:
‐ Strong
S
non linear
li
d
dependence
d
off the
h full‐scale
f ll
l signal
i
l on temperature (up
( to 1%/kelvin)
1%/k l i )
‐ Large initial offset (up to 100% of full scale or more)
‐ Strong drift of offset with temperature
These disadvantages
g can be compensated
p
with electronic circuitry.
y
The Piezoresistive sensors must not be confused with the piezoelectric sensors. These one
produce a surface voltage potential difference when stressed in certain directions. Quartz, Rochelle
salt, barium Titanate, lead‐Zirconate, and tourmaline are some of the common piezoelectric crystals.
The p
piezoelectric sensors are a dynamic
y
type
yp of transducer that is incapable
p
of measuringg steady‐state
y
pressures. They have, however, the highest frequency response of any sensor, so they are used for
vibration, acceleration and alternating forces, or pressures such as those produced by a vortex flow
meter. They can be used in resonant transmitters.
Page 20 of 152
T
Types of Transmitters
fT
itt
• Gauge & Absolute Pressure Transmitters Standard Type
Standard Type
With Remote Seal
With Remote Seal
Low pressure Gauge
Low pressure Gauge Page 21 of 152
T
Types of Transmitters
fT
itt
• Differential Pressure Transmitters Standard Type With Remote Seals
With Remote Seals Page 22 of 152
P
Process Connection Gauge Pressure Transmitters C
ti G
P
T
itt
½” NPTM Varivent ½” Gas M ½” NPTF Flanged with Flush Diaphragm Seal
Face to Face Flanged
Flanged with Extended Diaphragm Seal
Flanged
Page 23 of 152
P
Process Connection Differential Pressure Transmitters C
ti Diff
ti l P
T
itt
Standard Type Face to Face Flange with ¼” NPTF in the middle
Flange with ¼
NPTF in the middle
With 2 legs Capillary and With
2 legs Capillary and
Flush Diaphragm seals One Leg Capillary with Wafer Diaphragm Seal and Flush Direct mount Diaphragm Seal on another side
Seal on another side Flanged with Flanged
with
Flush Diaphragm Seal
Page 24 of 152
Di h
Diaphragm Seals
S l
Fl h
Flush type Flange
Fl
E
Extended type Flange
d d
Fl
EExtended type Flange With d d
Fl
Wi h
Anti‐electrostatic Coating Varivent type Flange
Wafer type Flange
Diaphragm Seal and Capillary Construction Page 25 of 152
R
Reasons of Using Remote Seals
fU i R
t S l
In pressure transmitter directly connected to process piping by the use of
impulse lines, the process fluid leaves the piping, fills the impulse lines and
enters the bodyy of the transmitter. Remote seals are recommended for all
applications where it is necessary to prevent the fluid to leave the piping, or to
enter the transmitter because of:
‐ The process fluid is highly corrosive
‐ The process fluid is dirty, solid laden, or viscous and can foul the
impulse line
‐ The p
process fluid can solidifyy in impulse
p
line or the transmitter
body, because of temperature decrease
‐ The process fluid is too hazardous to enter the area where the
transmitter is located
‐ The transmitter body must be located away from the process for easier
maintenance
‐ The process temperature exceeds the recommended maximum limits
for the transmitter
Page 26 of 152
Filli Fl id i Di h
Filling Fluid in Diaphragm Seals
S l
Page 27 of 152
S l F U
Seals For Urea Service
S i
Page 28 of 152
M if ld 1
Manifolds‐1
• Most of the times is recommended to use TWO VALVE MANIFOLDS f G
TWO VALVE MANIFOLDS for Gauge pressure (
y
transmitters ( NOT TWO WAY!!! 2 way can just be a gauge valve!!)
Valved Drain Port is
suitable for Corrosive or Toxic medias Gauge Valve
Gauge Valve
Plugged Drain Port is not suitable for Corrosive or Toxic medias Two Valve Manifold
Page 29 of 152
T
Types of 2VMs f 2VM
Inlet :½” NPTF
Outlet: ½” NPTF
V/D: ¼” NPTF
/
”
Inlet :½
Inlet
:½” NPTM
NPTM
Outlet: ½” NPTF
V/D: ¼” NPTF
Inlet :½” NPTF
Outlet: ½” NPTF
V/D: ¼” NPTF
V/D: ¼
NPTF
Inlet :½
Inlet
:½” NPTF
NPTF
Outlet: Face to Face Flange
Page 30 of 152
V/D: ¼” NPTF
Double Block and Bleed Manifolds For Offshore
Page 31 of 152
M if ld 2
Manifolds‐2
• Most of the times is recommended to use
Fi /Th
Five/Three
VALVE
MANIFOLDS
f
for
pressure transmitters.
Differential p
Page 32 of 152
Page 33 of 152
T
Types of 3/5VMs f 3/5VM
Inlet :2 x ½” NPTF
Outlet: Face to Face Flange
V/D: Plug ( Optional)
V/D: Plug ( Optional)
Inlet :2 x ½” NPTF
Outlet: 2 x ½” NPTF
Outlet: 2 x ½
NPTF
V/D: Plug ( Optional)
Inlet :2 x ½” NPTF
Outlet: Face to Face Flange
V/D: ¼ “ NPTF Inlet :2 x ½” NPTF
l
”
Outlet: 2 x ½” NPTF
V/D: ¼ “ NPTF Page 34 of 152
Closed Coupled Instrument p
Mounting System For Offshore Orifice Flanges
First Block Valves
Five Valve Manifold
DPT
Page 35 of 152
A li ti
Applications • Level Measurement Level Measurement
• Density Measurement
• Interface Level Measurement
• Flow Measurement l
Page 36 of 152
Level ‐ Open Tank
Level Open Tank‐1
1 Page 37 of 152
Level ‐ Open Tank
Level Open Tank‐2
2 Page 38 of 152
Level ‐ Close Tank‐1 Page 39 of 152
Level ‐ Close Tank
Level Close Tank‐2
2 Page 40 of 152
D it
Density Page 41 of 152
I t f
Interface Level
L
l
Page 42 of 152
Flow
Fl
Page 43 of 152
E t I f
Extra Information
ti
• Material Selection • Housing
Housing • Gasket
• Turn Down Ratio
• Protocols Page 44 of 152
M t i l S l ti
Material Selection One of the most important factors for the selection of suitable material is
their resistance to corrosion, but also their compatibility to specific
applications must be considered.
considered As an example,
example toxic filling
filling‐fluids
fluids of
the transmitter cannot be utilized for food applications, because in case
of leakage they could poison the process fluid. Corrosion is the gradual
destruction of a metal by chemical or electrochemical means. It is
affected by several factors, from the combination of chemicals, even if
present in small amounts, to temperature. As an example if the
p
ggoes above 40 °C in seawater,, then p
pittingg corrosion is a
temperature
threat for stainless steel. Therefore Manufacturers cannot guarantee
that a material is suited to a particular application under all possible
process conditions. It is the user’s responsibility to make a careful
analysis of all process parameters when specifying materials. Other
process fluids not discussed here are listed in the attached corrosion
table where some further information are presented, but only as a
reference
f
i
intended
d d only
l to make
k the
h user aware off the
h most common
problems of materials incompatibility for a given application.
Page 45 of 152
M t i l S l ti
Material Selection –
W tt d P t 1
Wetted Parts‐1
• Type 316 L Stainless Steel.
The 316 L SST is the standard material for the wetted parts of transmitters, it has a good
resistance to corrosion,
corrosion including low concentrations of nitric acid and most salt solutions
with some exception like no oxidizing acids such as Hydrochloric, Hydrofluoric, Sulphuric
and Phosphoric. The resistance of 316 L SST to alkaline solutions, organic acids, and other
organic compounds may depend on temperature. Concerning salts, the halide salts
(fluorine chlorine,
(fluorine,
chlorine bromine,
bromine iodine) can cause severe pitting and possibly stress‐corrosion
stress corrosion
cracking. In case of Hydrogen Sulphide (H2S) that is often present in oil/gas production,
the 316 L SST may be available with a specific certificate: NACE MR0175, see the
applicable data sheets. This standard applies in case of sufficient partial pressure of H2S
in gas,
gas i.e.
i e as an example a total process pressure of 400 KPa and a concentration of H2S
at least above 700 PPM, or a process pressure of 26 MPa and a concentration of H2S
above 10 PPM. This standard assures the prevention of sulphide stress corrosion cracking,
by reducing the stress, i.e. by means of a low hardness of the construction material and a
suitable
it bl manufacturing
f t i process off the
th transmitter.
t
itt Non
N
wetted
tt d partt like
lik bolts
b lt are also
l
covered by this standard since they affect the effectiveness of containment of the whole
instrument even if they are exposed to H2S far below the limit of applicability of the
mentioned NACE standard. The NACE certificate is also available for Monel and Hastelloy
C For
C.
F UREA grade
d applications,a
li i
specific
ifi certificate
ifi
i available
is
il bl for
f 316 L SST:
SST ASTM A262,
A262
practice C, Huey test.
Page 46 of 152
M t i l S l ti
Material Selection –
W tt d P t 2
Wetted Parts‐2
• Monel (67Ni‐33Cu)
Monel (67Ni‐33Cu) has good resistance at ambient temperatures to most of the no oxidizing
acids,
id such
h as hydrofluoric,
h d fl i sulphuric,
l h i and
d phosphoric
h
h i acids.
id It
I also
l resists
i
no oxidizing
idi i
salts. The nickel in the alloy improves its resistance toward alkalises. Hydrogen may
penetrate Monel in high hydrogen concentration applications. When used as a diaphragm
material, hydrogen atoms may permeate the diaphragm allowing hydrogen bubbles to
form within the fill fluid. Therefore, Monel should not be used as a diaphragm material
when the process is hydrogen gas.
