USER MANUAL FOR VATS FLOW METERS

advertisement
FLOW SENSOR – JT 121 & FITTING
USER MANUAL FOR VATS FLOW METERS
Technical Specifications
Technical Specifications
FLUID MONITOR – A/J 210
Function
Rate cum totalizer & batching optional
Supply Voltage
230 VAC + 10%
Meter Size
80mm dia X 100mm deep for field mounting
72 mm X 72 mm X 110 mm for panel mounting
Display
2 line 8 digit alpha-numeric LCD
Standard
Optional
Flow rate range
0.5 to 5 m/sec
Accuracy
+1% of full scale
Input Voltage
5-12 VDC
Output Signal
Square wave of 5 to 12 Volt amplitude
15 – 17.5 Hz/m/sec
Cable length
3 meters
Protection rating
IP 67
Material of construction
Body
Paddle
Pin
O’ring
PP
PVDF
Metal
Viton
PVDF
PVDF
Metal
Viton
Signal Input
Wiring connections:
Red wire: Supply 5 – 12 VDC
Black wire: Output signal TTL
Shield wire: Common
Note: Sensor has been reverse
polarity protected.
TTL from JT 121
Calibration
Using front panel membrane keys
Output
5A pot.free@230VAC
Note: For lines above 100 NB SS
weld ON nozzle is provided with
the flow meter. The nozzle has a
small saddle piece to ensure no
mistake is made during welding to
the pipe line.
LENGTH
Fitting NB 15 25
40
Length mm 250 175
235
MOC
-----ABS------------
1
50
65
80
100
300
350
450
500
-------------SS Tee --------------
3
GUIDE LINES FOR USE IN REVERSE OSMOSIS SYSTEMS:
VATS FLOW METERS INSTALLATION GUIDE LINES
For fittings up to 100 NB with flow straighteners:
All flow-straightened fittings require a straight run of 10 D before and 5 D after them
for good results.
Reject flow meter: The disturbances created in the flow/velocity profile are
maximum in this case. It is best recommended to provide an elbow immediately
after the reject control valve followed by the 10 D straight run. In case the outlet
is likely to be opened to atmosphere immediately after the sensor, mount the sensor
in a vertical plane with entry from the bottom.
sensor
cap
Flow Direction
fitting
10 D
5D
10 D
Incase of larger line sizes without the flow straighteners, the following straight
lengths must be provided
5D
10 D
Rej.Valve
Rej.Valve
Sensor/Indicator mounting guidelines:
10 D
5D
15 D
5D
Straight pipe
20 D
The unique paddle wheel design of the sensor permits it to be mounted in any plane..i.e.
the unit can be installed in vertical as well as horizontal piping. Insert the blind plug supplied
along with the meter in the fitting and flush the line with water. Depressurize the line, remove
the blind plug and insert the flow sensor gently. Ensure that the sensor O-rings are in place and
slightly greased. Push the sensor in till the threaded cap touches the T fitting. Before tightening
the cap ensure the direction of the sensor is proper. Incase of panel mounted units the arrow on
the sensor should point in the direction of flow. In case of field mounted units the sensor must
be mounted such that the display becomes parallel to the pipe line. Start tightening the cap by
hand. For ensuring the sensor in correct position a male/female locking arrangement has been
provided in the sensor and the fitting respectively. While tightening the sensor cap, by a slight
angular motion, one can get an idea of proper locking properly locked sensor/fitting will not have
any angular motion.
Reducer
5D
50 D
90 deg. bend
5D
Valve
DO NOT USE PIPE WRINCHES OR ANY OTHER TOOLS FOR TIGHTENING THE CAP
Follow the ARROW marking on the Fitting while installing
Line Size Selection Chart [For Water]
25 D
5D
40 D
2 elbows in same plane
5D
Pipe Size (NB)
15
3
Min. Flow (m / hr) 0.2
Max. Flow (m 3 / hr) 2.1
25
0.8
8.0
40
1.9
19
2 elbows in different plane
4
5
50
3.5
35
65
5.8
58
80
7.5
75
100
14
140
Programming VATS TOTALISER A/J210T:
The VATS Flowgauge is supplied along with its flow sensor and
installation fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
key for 1 second, the unit displays
VIEW
SETTINGS
The display scrolls through all the settings of scale factor, exponent and finally
coming back to
VATS
TOTALISR
VATS
TOTALISR
And then to the rate and totalised readings.