• Hastelloy C.
C
In Hastelloy C (54Ni‐16Mo‐16Cr), chromium and molybdenum are added to nickel to improve
the alloy’s resistance to oxidizing conditions. Hastelloy C is well suited to provide
protection against alkalises,
alkalises organic acids,
acids and other organic compounds.
compounds This alloy also
retains a considerable degree of resistance to no oxidizing conditions like Phosphoric acid
and also the acid salts such as Nickel and Copper chlorides. At moderate temperatures
Hastelloy C withstands Hydrochloric and sulphuric acids in most concentrations. Both
Monel and Hastelloy C have good corrosion resistance against atmospheric conditions
and fresh water. In addition, Hastelloy C is resistant to stagnant seawater.
Page 47 of 152
M t i l S l ti
Material Selection –
W tt d P t 3
Wetted Parts‐3
• Gold‐Plated Hastelloy C or Monel or SST
Hastelloyy C, like Monel and SST allows the p
permeation of Hydrogen
y g therefore avoided as a
diaphragm material for Hydrogen service. Indeed Hydrogen atoms can through the
transmitter diaphragms, which are very thin, once reached the fill fluid, combine to form
molecular hydrogen. Because molecular hydrogen is too large to back through the
diaphragm it gets trapped and forms bubbles in the fill fluid. These can severely affect
transmitter performance. Plating these materials’ diaphragm with gold provides
protection against hydrogen in all cases of high process pressure and temperature, which
increase the permeation Another form of protection is available from ABB: a hydrogen
preparation (corrosion gel), which is applied to the instrument’s diaphragm to reduce
Hydrogen permeation. Both these protections are not available for the single port family
off transmitter.
i
Page 48 of 152
M t i l S l ti
Material Selection –
W tt d P t 4
Wetted Parts‐4
• Tantalum
Tantalum has proved to be a useful material in corrosive applications where 316 L SST does
not perform
f
satisfactorily,
i f
il like
lik hydrochloric,
h d hl i hydrobromic,
h d b
i boiling
b ili
h d hl i nitric,
hydrochloric,
i i
phosphoric, and sulphuric acids. There are a few exceptions to this rule such as Aluminum
Fluoride, Potassium Carbonate and Sodium Sulphide, where Monel results more suitable.
Tantalum has also a good resistance to most acids, chemical solutions, and organic
compounds. Liquid metals generally do not affect Tantalum. However Tantalum can suffer
severe embrittlement if in service with high‐temperature oxygen or nitrogen, or with
hydrogen at any temperature. Also, it is attacked by strong alkaline solutions and by fused
alkalises
lk l
l k Sodium
like
d
Hydroxide.
d
d Tantalum
l
h a high
has
h h melting
l
point and
d good
d strength
h
even at elevated temperatures, this allows thin sections to be used since it is very
expensive.
• PFA (Teflon
(T fl from
f
D
Dupont)
)
ABB offers another unique solution to corrosive application. It coating of an AISI 316 L SS remote seal transmitter. The PFA outstanding and a coating of 0,2‐0,3 mm can solve severe corrosion costeffective way, i.e. without recurring to the use of more expensive metals. The only limitation is the maximum process temperature of 250 and a minimum increase of the temperature effect on accuracy.
Page 49 of 152
H
Housing
i
For marine environment there is a corrosion
risk,
i k related
l t d to
t the
th presence off chloride,
hl id an
place to an accelerated
ion that ggives p
galvanic corrosion of aluminum housing
because of the copper content of aluminum
alloy. In these cases it can be specified a low
copper content of aluminum, less than 0,1%.
Page 50 of 152
G k t
Gasket The most widespread material for the transmitter gasket is PTFE (Teflon) because of its general
gasket is PTFE (Teflon) because of its general corrosion suitability with several materials. A known limitation is in case of process which p
temperature can periodically vary of several degrees, compromising the tightness because g
p
g
g
of the limited elasticity of this material. Other special cases are the food or pharmaceutical applications that require an approved material listed by the American Food and Drug Administration (FDA) or other national d
(
)
h
l
equivalent bodies.
Page 51 of 152
T
Turn Down Ratio
D
R ti
The Turn Down Ratio of a transmitter is the ratio between its Upper Range Limit and the ti b t
it U
R
Li it d th
p
minimum recommended span. Some time it is also called rangeability. It represents the capability of the transmitter to cover several
capability of the transmitter to cover several pressure ranges, without deteriorating the transmitter performance: accuracy, etc.
Page 52 of 152
P t
Protocols l
• 4‐20 mA
• Hart
• ModBus
• ProfiBus
• Foundation FieldBus Page 53 of 152
Chapter 2
Presentation of Temperature
Transmitters
Page 54 of 152
Temperature Transmitters
Page 55 of 152
Table of Contents
Table of Contents
¾Transmitter Types
¾Sensors
¾Thermowells
Page 56 of 152
Transmitter Types
Transmitter Types
¾Head Mounted ¾Field Mounted ¾Rail Mounted ¾Non Contact
Page 57 of 152
Head Mounted Transmitters
Head Mounted Transmitters
•
2‐wire 4 20mA loop powered type or Fieldbus (PROFIBUS PA or FOUNDATION Fieldbus)
2‐wire 4...20mA loop powered type or Fieldbus (PROFIBUS PA or FOUNDATION Fieldbus)
•
Temperature linear output signals Custom linearization capabilities (user curve) •
Arithmetic calculations such as mean, differential etc.
•
Inputs can be RTD PT10 ....1000 or Different types of Thermo Couples Page 58 of 152
Field Mounted Transmitters
Field Mounted Transmitters
•
Same characteristic as Head mounted Types
Same characteristic as Head mounted Types
•
With Ex Housings •
With / Without Local indicator •
To be connected on Thermowells or Remote mounted on 2” Stand Pipe Page 59 of 152
Rail Mounted Transmitters
Rail Mounted Transmitters
•
Same characteristic as Head mounted Type
Same characteristic as Head mounted Type
•
Suitable for mounting in the panels Page 60 of 152
Non Contact Transmitters
Non Contact Transmitters •
•
•
•
Temp. measuring range
Temp
measuring range‐30
30...900 900 °C
C
Response time250 ms
Measured spot marking with laser spot Spectral d
ki
i hl
S
l
sensitifity8‐14 µm
Page 61 of 152
Sensors
• RTD RTD
Temperature range: – 200 … + 600 °C Measuring Element: PT100.....1000 (Ω) to DIN EN 60731 (IEC 755) 2,3 or 4 wire ‐
Single / Double Electrical Connection: Screw terminals (spring loaded)Flying leads, cables, plugs, head F
(p g
) y g
,
,p g ,
• Thermo‐couple
Thermo couple
Temperature range: Type J approx. 0 … 700 °C
Type K approx. 0 … 1100 °C
Measuring Element: Thermocouples single and duplex Type K J to DINEN 60584 (IEC584)
Measuring Element: Thermocouples, single and duplex, Type K, J to DINEN 60584 (IEC584)
Electrical Connection: Screw terminals (spring loaded)Flying leads, cables, plugs, head F Standard Material of Thermocouple: Type K:Inconel 600 or 310 Stainless Steel
Type J: 321 Stainless Steel Resistance thermometer: 321 Stainless Steel
Page 62 of 152
Thermowells Thermowells
Page 63 of 152
Chapter 3
Standards
Page 64 of 152
Chapter 3
Part 1
Engineering Standard For
Pressure and Temperature
Instruments
Page 65 of 152
Chapter 3
Part 2
Material Standard For
Pressure and Temperature
Instruments
Page 76 of 152
Chapter 4
Sample SPEC
Page 112 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
Specification for
Pressure Transmitters
PAGE
1
OF
7
SPECIFICATION FOR PRESSURE TRANSMITTERS
CHCE Document Number:
D1
Approved for Construction
D0
Issued for Review and Comment
REV.
PURPOSE OF ISSUE
PREPARED BY
REVIEWED BY
APPROVED BY
DATE
Page 113 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
Specification for
Pressure Transmitters
PAGE
2
OF
7
REVISION INDEX
0
X
X
X
X
X
X
X
1
X
X
X
X
X
X
X
2
3
PAGE
PAGE
1
2
3
4
5
6
7
OWNER / MC
CONTRACTOR
4
0
X
X
X
X
X
X
X
1
X
X
X
X
X
X
X
2
3
4
OWNER / MC
0
1
2
3
CONTRACTOR
4
0
1
2
3
4
THIS PAGE IS A RECORD OF ALL REVISIONS TO THIS DOCUMENT.
- REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION OF THE
REVISION. THESE REMARKS SHALL BE INTERPRETED IN CONJUNCTION WITH THE
REVISED TEXT MARKED BY REVISION NUMBERS.
- WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE
ORIGINAL DOCUMENT.
Page 114 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
REV.
PAGE
Specification for
Pressure Transmitters
3
OF
7
CONTENTS
SHEET No.
4
1-
SCOPE
2-
CONFLICTING REQUIREMENTS
4
3-
CODE AND STANDARDS
4
4-
DIFINITIONS AND TERMINOLOGIES
4~5
5-
TECHNICAL REQUIREMENTS
5~7
Page 115 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
Specification for
Pressure Transmitters
1.
REV.
PAGE
4
OF
7
SCOPE
The purpose of this specification together with data sheets and documents included in the
Material Requisition (MR) is to define the minimum requirements for design,
manufacture, supply, test & delivery of pressure transmitters for “AAAA" in the Persian
Gulf according to related standards, codes & the best engineering practices.
2.
CONFLICTING REQUIREMENTS
In the event of any conflict between this specification, related standards, codes, purchase
requisition, etc. the order of precedence will be as follows:
- Data sheets included in the MR
- This specification
- Codes and standards
3.
CODE AND STANDARDS
IPS-E-IN-110
IPS-M-IN-110
IPS-C-IN-110
API RP551
API PR554
NACE MR 01 75
ASME B 1.20.1
ASME B16.5
IEC 60-079
IEC 60-529
IEC 60-801
4.
Engineering standard for pressure instrument .
Material and equipment standard for pressure instrument.
Construction standard for pressure instrument.
Process measurement instrumentation
Process instrumentation
Standard Material Requirement: Sulfide stress cracking resistant
italic materials oilfield equipment.
Pipe thread, general purpose (Inch) revision and redesignation of
ASME/ANSI B2.1-1968 r (2001)
Pipe flange and flanged fittings
Electrical apparatus for explosive gas atmospheres
Classification of degrees of protection provided by enclosures
Electromagnetic compatibility for industrial-process measurement
and control equipment
DEFINITIONS AND TERMINOLOGIES
Owner:
Manufacturer:
Purchaser / Contractor:
Vendor / supplier :
Shall mean National Iranian Gas company.
Shall mean the party who manufactures the item of work.
Shall mean the parties which have contractual responsibility
for the design, engineering, procurement and construction of
the plant.
Shall mean company mentioned in the contract as supplying
any equipment in the project.
Page 116 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
Specification for
Pressure Transmitters
Shall :
Should:
Will :
May:
Must:
5.
REV.
PAGE
5
OF
7
Refers to a requirement
Refers to a recommendation
Refers to an action by the purchaser other than by the
vendor / supplier
Refers to one acceptable course of action.
Refers to a statutory requirement.
TECHNICAL REQUIREMENTS
5.1 The pressure element shall be AISI 316 stainless steel unless otherwise specified in data
sheets.
5.2 Sensing element fill-fluid shall be silicon oil. Fluorinate fluid may be used for special
services (when degrease cleansing treatment or both degrease cleansing and
dehydrating treatment for wetted parts is required) when specified in individual data
sheet.
5.3 The transmitter accuracy shall be equal or better than ±0.5% of calibrated span including
the effects of linearity, hystersis, And repeatability.
5.4 The transmitter shall be equipped with an integral indicator for maintenance purpose.
Integral output meter shall have LCD display and indicate engineering units on linear
scale.
5.5 Transmitters output signal shall be immune from Radio Frequency Interference (RFI) and
Electro Magnetic Interference (EMI). Such that no change in reading or status occurs,
when a UHF 6 watt walkie-talkie, wireless paging system and other communication
equipment are held in close proximity with the instrument covers recomved.
5.6 Enclosure housing (electronic) shall conform with IEC 529/IP 65. For classified area, all
transmitters shall be intrinsically safe for use in zone2, Gas Group IIB, Temperature class
T3 as minimum and certified by acceptable association, such as BASSEEFA according to
the CENELEC standard.
5.7 Instrument case and cover shall be made of high resistance material such as low copper
die – cast aluminum .
5.8 Process connection shall be ½" NPTF, unless specified otherwise. Connection shall be
provided where diaphragm seal type instruments are specified. The type, material and
rating of the flange shall be specified in the data sheets.
Page 117 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
REV.
Specification for
Pressure Transmitters
PAGE
6
OF
7
5.9 Electrical entrance to the transmitter shall be made by means of ISO M20×1.5 cable
glands unless otherwise specified.
5.10 Mounting of the transmitter shall be implemented by means of DN50 (2") vertical or
horizontal pipe bracket. All mounting accessories made of 316 stainless steel shall be
provided with the instrument.
5.11 The transmitter shall be supplied with a stainless steel nameplate fastened to the
instrument by S.S. 316 screws.
The following information shall be engraved on the nameplate:
-
Instrument tag-number.
Manufacturer’s name, model and serial number.
Pressure rating of pressure holding parts.
Electrical classification certificate code and certifying organization.
Operating range.
Calibrated range.
5.12 Pressure elements shall be furnished with overrange protection to at least 1.5 times the
maximum range of the instrument , and elements in vacuum service shall be capable of
withstanding full vacuum .
5.13 Pressure Transmitters shall be used for all control applications . Transmitters shall be
programmable HART smart 4-20 output .
5.14 Pressure range of transmitters shall be selected so that , normal operating pressure will
be within 50% and 85% of calibrated range.
5.15 For corrosive services, wetted parts shall meet the requirements of NACE standard MR01-75. (Latest edition)
5.16 All martial supplied under this specification shall be adequate for the proposed services.
Proper consideration shall be given to their function with regard to the environmental
conditions, corrosion, chemical and process hazard.
5.17 Vendor shall comply in totality with data sheets included in the Material Requisition.
The vendor is requested to fill in the relevant sections / lines in the data sheets and
submit the completed data sheets with his quotation for review and evaluation.
5.18 Electronic components of field transmitters shall be tropicalised.
Page 118 of 152
OWNER:
MC:
DOCUMENT TITLE
Specification for
Pressure Transmitters
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
REV.
PAGE
7
OF
7
5.19 Transmitters shall be provided with open circuit (sensor failure) protection and shall
give upscale indication for all failures.
5.20 international System of Units (SI) shall be used for the whole project, engineering
calculation results, instrument ranges and control signals. All dimension and ratings shall
be metric except for pipes and fittings threads, which shall be in inches.
5.21 For transmitters subject to the corrosive or viscous fluids, chemical diaphragm seals
integral with the instrument shall be sued, the sealing liquid shall be compatible with the
process fluid temperature. (If specified in relevant data sheet).
5.22 Pressure transmitters shall be fitted with 2-valve manifolds made of 316 stainless steel
material as minimum.
Page 119 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
Specification for Differential Pressure
Transmitters (Level & Flow)
PAGE
1
OF
7
SPECIFICATION FOR DIFFERENTIAL PRESSURE TRANSMITTERS
(LEVEL & FLOW)
CHCE Document Number:
D1
Approved for Construction
D0
Issued for Review and Comment
REV.
PURPOSE OF ISSUE
PREPARED BY
REVIEWED BY
APPROVED BY
DATE
REVISION INDEX
Page 120 of 152
OWNER:
MC:
PROJECT:
CONTRACTOR:
DOCUMENT TITLE
DOCUMENT NUMBER
REV.
Specification for Differential Pressure
Transmitters (Level & Flow)
2
OWNER / MC
0
X
X
X
X
X
X
X
1
X
X
X
X
X
X
X
2
3
PAGE
PAGE
1
2
3
4
5
6
7
CONTRACTOR
4
PAGE
0
X
X
X
X
X
X
X
1
X
X
X
X
X
X
X
2
3
4
OWNER / MC
0
1
2
3
OF
7
CONTRACTOR
4
0
1
2
3
4
THIS PAGE IS A RECORD OF ALL REVISIONS TO THIS DOCUMENT.
- REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION OF THE
REVISION. THESE REMARKS SHALL BE INTERPRETED IN CONJUNCTION WITH THE
REVISED TEXT MARKED BY REVISION NUMBERS.
- WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE
ORIGINAL DOCUMENT.
Page 121 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
REV.
PAGE
Specification for Differential Pressure
Transmitters (Level & Flow)
3
OF
7
CONTENTS
SHEET No.
4
1-
SCOPE
2-
CONFLICTING REQUIREMENTS
4
3-
CODE AND STANDARDS
4
4-
DIFINITIONS AND TERMINOLOGIES
4~5
5-
TECHNICAL REQUIREMENTS
5~7
Page 122 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
Specification for Differential Pressure
Transmitters (Level & Flow)
1.
REV.
PAGE
4
OF
7
SCOPE
The purpose of this specification together with the data sheets and other documents
included in the Material Requisition (MR) is to define the minimum requirements for
design, manufacture, supply, test & delivery of differential pressure transmitters (level &
flow) for “AAAA”
according to related standards, codes & the best engineering
practices.
2.
CONFLICTING REQUIREMENTS
In the event of any conflict between this specification, related standards, codes, purchase
requisition, etc. the order of precedence shall be as follows:
- Data sheets included in the MR.
- This specification
- Codes and standards
3.
CODES AND STANEDARDS
IPS-E-IN-110
IPS-M-IN-110
IPS-C-IN-110
API RP 551
API RP 554
NACE MR 01 75
ASME B 1.20.1
ASME B16.5
IEC 60-079
IEC 60-529
IEC 60-801
4.
Engineering standard for pressure instrument .
Material and equipment standard for pressure instrument.
Construction standard for pressure instrument.
Process measurement instrumentation
Process instrumentation
Standard Material Requirement : Sulfide stress cracking resistant
metallic materials oilfield equipment.
Pipe thread, general purpose (Inch) revision and redesignation of
ASME/ANSI B2.1-1968 r (2001)
Pipe flange and flanged fittings
Electrical apparatus for explosive gas atmospheres
Classification of degrees of protection provided by enclosures
Electromagnetic compatibility for industrial-process measurement
and control equipment
DEFINITIONS AND TERMINOLOGIES
Owner:
Manufacturer:
Purchaser / Contractor:
Shall mean National Iranian Gas Company.
Shall mean the party who manufactures the item of work.
Shall mean the parties which have contractual responsibility
for the design, engineering, procurement and construction of
the plant.
Page 123 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
Specification for Differential Pressure
Transmitters (Level & Flow)
Vendor / supplier :
Shall :
Should:
Will :
May:
Must:
5.
REV.
PAGE
5
OF
7
Shall mean company mentioned in the contract as supplying
any equipment in the project.