Note : Incase the
key is pressed and a wrong password is entered, the unit
displays
8
PASSWORD
ERROR
The display then automatically rolls to the
VATS
TOTALISR
And then to the rate and totalised readings as per the old
settings.
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
VATS
TOTALIZER
And then to the rate and totalised readings as per the old settings.
For calibration/re-calibration of the instrument the previously programmed scale
factor can be increased in proportion to the difference in the reading between the
actual flow and the displayed reading.
And then to the rate and totalised readings.
HOW TO SET THE TOTALIZER VIEW MODE
Press
key for 5 seconds, till the unit will display:
PASSWORD
0000000
Press the
and
keys to set the display as
key, the unit displays
Press
RESET
TOTAL?_
To reset the earlier totalised reading press
Key, the unit will display
TOTAL
CLEARED
Else Press
PASSWORD
0000000
Press the
key for 5 seconds, the unit will display:
and
keys to set the display as
PASSWORD
0000031
PASSWORD
0000012
Press
Press
key ,the display automatically rolls over to
key, the unit displays the scale factor
SETSCALE
0.-----Press
and
keys to increase the scale factor if required.
Press
key, the unit displays the exponent.
EXPONENT
10 e-x
The value of x can be changed from –3 to +3 by pressing the
key.
Press
Fitting:
For easy installation a TEE type fitting is supplied with the batcher of the suitable pipe
size. This fitting has BUILT IN FLOW STRAIGHTENERS. These ensure that long
upstream/down stream straight lengths are not required. Standard fittings are available
with BS 10 table D drilling flanges.
key, the unit displays
VATS
TOTALIZER
And then to the rate and totalised readings.
VATS BATCHER A050
HOW TO SET THE OUTPUT/BATCH COUNT:
9
10
The vats batcher consists of the following three parts i.e.
1.The flow sensor 2. The electronic module 3. Installation fitting
10%------------100%
Flow sensor: Refer JT 121 data sheet
SET
100
SET
10
SET
1
SET
Electronic module: The module basically consists of an LED bar graph of 10 LEDs, which
indicates the % of the output (set), completed. Once the desired output is attained the unit
shows all the ten LEDs ON and the relay inside the unit gets energized for 2 seconds. The
relay output is fed to the auto valve actuator to initiate the regeneration process. Since the
unit is used to initiate regeneration process, the unit must be set for AUTO reset mode i.e.
the batcher would automatically reset after giving a 2 second pulse. The four LEDs below
the bar graph are used in the setting of the batch count.
LED bar graph
SET
Procedure:
Press
SET
key. The
mode press the
ENT
Technical Specifications:
ENT
SET
Membrane key pad
Key , the
SET
100
SET
LED will start blinking. To be able to enter the program
key till the first FIVE LEDs of the BAR GRAPH light up. Press
LED would start glowing, press the
hundred’s digit of the output in m3. Press
Spply: 230 VAC
Display: % output with a 10 LED BAR GRAPH
Programming: Using the front panel membrane key pad.
Output: Potential free contact @ 5 A at 230 VAC Auto or Manually resettable.
Input: From VATS flow sensor
Least Count: 1 m3 (unless specified otherwise)
Protection: IP 65
Gland: PG7
Maximum Set point: 999 m3 (unless specified otherwise)
sensor
Relay output
Pole/NO
Rear wiring connection
Press
SET
ENT
key, the
key to set the
10
LED will start glowing.
Key to set the ten’s digit of the output in m3. Press
LED will start Glowing. Press
press
ENT
SET
SET
key, the
ENT
1
key to set the unit’s digit of the output in m3.
key. All the LEDs will switch off except the SET LED which will stop
blinking indicating that the BATCHER is in service.
NOTE:
If the batcher is to be set in an auto-reset mode then all Leds must be ON, where as if only 50% of
LEDs are kept ON then the unit would operate on a MANUAL RESET MODE .i.e. once the desired
quantity of the liquid passes through the meter, the relay would get energised.
Press ENT key to RESET the Relay. In an Auto reset mode the relay would get reset after 2 seconds.