Refers to a requirement
Refers to a recommendation
Refers to an action by the purchaser other than by the
vendor / supplier
Refers to one acceptable course of action.
Refers to a statutory requirement.
TECHNICAL REQUIREMENTS
5.1.
The pressure element shall be AISI 316 stainless steel unless otherwise specified in data
sheets.
5.2.
Sensing element fill-fluid shall be silicon oil. Fluorinate fluid may be used for special
services (when degrease cleansing treatment or both degrease cleansing and dehydrating
treatment for the wetted parts is required) when specified in individual data sheet.
5.3.
The transmitter accuracy shall be equal or better than 0.5% of calibrated span including
the effects of linearity, hystersis, And repeatability.
5.4.
Transmitters output signal shall be immune from Radio Frequency Interference (RFI)
and Electro Magnetic Interference (EMI), such that no change in reading or status
occures, when a UHF 6watt walkie-talkie, wireless paging system and other
communication equipment are held in close proximity with the instrument covers
removed.
5.5.
Enclosure housing (electronic) shall conform with IEC 529/IP 65. For classified area all
transmitters shall be intrinsically safe for use in zone 2, Gas Group IIB, Temperature
class T3 as minimum and certified by acceptable association, such as BASSEEFA
according to the CENELEC standard.
5.6.
Instrument case and cover shall be made of high resistance material such as low copper
die – cast aluminum.
5.7.
Process connection shall be ½" NPTF unless specified otherwise. Process connection
shall be 3” flanged for diaphragm sealed with capillary type level transmitters. Material
and rating shall be as per data sheet.
5.8.
Electrical entrance to the transmitter shall be made by means of ISO M20×1.5 cable
glands.
Page 124 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
REV.
Specification for Differential Pressure
Transmitters (Level & Flow)
PAGE
6
OF
7
5.9.
Mounting of the transmitter shall be implemented by means of DN50 (2") vertical or
horizontal pipe bracket. All mounting accessories made of 316 stainless steel shall be
provided with the instrument.
5.10.
The transmitter shall be supplied with a stainless steel nameplate fastened to the
instrument by S.S. 316 screws.
The following information shall be engraved on the nameplate:
-
Instrument tag-number.
Manufacturer’s name, model and serial number.
Pressure rating of pressure holding parts.
Electrical classification certificate code and certifying organization.
Operating range.
Calibrated range.
5.11.
For differential pressure transmitters over-range pressure protection shall be able to
protect the sensing element from the maximum design pressure applied to each side with
the opposite side vented to atmosphere.
5.12.
Zero elevation / suppression shall be provided for differential pressure type transmitters
used for level measurement.
5.13.
For flow transmitters square root extraction shall be carried out with in the transmitter.
5.14.
The output signal of the transmitter shall be electronic type with HART smart 4-20 mA.
5.15.
Measuring elements must be capable of withstanding pressure up to that of the body
rating in either direction with neither damage nor zero shift greater than 1% of the span
resulting.
5.16.
For corrosive services, wetted parts shall meet the requirements of NACE standard
MR-01-75. (Latest edition)
5.17.
All material supplied under this specification shall be adequate for the proposed services.
Proper consideration shall be given to their function with regard to the environmental
conditions, corrosion, chemical and process hazard.
5.18.
Vendor shall comply in totality with data sheets included in the Material Requisition the
vendor is requested to fill in the relevant sections/lines in the data sheets and submit the
completed data sheets with his quotation for review and evaluation.
Page 125 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
Specification for Differential Pressure
Transmitters (Level & Flow)
REV.
PAGE
7
OF
7
5.19.
Flow transmitters shall be provided with integral square root extraction and an integral
out put meter (LCD meter).
5.20.
Differential pressure transmitters shall be as flow transmitters, without the square root
extraction function but with an integral output meter showing a linear scale.
5.21.
Sensing devices that measure differential pressure shall have rupture proof liquid filled
diaphragms. The devices shall be temperature compensated with adjustable dampening
and over range protection to full working pressure of the housing.
5.22.
Electronic components of filed transmitters shall be tropicalized.
5.23.
Transmitter shall be provided with open circuit (sensor failure) protection and shall give
upscale indication for all failures.
5.24.
International System of Units (SI) shall be used for the whole project, engineering
calculation results, instrument ranges and control signals. All dimension and ratings shall
be metric except for pipes and fittings threads, which shall be in inches.
5.25.
For transmitters subject to the corrosive or viscous fluids, chemical diaphragm seals
integral with the instrument shall be sued, the sealing liquid shall be compatible with the
process fluid temperature. (If specified in relevant data sheet).
5.26.
All differential pressure transmitters shall be provided with 5-valve manifolds made of
316 stainless steel as minimum.
5.27.
Ambient temperature effects on all measuring elements shall be kept to a minimum.
5.28.
Diaphragms , range springs , etc. of all measuring elements shall have a minimum
thermoplastic coefficient.
Page 126 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
PAGE
1
OF
8
SPECIFICATION FOR TEMPERATURE TRANSMITTERS
CHCE Document Number:
D1
Approved for Construction
D0
Issued for Review and Comment
REV.
PURPOSE OF ISSUE
PREPARED BY
REVIEWED BY
APPROVED BY
DATE
Page 127 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
PAGE
2
OF
8
REVISION INDEX
0
X
X
X
X
X
X
X
X
1
X
X
X
X
X
X
X
X
2
3
PAGE
PAGE
1
2
3
4
5
6
7
8
OWNER / MC
CONTRACTOR
4
0
X
X
X
X
X
X
X
X
1
X
X
X
X
X
X
X
X
2
3
4
OWNER / MC
0
1
2
3
CONTRACTOR
4
0
1
2
3
4
THIS PAGE IS A RECORD OF ALL REVISIONS TO THIS DOCUMENT.
- REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION OF THE
REVISION. THESE REMARKS SHALL BE INTERPRETED IN CONJUNCTION WITH THE
REVISED TEXT MARKED BY REVISION NUMBERS.
- WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE
ORIGINAL DOCUMENT.
Page 128 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
PAGE
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
3
OF
8
CONTENTS
SHEET No.
4
1-
SCOPE
2-
CONFLICTING REQUIREMENTS
4
3-
CODES AND STANDARDS
4
4-
DIFINITIONS AND TERMINOLOGIES
5
5-
GENERAL SPECIFICATION
4~5
6-
THERMAL ELEMENTS
6
7-
THERMOWELLS
6
8-
TRANSMITTERS
7~8
Page 129 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
1.
REV.
PAGE
4
OF
8
SCOPE
The purpose of this specification together with data sheets and documents included in the
Material Requisition (MR) is to define the minimum requirements for design,
manufacture, supply, test & delivery of temperature transmitters for “AAAA”according
to related standards, codes & the best engineering practices.
2.
CONFLICTING REQUIREMENTS
In the event of any conflict between this specification, related standards, codes, purchase
requisition, etc. the order of precedence shall be as follows:
- Data sheets included in the Material Requisition.
- This specification
- Codes and Standards
3.
CODES AND STANDARDS
IPS-E-IN-120
IPS-M-IN-120
IPS-C-IN-120
API RP 551
API PR 554
NACE MR 01 75
ASME B16.5
ASME B1.20.1
ASME PTC 19.3
BS 1904
BS 2765
BS 6527
IEC 60-079
IEC 60-529
IEC 60-751
Engineering standard for temperature instrument.
Material and equipment standard for temperature instrument
Construction standard for temperature instrument
Process measurement instrumentation
Process instrumentation
Standard Material Requirement: Sulfide stress cracking resistant
metallic materials oilfield equipment.
Pipe flange and flanged fittings
Pipe thread, general purpose (Inch) revision and redesignation of
ASME/ANSI B2.1-1968 r (2001)
Temperature measurement instrument and apparatus
Specification for industrial platinum resistance thermometers
sensors
Specification for dimensions of temperature detecting elements
and corresponding pockets
Limits and methods of measurement of radio interference
characteristic information technology equipment
Electrical apparatus for exclusive gas atmospheres
Classification of degrees of protection provided by enclosures
Industrial platinum resistance thermometers sensors
Page 130 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
4.
PAGE
5
OF
8
DEFINITIONS AND TERMINOLOGIES
Owner:
Manufacturer:
Purchaser / Contractor:
Vendor / supplier :
Shall :
Should:
Will :
May:
Must:
5.
REV.
Shall mean National Iranian Gas Company .
Shall mean the party who manufactures the item of work.
Shall mean the parties which have contractual responsibility
for the design, engineering, procurement and construction of
the plant.
Shall mean company mentioned in the contract as supplying
any equipment in the project.
Refers to a requirement
Refers to a recommendation
Refers to an action by the purchaser other than by the
vendor / supplier
Refers to one acceptable course of action.
Refers to a statutory requirement.
GENERAL SPECIFICAITON
5.1 Enclosure housing (electronic) shall conform with IEC 529/ IP65. For classified area all
transmitters shall be intrinsically safe for use in zone 2, Gas Group IIB, Temperature
class T3 as minimum and certified by acceptable association, such as BASEEFA
according to the CENELEC standard.
5.2 For the measurement of fluid temperature below 0°C , the length of the heads extension
shall suit the insulating thickness but the head shall extend at least 200mm outside the
insulation.
5.3 For corrosive services, wetted parts shall meet the requirements of NACE standard MR01-75.
5.4 All material supplied under this specification shall be adequate for the proposed services.
Proper consideration shall be given to their function with regard to the environmental
conditions, corrosion, chemical attack, electrical and process hazard.
5.5 Vendor shall comply in totality with data sheets included in the MR. The vendor is
requested to fill in the relevant sections / lines in the data sheets and submit the
completed data sheets with his quotation for review and evaluation.