For setting any digit, the SET key is pressed such that the number of LEDs that glow in the bar
graph 0 to 9 correspond to the value of the digit. During normal service the Last LED of the Bar
graph would keep blinking whenever flow takes place. The % completion of the output would get
displayed in the BAR GRAPH.
Power Supply
For setting the relay mode auto/manual, press set key and enter a
password of nine. Press enter key. The bar graph will either show all
LEDs ON(auto reset) or 5 LEDs ON (manual reset).Press set key to
toggle to the required setting. Press enter key. Relay MODE is set.
To reset the relay automatically once the batch count is achieved
press
key
The unit displays
Programing VATS BATCHER A / J 210 B :
AUTO
RESET?
Press
key, the unit will display
DISPLAY
TOLAL?_
The VATS Flowgauge is supplied along with its flow sensor and installation
fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
key, the unit
DISPLAY
BATCH?_
Press
key, the unit will display
key for 1 second, the unit displays
VIEW
SETTINGS
The display scrolls through all the settings of scale factor, relay and reset
Modes and finally coming back to
VATS
BATCHER
And then to the rate and totalised readings.
HOW TO SET THE BATCHER VIEW MODE
Press
For viewing only the cumulative flow of the batch press
displays
RESET
TOTAL?_
To reset the earlier totalised reading press
key, the unit will display
TOTAL
CLEARED
Else Press
key, the display automatically rolls over to
VATS
BATCHER
And then to the rate and totalised readings.
key for 5 seconds, till the unit will display:
Note:
PASSWORD
0000000
Press the
Incase the
and
keys to set the display as
PASSWORD
0000012
Press
MANUAL
RESET?_
key, the unit displays
key is pressed and a wrong password is entered, the unit displays
PASSWORD
ERROR! _
The display then automatically rolls to the
VATS
BATCHER
And then to the rate and totalised readings as per the old settings.
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
VATS
BATCHER
VATS
BATCHER
And then to the rate and totalised readings as per the
old settings.
And then to the rate and totalizer readings as per the old setting
For calibration/re-calibration of the instrument the previously programmed
scale factor can be increased in proportion to the difference in the reading
between the actual flow and the displayed reading.
SETTING THE BATCH
Press
Press
PASSWORD
0000000
key, the unit will display
PASSWORD
0000000
Press the
Press the
and
keys to set the display as
PASSWORD
0000011
Press
SETRELAY
000000.0
Each of the above digits can be changed to set the batch quantity/value
at which the relay is to be energised by using the
and
keys.
Press
key, the unit displays batch count
i.e. the total number of times the relay was energised.
BAT.CNT.
0000000
Press
RESET
BAT.CNT.
For resetting the count to zero press
BAT.CNT.
CLEARED
else press
key the unit displays
key the display automatically rolls to the
keys to set the display as
key, the unit displays the scale factor
SETSCALE
0.------
Press
and
Press
key, the unit displays the exponent.
keys to increase the scale factor if required.
EXPONENT
10 e-x
The value of x can be changed from –3 to +3 by pressing the
key.
Press
key, the unit asks whether the batch count should be cleared
and
PASSWORD
0000031
Press
key, the unit displays batch setting
key for 5 seconds, the unit will display:
key, the unit displays
VATS
BATCHER
And then to the rate and totalised readings.
The display scrolls through all the settings of scale factor, relay and reset
Modes and finally coming back to
VATS
PULSER
And then to the rate and totalised readings.
HOW TO SET VIEW MODE
Press
key for 5 seconds, the unit will display:
PASSWORD
0000000
Press the
and
keys to set the display as
PASSWORD
0000012
Press
key, the unit displays
RESET
TOTAL?_
To reset the earlier totalised reading press
Programing VATS PULSER ( A /J210 )
PULSER MODE
key, the unit will display
TOTAL
CLEARED
else Press
key, the unit displays
VATS
PULSER
And then to the rate and totalised readings.
The VATS Flowgauge is supplied along with its flow sensor and installation
fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
key for 1 second, the unit displays
VIEW
SETTINGS
Note:
Incase the
PASSWORD
ERROR! _
key is pressed and a wrong password is entered, the unit displays
The display then automatically rolls to the
VATS
PULSER
And then to the rate and totalised readings as per the old settings.