5.6 All threaded connection shall be NPT to ASME B1.20.1 and flanged connections shall
be to ASME B16.5 .
Page 131 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
PAGE
6
OF
8
5.7 Electrical connection to be M20 x 1.5 ISO (F).
5.8 International system of units (SI) shall be used for the whole project, engineering
calculation results, instrument ranges and control signals. All dimension and ratings
shall be metric, except for pipes and fittings threads, which shall be in inches and for
temperature defined in degree Celsius instead of Kelvin.
5.9 Thermo well connection shall be flange type with connection size of 2" . Flange shall be
in accordance with the relevant piping class, but minimum ANSI 300#.
6.
THERMAL ELEMENTS
6.1
The junction of thermo element shall be in contact with the thermowell to minimize the
transfer lag.
6.2
Spring loaded sensor shall be used, with mineral insulation, stainless steel sheath and
calibrated as per IEC 60-751.
6.3
RTDs shall be ground insulated type.
6.4
The used of RTD’s shall normally be limited to the Range of - 200˚C to 750˚C .
6.5
RTD’ s shall be platinum preferably 3 wire .
6.6
RTD’s Pt100 shall comply with BS 1904 and have a Resistance of 100 ohms at 0˚C and a
fundamental interval of 38 ohms . They shall be of the grade of accuracy appropriate to
the application .
7.
THERMOWELLS
7.1 ½ " NPT screwed type thermowell shall be used for connection of RTD to the well.
7.2 The thermowell shall be fabricated from solid bar stock in a tapered configuration. The
bore shall be concentric 10% of wall thickness. Thermowell material shall be stainless
steel as a minimum, where the nature of fluid requires a higher alloy or other material,
the thermowell material shall be consistent with the piping or equipment specification.
7.3 The well shall withstand a hydrostatic test pressure according to the flange rating.
Page 132 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
REV.
PAGE
7
OF
8
7.4 Thermowells for test points shall be provided with plug and stainless steel chain attached
to the head.
7.5 The wake frequency shall not exceed 80% of the natural frequency of the thermowell.
Calculation shall be provided for all non-standard lengths, as per ASME PTC 19.3 in
high velocity lines.
7.6 Where high velocity gases are present, it will be necessary to check thermowell for
"Vortex shedding effect".
7.7 Each thermo well shall be stamped with relevant instrument Tag No. material and
nominal “U” dimension with a letter size of 5mm. Nominal flange size, rating and
material shall be clearly stamped on the thermowell flange at a visible place.
8.
TRANSMITTERS
8.1
Galvanic ally isolation between input and output and ground shall be provided.
8.2
Transmitters shall be Two wire suitable for connection to PT-100 RTD sensor, which
may be used for temperature measurement in the range of -200°C to 750°C.
8.3
All transmitters shall have reverse polarity protection.
8.4
The transmitter accuracy shall be equal or better than ±0.5% of calibrated span including
the effects of linearity, hystersis, and repeatability.
8.5
Transmitters shall be equipped with the stainless steel name plate, permanently attached
to them with the following engraved data :
a.
b.
c.
d.
e.
f.
Instrument tag no.
Manufacturer’s serial no. model no.
Temperature range
Max working temperature
Over range protection temperature
Hazardous Area Certification
8.6
The transmitter shall be equipped with an integral indicator, having LCD display.
8.7
Head mounted temperature transmitters shall be used for all control applications
transmitters shall be programmable HART smart 4-20 mA output .
Page 133 of 152
OWNER:
MC:
DOCUMENT TITLE
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
SPECIFICATION FOR
TEMPERATURE TRANSMITTERS
REV.
PAGE
8
OF
8
8.8
Transmitters output signal shall be immune from Radio Frequency Interference (RFI) and
Electron Magnetic Interference (EMI), such that no change in reading or status occurs,
when a UHF 6 watt walkie-talkie, wireless paging system and other communication
equipment are held in close proximity with the instrument covers removed.
8.9
Electronic components of field transmitters shall be tropicalized.
8.10
Transmitters shall be provided with open circuit (sensor failure) protection and shall give
up scale indication for all failures.
8.11
Temperature transmitters shall in general be integrally (head). Complete assembly of
temperature transmitter and RTD plus thermowell shall be provided by vendor.
8.12
Transmitters case and cover shall be made of high resistance material such as low copper
die-cast aluminum.
Page 134 of 152
Chapter 5
Sample Datasheet
Page 135 of 152
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
PAGE
Data Sheet for
1
Diffrential Pressure Transmitters
OF 8
DATA SHEET FOR DIFFERENTIAL PRESSURE TRANSMITTERS
QTY: 12
CHCE Document Number:
D1
Approved for Construction
D0
Issued for Approval
Rev.
PURPOSE OF ISSUE
PREPARED BY
REVIEWED BY
APPROVED BY
DATE
Page 136 of 152
OWNER:
MC:
PROJECT:
CONTRACTOR:
DOCUMENT TITLE
DOCUMENT NUMBER
REV.
PAGE
DATA SHEET F0R
Diffrential Pressure Transmitters
2
OF
8
REVISION INDEX
0
1
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2
3
PAGE
PAGE
1
2
3
4
5
6
7
8
OWNER / MC
CONTRACTOR
4
0
1
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
2
3
4
OWNER / MC
0
1
2
3
CONTRACTOR
4
0
1
2
3
4
THIS PAGE IS A RECORD OF ALL REVISIONS TO THIS DOCUMENT.
- REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION OF THE REVISION. THESE REMARKS
SHALL BE INTERPRETED IN CONJUNCTION WITH THE REVISED TEXT MARKED BY REVISION NUMBERS.
- WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE ORIGINAL DOCUMENT.
Page 137 of 152
SHEET 3
PROJECT:
DATA SHEET FOR DIFFERENTIAL
DOC. NO.
PRESSURETRANSMITTERS
NO
BY
DATE
OF 8
REVISON
1
2
CONTRACT
REQ.
BY
1
Tag No.
XMTR
(Note 1) Control
Record
3 Case
MFR STD
Nom Size
4 Mounting
Flush
Surface
5 Enclosure Class
General Purpose
Indicate
Blind
Transnsmitter
CHK'D
APPR.
117 V 60 Hz
Other ac
7 Chart
12 in. Cire.
24hr
Other
Explosion-Proof
9 Scale
Type
10 Trans. Output
4-20mA
Elec.
Other
2
3
21-10 kpa(3-15 psig)
For Receiver see Spec sheet.
Class IP65
Volts 24VDC
Range
Spring
Range: 1
10-50mA
Other
Other Note 2
dc
Other
Integ
Other on 2" pipe
Yoke
Weather Proof
6 Power Supply
11 Control Modes
P.O.
Material low copper die -cast aluminium
Color: MFR STD
For use in Intrinsically Safe System
8 Chart Drive
DATE
Service
2 Function
GENERAL
REV.
No.
Other
Note3
P= Prop(Gain.), I= Integral (Auto Reset), D=Derivative (Rate)
Sub: s= Slow f= Fast
If
Df
P
PI
PD
PID
Is
Ds
Other
CONTROLLER
UNIT
12 Action
13 Auto-Man Switch
On Meas. Increase Output: Increases
None
MFR STD
Other
14 Set Point Adj.
15 Manual Reg.
None
MFR STD
Other
16 Output
4-20mA
17 Service
18 Element Type
Flow
19 Material
20 Rating
316 S.S.
21 Diff. Range
22
Fixed
10-50mA
21-10 kpa(3-15 psig)
Level
Diaphragm
Overrange
Decreases
Bellows
Mercury
1.5 times of design perssure
Elevation
25 Alarm Switches
26 Function
Quantity
27 Options
Pressure Elements
Max Temp.
Form
Deviation
Max. Press.
Rating
Contacts To
Renge
Temp. Element
Cond. Pots
psig
Other Bottom
Meas. Var.
Filt Reg.
Body Rating (NOTE 4)
Suppression
Fluid See Next Sheet
Valve Manifold
Other
Other
Set At (See Next Sheet)
23 Process Data
24 Process Conn.
½ in. NPT
Other
Diff. Press
Range
Sup. Gage
On Inc. Meas.:
Material
Type
Output Gage
Charts
five way with 316ss materail , min cwp =3000
Adj. Damp
Integral Sq. Rt. Ext .
Integrator
Other 2"S.S. pipe bracket with S.S. Ubolts, 5 Valve manifold (316 S.S 1/4" Vent & Drain NPTF).
28 MFR. & Model No.
Notes:
1. Indicator with 0- √10 scale for flow transmitters.
2. Enclosure shall be suitable for use in zone 2, EExi, IIB, T3 and ingress protection shall be IP65.
3. Electrical entrance to the transmitter shall be of ISO M20 x 1.5 and cable gland will be supplied by others.
4. PD Transmitters shall withstand the max. static pressure .
5.The transmitter accuracy shall be equal or better than 0.5%of full span.
Page 138 of 152
.
DATA SHEET FOR
DIFFERENTIAL
PRESSURETRANSMITTERS
PROJECT :
NO
BY
1
D0
SHEET
4
OF 8
DOC. NO.
REV.
REVISON
CONTRACT
DATE
2
REQ.
BY
Rev. Tag. No.
FT-1020
FT-1090
FT-1092
FT-1120
FT-1150
Operating/
Set Range mm
Design Press.
H2O
Kg/cm²g
0-5000
0-1250
0-1250
0-2500
0-2500
120.5 / 160
74 / 81.4
74 / 81.4
22 / 24.2
6.0 /8.0
Design
Temp. ˚C
-13/85
-13/80
-13/84.2
-13/110
-13/150.4
Operating
Temp. ˚C
Service/Line No.
60.0
-0.4
59.2
85
125.4
(HC/TWO PHASE)GAS-001-C15-10"-PT
(HC/TWO PHASE)CON-008-C6A-3"-PT
(HC/TWO PHASE)CON-006-C9A-6"-PT
(HC/TWO PHASE)CON-068-C3A-4"-1H
(HC/LIQUID) CON-034-C1A-4"-PT
P.O.
CHK'D
APPR.
P&ID No.
Notes
Page 139 of 152
SHEET 5 OF 8
DATA SHEET FOR
DIFFERENTIAL
DOC. NO.
PRESSURETRANSMITTERS
NO
BY
DATE
REVISON
PROJECT:
1
REV.
CONTRACT
DATE
2
BY
1
Tag No.
XMTR
APPR.
Service
(Note 1) Control
2 Function
Record
3 Case
MFR STD
Nom Size
4 Mounting
Flush
Surface
5 Enclosure Class
General Purpose
GENERAL
CHK'D
Indicate
Blind
Transnsmitter
Color: MFR STD
Material
Yoke
Other on 2" pipe
Weather Proof
Explosion-Proof
117 V 60 Hz
Other ac
7 Chart
12 in. Cire.
Other
8 Chart Drive
24hr
9 Scale
Type
10 Trans. Output
4-20mA
Range
Elec.
No.
Spring
Range: 1
10-50mA
Class IP65
Volts 24VDC
dc
Other
Other
Other Note 2
For use in Intrinsically Safe System
6 Power Supply
Integ
low copper die-cast aluminium
Other
2
21-10 kpa(3-15 psig)
3
Other
For Receiver see Spec sheet. Note 3
11 Control Modes
P= Prop(Gain.), I= Integral (Auto Reset), D=Derivative (Rate)
Sub: s= Slow f= Fast
If
Df
P
PI
PD
PID
Is
Ds
Other
CONTROLLER
UNIT
12 Action
13 Auto-Man Switch
On Meas. Increase Output: Increases
None
MFR STD
Other
14 Set Point Adj.
15 Manual Reg.
None
MFR STD
Other
16 Output
4-20mA
17 Service
18 Element Type
Flow
19 Material
20 Rating
316 S.S.
21 Diff. Range
22
Fixed
23 Process Data
24 Process Conn.
10-50mA
21-10 kpa(3-15 psig)
Level
Diaphragm
Overrange
Decreases
Bellows
Mercury
1.5 times of design perssure
Elevation
27 Options
Pressure Elements
Meas. Var.
Max Temp.
Form
Deviation
Max. Press.
Rating
Contacts To
Renge
Temp. Element
Cond. Pots
psig
Other Bottom
Quantity
Valve Manifold
Body Rating (NOTE 4)
Suppression
25 Alarm Switches
26 Function
Filt Reg.
Other
Other
Set At (See Next Sheet)
Fluid See Next Sheet
½ in. NPT
Other
Diff. Press
Range
Sup. Gage
On Inc. Meas.:
Material
Type
Output Gage
Charts
five way with 316ss materail , min cwp =3000
Adj. Damp
Integral Sq. Rt. Ext .
Other 2"S.S. pipe bracket with S.S. Ubolts, 5 Valve manifold (316 S.S 1/4" Vent & Drain NPTF).
28 MFR. & Model No.
Notes:
1. Integral output meter shall have LCD display and indicate engineering units on linear scale .
2. Enclosure shall be suitable for use in zone 2, EExi, IIB, T3 and ingress protection shall be IP65.
3. Electrical entrance to the transmitter shall be of ISO M20 x 1.5 and cable gland will be supplied by others.
4. PD Transmitters shall withstand the max. static pressure .
5.The transmitter accuracy shall be equal or better than 0.5% of full span.
Page 140 of 152
DATA SHEET FOR DIFFERENTIAL
PRESSURETRANSMITTERS
PROJECT :
BY
NO
D0
SHEET
6
OF 8
DOC. NO.
REV.
REVISON
CONTRACT
1
DATE
2
REQ.
BY
Rev.
Tag. No.
Operating/
Set Range mm
Design Press.
H2O
Kg/cm²g
Design
Temp. ˚C
Operating
Temp. ˚C
Service/Line No.
LT-1030
800
120/160
-13/85
60
V-100 HC/LIQUID
LT-1090
800
74 / 81.4
-13/80
49.8
V-201 HC/LIQUID
27.7
V-202 HC/LIQUID
LT-1100
850
14/16
-13/80
D2
LT-1120
1700
4.5/6.5
-13/150
125
T-200 HC/TWO PHASE
D2
LT-1130
1350
16/18
-13/80
20.6
V-301 HC/LIQUID
LT-1170
1700
3/5
-49/80
AMB/-44
V-405 CH/LIQUID
LT-1301
10500
ATM/3.5
80
45
TK-902
P.O.
CHK'D
P&ID No.
APPR.
Notes
DELETED
Page 141 of 152
DATA SHEET FOR DIFFERENTIAL SHEET 7
DOC. NO.
PRESSURETRANSMITTERS
PROJECT:
NO
BY
DATE
OF 8
1
2
CONTRACT
BY
1
Tag No.
XMTR
DATE
CHK'D
APPR.
Service
(Note 1) Control
2 Function
Record
3 Case
MFR STD
Nom Size
4 Mounting
Flush
Surface
5 Enclosure Class
General Purpose
GENERAL
REV.
REVISON
Indicate
Blind
Transnsmitter
Explosion-Proof
117 V 60 Hz
Other ac
Other
8 Chart Drive
12 in. Cire.
24hr
9 Scale
Type
10 Trans. Output
4-20mA Volts 24VDC
dc
Other
Elec.
Range
Spring
Other
2
3
Range: 1
10-50mA
Class IP65
Other Note 2
For use in Intrinsically Safe System
7 Chart
Other
Other on 2" pipe
Yoke
Weather Proof
6 Power Supply
Integ
Material low copper die-cast aluminium
Color: MFR STD
21-10 kpa(3-15 psig)
No.
Other
For Receiver see Spec sheet. Note3
11 Control Modes
P= Prop(Gain.), I= Integral (Auto Reset), D=Derivative (Rate)
Sub: s= Slow f= Fast
If
Df
P
PI
PD
PID
Is
Ds
Other
CONTROLLER
UNIT
On Meas. Increase Output: Increases
12 Action
13 Auto-Man Switch
None
MFR STD
Other
14 Set Point Adj.
15 Manual Reg.
None
MFR STD
Other
16 Output
4-20mA
17 Service
18 Element Type
Flow
19 Material
20 Rating
316 S.S.
21 Diff. Range
22
Fixed
23 Process Data
24 Process Conn.
10-50mA
21-10 kpa(3-15 psig)
Level
Diaphragm
Overrange
Decreases
Bellows
Mercury
1.5 times of design perssure
Quantity
27 Options
Pressure Elements
Meas. Var.
Max Temp.
Form
Deviation
Max. Press.
Rating
Contacts To
Renge
Temp. Element
Cond. Pots
psig
Other Bottom
25 Alarm Switches
26 Function
Filt Reg.
Body Rating (NOTE 4)
Suppression
Fluid See Next Sheet
Valve Manifold
Other
Other
Set At (See Next Sheet)
Elevation
½ in. NPT
Other
Diff. Press
Range
Sup. Gage
On Inc. Meas.:
Material
Type
Output Gage
Charts
five way with 316ss materail , min cwp =3000
Adj. Damp
Integral Sq. Rt. Ext .
Integrator
Other 2"S.S. pipe bracket with S.S. Ubolts, 5 Valve manifold (316 S.S 1/4" Vent & Drain NPTF).
28 MFR. & Model No.
Notes:
1. Integral output meter shall have LCD display and indicate engineering units on linear scale .
2. Enclosure shall be suitable for use in zone 2, EExi, IIB, T3 and ingress protection shall be IP65.
3. Electrical entrance to the transmitter shall be ISO M20 x 1.5 and cable gland will be supplied by others.
4. PD Transmitters shall withstand the max. static pressure .
5.The transmitter accuracy shall be equal or better than 0.5% of full span.
Page 142 of 152
.
DATA SHEET FOR DIFFERENTIAL SHEET 8
DOC. NO.
PRESSURETRANSMITTERS
PROJECT :
NO
BY
1
DATE
OF 8
REV.
REVISON
CONTRACT
DATE
2
REQ.
BY
Rev. Tag. No.
PDT-1120
Diff.
Range
Barg
Operating
Diff. Press
Barg
Operating
Press.
Barg
0-2.4
1.2
4.5
Design
Press.Of
Service (R1)
Barg
6.5
Design
Temp.Of
Service (R1)
˚C
-13/150
Service/Linc No
P.O.
CHK'D
P&ID No.
(HC/VAPOUR) / T-200
Notes :
Page 143 of 152
APPR.
Notes
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
Data Sheet for Temperature
Transmitters
CONTRACTOR:
DOCUMENT NUMBER
REV.
PAGE
1
OF 4
DATA SHEET FOR
TEMPERATURE TRANSMITTERS
QTY: 18
CHCE Document Number:
D1
Approved for Construction
D0
Issued for Approval
B0
Issued for Approval
Rev.
PURPOSE OF ISSUE
PREPARED BY
REVIEWED BY
APPROVED BY
DATE
Page 144 of 152
OWNER:
MC:
PROJECT:
CONTRACTOR:
DOCUMENT TITLE
DOCUMENT NUMBER
REV.
PAGE
Data Sheet For Temperature
Transmitters
2
OF 4
REVISION INDEX
0
1
X
X
X
X
X
X
X
X
2
3
PAGE
PAGE
1
2
3
4
OWNER / MC
CONTRACTOR
4
0
1
X
X
X
X
X
X
X
X
2
3
4
OWNER / MC
0
1
2
3
CONTRACTOR
4
0
1
2
3
THIS PAGE IS A RECORD OF ALL REVISIONS TO THIS DOCUMENT.
- REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION OF THE REVISION. THESE REMARKS
SHALL BE INTERPRETED IN CONJUNCTION WITH THE REVISED TEXT MARKED BY REVISION NUMBERS.
- WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE ORIGINAL DOCUMENT.
Page 145 of 152
4
DATA SHEET FOR
TEMPERATURE TRANSMITTERS
PROJECT:
NO
1
2
BY
DATE
SHEET
DOC.NO.
GENERAL
XMTR
CONTROLLER
INPUT
ALARM
OPTIONS
Tag No.
Function
3
4
5
Type
Case
Mounting
6
7
8
Enclosure Class
Power Supply
Chart
9
10
Scale
Printout
11
Selector Switches
12
Trans. Output
13
Control Modes
14
15
16
17
18
19
Action
Auto-Man Switch
Set Point Adj.
Manual Reg.
Output
Thermocouple Type
20
Other Input
21
22
Alarm Switches
Function
23
24
25
T/C Burnout Drive
Accessories
26
MFR. & Model No.
4
REV.
CONTRACT
BY
2
OF
REVISON
REQ.
1
3
DATE
P.O.
CHK'D
APPR.
Service
Record
Other
Auto Bal.
Indicate
(Note 1)
Mon Bal.
Control
Galv
MFR STD
Nom Size
Flush
Surface
Rack
For Multiple Spec, See Sheet.
Blind
Transmit
Other
Color: MFR STD
Material low copper die-cast aluminium
Multi-Case
Other head mounted
Explosion-Proof
Class
Other Note 2
Gen. Purp
Weather Proof
117 V 60 Hz
Other 24VDC
Strip
Cire
Time Mards
Range
No
Chart Speed:
Change Gears
Type
Rangel
2
No. of Points
See Per Point
Full Travel Speed
Print Character Color
Point Select
No. and Form
In Case
External
Switch Cabinet Specs
4-20mA
10-50mA
21-103 kpa(3-15 psing)
Other (Note 3)
Input-Output Isolation
For Reciever see spec. Sheet.
P=prop(Gain), I=Integral (Auto Reset), D=Derivative (Rate),
Sub: s=Slow
f=Fast
P
PI
PD
PID
If
Df
Is
Ds
Other
On Meas. Increase Output: Increases
Decreases
None
MFR STD
Specify
Manual
External
Remote
Specify
None
MFR STD
Other
4-20mA
10-50mA
21-103 kpa(3-15 psing)
Other
J(IC)
K(CA)
T(CC)
E(CHR-CON)
Other
Ref Juntion Comp
Lead Resistance (Galv.)
PT100
Resistance TempSensor
Other
Quantity
Form
Meas. Var
Deviation
Other
Front Adj.
Back Adj.
None
Upscale
Case Illuminator
Filter Reg.
(Note4)
Calibration
Rating
Contacts to
Measure
Downscale
Charts
Other Note 5
Notes:
1- The transmitter shall be equipped with an integral indicaitor, having LCD disply.
2- Enclosure shall be suitable for use in zone 2,EExi, IIB, T3 and ingress protection shall be IP 65.
5- Transmitters shall be selected to have a Min. accuracy of ±0.5% of calibrated range.
Page 146 of 152
PROJECT:
DATA SHEET FOR
TEMPERATURE TRANSMITTER
NO
BY
DATE
SHEET
4
OF 4
DOC.NO.
REV.
REVISON
CONTRACT
1
DATE
2
REQ.
P.O.
BY
Type
Input
Well U
Dim.
(m.m.)
0-100
RTD
300
2", 1500 #RTJ
-13/85
30 / 60
0-100
RTD
250
2", 1500 #RTJ
-13/85
30 / 60
*
0-50
RTD
250
2", 900#R.F.
-13/80
4 / 10.4
TT/TE-1051
*
-40-20
RTD
300
2 ", 600#R.F.
-13/80
-11 / -4.3
69.4 / 76.34
TT/TE-1060
*
-40-20
RTD
300
2", 600#R.F.
-15/80
-10 / -3.9
69.4 / 76.34 (HC/VAPOUR)/GAS-014-C6A-10"-1C
TT/TE-1080
*
0-100
RTD
250
2 ", 300#R.F.
80
55
4/6
(HC/LIQUID)/CON-026-C1A-6"-PT
TT/TE-1090
*
0-100
RTD
200
2", 600#R.F.
-13/80
45 / 49.8
74 / 81.4
(HC/VAPOUR)/GAS-020-C6A-2"-PT
TT/TE-1091
*
-10-20
RTD
200
2", 600#R.F.
-13/80
-0.37/6.3
74 / 81.4
(HC/2PHASE)/CON-008-C6A-3"-PT
TT/TE-1092
*
0-100
RTD
250
2", 900#R.F.
-13/84
48/59.2
74 / 81.4
(HC/2PHASE)/CON-006-C9A-6"-PT
TT/TE-1100
*
0-60
RTD
200
2", 300#R.F.
-13/80
21/27.7
14 / 16
(HC/VAPOUR)/GAS-024-C1A-4"-PT
TT/TE-1110
*
0-100
RTD
200
2", 300#R.F.
-13/80
46
23 / 25.3
(HC/LIQUID)/CON-066-C3A-4"-IH
TT/TE-1120
*
0-100
RTD
250
2", 300#R.F.
-13/80
34/36.5
3.8 / 5.8
(HC/VAPOUR)/GAS-025-C1A-6"-PT
TT/TE-1121
*
0-200
RTD
500
2", 300#R.F.
-13/150
123.6/125
4 / 6.5
(HC/2PHASE)/T-200
TT/TE-1122
*
0-150
RTD
250
2", 300#R.F.
-13/119
93.6/94
4.5 / 6.5
(HC/LIQUID)/CON-018-C1A-6"-1H
TT/TE-1123
*
0-100
RTD
500
2", 300#R.F.
-13/80
54.9/55.6
4.1/ 6
(HC/VAPOUR)/T-200
TT/TE-1141
*
0-50
RTD
300
2", 1500#RTJ
-13/80
9/15.0
TT/TE-1150
*
0-200
RTD
200
2", 300#R.F. -13/150.3
TT/TE-1190
*
0-100
RTD
200
2", 300#R.F.
Range
Rev.
Tag No.
Adj.
Rang
Set
Range
TT/TE-1020
*
TT/TE-1030
*
TT/TE-1050
Process
Design
Normal Op/Max
Connection
Temp (ºC )
Temp. (ºC )
& Rating
-13/85
Normal
Op./Max.
Press.
(barg)
Service /Line No./
or Equipment
CHK'D
P&ID No.
APPR.
Note
120.5 / 160 (HC/2PHASE)/GAS-001-C15B-10"-PT
120 / 160
(HC/VAPOUR)/GAS-006-C15B-8"-PT
105.4 / 113.4 (HC/VAPOUR)/GAS-012-C9A-8"-1C
(HC/2PHASE)/GAS-013-C6A-10"-1C
119 .4/ 160 (HC/2PHASE)/GAS-010-C15A-10"-1C
123.8/125.3
6/8
(HC/LIQUID)/CON-034-C1A-4"-PT
60
7.5 / 9.5
(AIR )ISA-001-G1C-2"-NP
Note:
* The Adj. range to be specified by vendor.
Page 147 of 152
.
OWNER:
MC:
PROJECT:
DOCUMENT TITLE
CONTRACTOR:
DOCUMENT NUMBER
REV.
DATA SHEET FOR
PRESSURE TRANSMITTER
PAGE
1 OF 4
DATA SHEET FOR PRESSURE TRANSMITTER
QTY:17
CHCE Document Number:
D1
Approved for Construction
D0
Issued for Approval
B0
Issued for Approval
Rev.
PURPOSE OF ISSUE
PREPARED BY
REVIEWED BY
APPROVED BY
DATE
Page 148 of 152
OWNER:
MC:
PROJECT:
CONTRACTOR:
DOCUMENT NUMBER
DOCUMENT TITLE
REV.
PAGE
DATA SHEET FOR
PRESSURE TRANSMITTER
2 OF 4
REVISION INDEX
0
1
X
X
X
X
X
X
X
X
2
3
PAGE
PAGE
1
2
3
4
OWNER / MC
CONTRACTOR
4
0
1
X
X
X
X
X
X
X
X
2
3
4
OWNER / MC
0
1
2
3
CONTRACTOR
4
0
1
2
3
THIS PAGE IS A RECORD OF ALL REVISIONS TO THIS DOCUMENT.
- REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION OF THE REVISION. THESE REMARKS
SHALL BE INTERPRETED IN CONJUNCTION WITH THE REVISED TEXT MARKED BY REVISION NUMBERS.
- WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE ORIGINAL DOCUMENT.
Page 149 of 152
4
PROJECT:
SHEET
DATA SHEET FOR
PRESSURE TERANSMITTER
NO
1
BY
DATE
3
OF 4
REV.
DOC.NO.
REVISON
CONTRACT
DATE
2
REQ.
BY
1
Tag No.
2 Function
P.O.
CHK'D
Service
Record
Indicate
(Note 1)
Control
Blind
Trans
Other
GENERAL
3 Case
MFR STD
4 Mounting
Flush
Nom Size
5 Enclosure Class
General Purpose
Color: MFR STD
Surface
Yoke
Weather Proof
Explosion-Proof
For use in Intrinsically Safe System
6 Power Supply
117 V 60 Hz
Other ac
Strip
Roll
7 Chart
low copper die-cast aluminium
Class
Other Note 2
dc
Volts 24
Fold
Circular
Range
Time Marks
Number
8 Chart Drive
Speed
9 Scale
Type
Power
10 Transmitter Output
4-20mA
11 Control Modes
P= Prop(Gain.), I= Integral (Auto Reset), D=Derivative (Rate), Sub: s=Slow, f=Fast
Range: 1
XMTR
Material
Other
P
2
10-50mA
3
4
21-10 kpa(3-15 psig)
PI
PD
PID
Other (NOTE 4)
If
Df
Is
Ds
Other
CONTROLLER
12 Action
None
14 Set Pint Adj.
Manual
15 Manual Reg.
None
16 Output
ELEMENT
On meas. Increase Output: Increases
13 Auto-Man Switch
4-20mA
Decreases
MFR STD
Other
External
Remote
MFR STD
Other
10-50mA
21-10 kPa(3-15 psig)
17 Service
Gage Press
Vacuum
18 Element Type
Diaphragm
19 Material
316SS
Ber. Copper
20 Range
Fixed
Adj. Range See Next sheet
Helix
Overrange Protection
Press:
¼ in. NPT
Normal
½in. NPT
Location:
Bellows
Other
Other
Max
Bottom
Quantity
Set at
Element Range See next sheet
Other
Back
Form
26 Function
Press
27 Options
Filter-Reg.
Deviation
Supply Gage
Diaph Seal
Type
Conn.
Other
Compound
to 1.5 time of Max. range
24 Process Conn.
OPTIONS
Absolute
Bourdon
23 Process Data
25 Alarm Switches
Other
Capillary: Length
Other
Rating
Contacts To
Output Gage
Diaph
On Inc. Press.:
Charts
Bot Bowl
Mtl.
Other 2" S.S. pipe Bracket with S.S. Ubolts, 2 valve manifold (316 S.S 1/2" vent & drain NPTF).
D
28 MFR. & Model No.
Notes:
1. Intergral output meter shall have LCD disply and indicate engineering units on linear scale.
2. Enclosure shall be suitable for use in zone 2, EExi, IIB, T3 and ingress protection shall be IP 65.
3. The transmitter accuracy shall be equal or better than 0.5% of calibration span.
4. Electrical connection to be M20 × 1.5 ISO (F) and the cable gland will be provided by others.
.
Page 150 of 152
APPR.
PROJECT:
SHEET
DATA SHEET FOR
PRESSURE TRANSMITTER
NO
BY
1
4
OF 4
REV.
DOC.NO.
DATE REVISON
CONTRACT
DATE
2
REQ.
P.O
CHK'D APPR.
M.M.
BY
Range (barg)
Operating
Pressure
(barg)
Max.
Pressure
(barg)
Operating
Temp.
(ºC )
120.5
160
60.0
Item
Tag No.
1
PT-1020
*
0-240
2
PT-1030
*
0-240
120.0
160
3
PT-1050
*
0-200
105.4
113.4
4
PT-1051
*
0-200
105.4
113.4
5
PT-1052
*
0-140
69.4
76.34
6
PT-1060
*
0-140
69.4
7
PT-1090
*
0-150
74.0
8
PT-1091
*
0-150
9
PT-1092
*
0-150
10
PT-1100
*
11
PT-1120
12
PT-1121
Adj.
Set
Range Range
Design
Design Temp.
press.
(ºC )
(barg)
Service/Line No.
or Eq. No.
160
-13/85
HC (2PHASE) (GAS-001-C15B-10"-PT)
60.0
160
-13/85
HC(VAPOUR)(GAS-006-C15B-8"-PT)
10.4
113.4
-13/80
HC(2PHASE) (GAS-011-C9A-10"-1C)
10.4
113.4
-13/80
HC(VAPOUR)(GAS-012-C9A-8"-1C)
-11
76.34
-16/80
HC(2PHASE) (GAS-013-C6A-10"-1C)
76.34
-10
76.34
-15/80
HC(VAPOUR)(GAS-014-C6A-10"-1C)
81.4
49.8
81.4
-13/80
HC(VAPOUR)(GAS-020-C6A-2"-PT)
74.0
81.4
-0.36
81.4
-13/80
HC(2PHASE) (CON-008-C6A-3"-PT)
74.0
81.4
59.0
81.4
-13/80
HC(2PHASE) (CON-006-C9A-6"-PT)
0-30
14.0
16.0
27.7
16.0
-13/80
HC(VAPOUR)(GAS-024-C1A-4"-PT)
*
0-10
4.5
6.5
125
6.5
-13/150
HC(2PHASE) (T-200)
*
0-10
4.0
6.0
24.0
6.0
-13/80
HC( 2PHASE) (CON-017-C1A-4"-PT)
13
PT-1122
*
0-10
3.8
5.8
36.5
5.8
-13/80
HC(VAPOUR)(GAS-025-C1A-6"-PT)
14
PT-1130
*
0-35
16.0
18.0
20.6
18.0
-13/80
HC (2PHASE) (GAS-023-C1A-2"-PT)
15
PT-1150
*
0-50
24.0
26.4
28.14
26.4
-13/80
HC(LIQUID) (CON-064-C3A-4"-PT)
16
PT-1190
*
0-20
7.5
9.5
60
9.5
-13/85
AIR / V107
17
PT-1191
*
0-20
7.5
9.5
60
9.5
-13/85
AIR / V107
P&ID No.
Notes:
* THE Adj. RANGE TO BE SPECIFIED BY VENDOR .
Page 151 of 152
Note
PROJECT:
DATA SHEET FOR
TEMPERATURE TRANSMITTER
NO
BY
DATE
SHEET
4
OF 4
DOC.NO.
REV.
REVISON
CONTRACT
1
DATE
2
REQ.
P.O.
BY
Type
Input
Well U
Dim.
(m.m.)
0-100
RTD
300
2", 1500 #RTJ
-13/85
30 / 60
0-100
RTD
250
2", 1500 #RTJ
-13/85
30 / 60
*
0-50
RTD
250
2", 900#R.F.
-13/80
4 / 10.4
TT/TE-1051
*
-40-20
RTD
300
2 ", 600#R.F.
-13/80
-11 / -4.3
69.4 / 76.34
TT/TE-1060
*
-40-20
RTD
300
2", 600#R.F.
-15/80
-10 / -3.9
69.4 / 76.34 (HC/VAPOUR)/GAS-014-C6A-10"-1C
TT/TE-1080
*
0-100
RTD
250
2 ", 300#R.F.
80
55
4/6
(HC/LIQUID)/CON-026-C1A-6"-PT
TT/TE-1090
*
0-100
RTD
200
2", 600#R.F.
-13/80
45 / 49.8
74 / 81.4
(HC/VAPOUR)/GAS-020-C6A-2"-PT
TT/TE-1091
*
-10-20
RTD
200
2", 600#R.F.
-13/80
-0.37/6.3
74 / 81.4
(HC/2PHASE)/CON-008-C6A-3"-PT
TT/TE-1092
*
0-100
RTD
250
2", 900#R.F.
-13/84
48/59.2
74 / 81.4
(HC/2PHASE)/CON-006-C9A-6"-PT
TT/TE-1100
*
0-60
RTD
200
2", 300#R.F.
-13/80
21/27.7
14 / 16
(HC/VAPOUR)/GAS-024-C1A-4"-PT
TT/TE-1110
*
0-100
RTD
200
2", 300#R.F.
-13/80
46
23 / 25.3
(HC/LIQUID)/CON-066-C3A-4"-IH
TT/TE-1120
*
0-100
RTD
250
2", 300#R.F.
-13/80
34/36.5
3.8 / 5.8
(HC/VAPOUR)/GAS-025-C1A-6"-PT
TT/TE-1121
*
0-200
RTD
500
2", 300#R.F.
-13/150
123.6/125
4 / 6.5
(HC/2PHASE)/T-200
TT/TE-1122
*
0-150
RTD
250
2", 300#R.F.
-13/119
93.6/94
4.5 / 6.5
(HC/LIQUID)/CON-018-C1A-6"-1H
TT/TE-1123
*
0-100
RTD
500
2", 300#R.F.
-13/80
54.9/55.6
4.1/ 6
(HC/VAPOUR)/T-200
TT/TE-1141
*
0-50
RTD
300
2", 1500#RTJ
-13/80
9/15.0
TT/TE-1150
*
0-200
RTD
200
2", 300#R.F. -13/150.3
TT/TE-1190
*
0-100
RTD
200
2", 300#R.F.
Range
Rev.
Tag No.
Adj.
Rang
Set
Range
TT/TE-1020
*
TT/TE-1030
*
TT/TE-1050
Process
Design
Normal Op/Max
Connection
Temp (ºC )
Temp. (ºC )
& Rating
-13/85
Normal
Op./Max.
Press.
(barg)
Service /Line No./
or Equipment
CHK'D
P&ID No.
APPR.
Note
120.5 / 160 (HC/2PHASE)/GAS-001-C15B-10"-PT
120 / 160
(HC/VAPOUR)/GAS-006-C15B-8"-PT
105.4 / 113.4 (HC/VAPOUR)/GAS-012-C9A-8"-1C
(HC/2PHASE)/GAS-013-C6A-10"-1C
119 .4/ 160 (HC/2PHASE)/GAS-010-C15A-10"-1C
123.8/125.3
6/8
(HC/LIQUID)/CON-034-C1A-4"-PT
60
7.5 / 9.5
(AIR )ISA-001-G1C-2"-NP
Note:
* The Adj. range to be specified by vendor.
Page 152 of 152
.
Download