CLEARED
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
else press
VATS
PULSER
And then to the rate and totalizer readings as per the old setting
SETTING THE BATCH
Press
And then to the rate and totalised readings as per the old settings.
For calibration/re-calibration of the instrument the previously programmed
scale factor can be increased in proportion to the difference in the reading
between the actual flow and the displayed reading.
Press
and
keys to set the display as
key, the unit displays batch setting
Each of the above digits can be changed to set the batch quantity/value
at which the relay is to be give pulse by using the
and
keys.
After every programmed Qty of liquid is passed through , the unit will give a
pulse out to the Dosing / Metering pump.
Press
key, the unit displays batch count
i.e. the total number of times the relay was energised.
BAT.CNT.
0000000
Press
key, the unit asks whether the batch count should be cleared
RESET
BAT.CNT.
For resetting the count to zero press
BAT.CNT.
key the unit displays
and
keys to set the display as
PASSWORD
0000031
Press
SETRELAY
000.0000
key for 5 seconds, the unit will display:
PASSWORD
0000000
Press the
PASSWORD
0000011
Press
VATS
PULSER
key, the unit will display
PASSWORD
0000000
Press the
key the display automatically rolls to the
key, the unit displays the scale factor
SETSCALE
0.-----Press
and
Press
keys to increase the scale factor if required.
key, the unit displays the exponent.
EXPONENT
10 e-x
The value of x can be changed from –3 to +3 by pressing the
key.
Press
key, the unit displays
VATS
PULSER
And then to the rate and totalised readings.
PASSWORD
0000000
Press the
and
keys to set the display as
PASSWORD
0000012
Press
key, the unit displays the scale factor
RESET
TOTAL?_
To reset the earlier totalised reading press
Programming VATS RATE SWITCH ( A/J210) :
key, the unit will display
TOTAL
CLEARED
Press
key, the display automatically rolls over to
VATS
RATE SW.
The VATS Flow gauge is supplied along with its flow sensor and installation
fitting of the suitable line size duly calibrated.
How to view all the settings:
Press
And then to the rate and totalised readings.
Note:
Incase the
displays
key is pressed and a wrong password is entered, the unit
key for 1 second, the unit displays
VIEW
SETTINGS
PASSWORD
ERROR ! _
The display then automatically rolls to the
The display scrolls through all the settings of scale factor, relay and reset modes and finally coming back to
VATS
VATS
RATE SW.
And then to the rate and totalised readings.
HOW TO RESET THE TOTALISER READING
Press
key for 5 seconds, the unit will display:
RATE SW.
And then to the rate and totalised readings as per the old settings.
Incase the
key is pressed and no password is entered for 10 seconds the
display automatically rolls to the
VATS
RATE SW.
And then to the rate and totalised readings as per the old settings.
Press the
and
keys to set the display as
SETTING THE RELAY
Press
PASSWORD
key, the unit will display
0000031
PASSWORD
Press
0000000
Press the
and
key, the unit displays the scale factor
SETSCALE
keys to set the display as
0.------
PASSWORD
0000011
Press
key, the unit displays flow setting
SETRATE
press
and
keys to increase the scale factor if required.
Press
key, the unit displays the exponent.
00000.00
EXPONENT
Each of the above digits can be changed to set the low flow rate
value below which the relay will remain energised by using the
and
keys.
The value of x can be changed from –3 to +3 by pressing the
Press
10 e-x
Press
key, the unit asks for the hysterysis .
VATS
HYSTERIS
RATE SW.
--%
The hysterysis value can be set from 0 to 10% by pressing the
Press
key.
key, the display automatically rolls to the
VATS
RATE SW.
And then to the rate and totalised readings as per the old settings.
For calibration/re-calibration of the instrument the previously programmed scale
factor can be increased in proportion to the difference in the reading between the
actual flow and the displayed reading.
Press
key for 5 seconds, the unit will display:
PASSWORD
0000000
key, the unit displays
And then to the rate and totalised readings.
key.
TROUBLE SHOOTING OF VATS FLOW METERS:
During commissioning:
Trouble
Display remains zero
even when actual
flow is there
Trouble
Probable cause
Flow less than the
minimum sensing value.
Sensor not inserted in the
correct plane.
Paddle not moving freely
Wrong sensor
wiring.(mainly applicable
for panel mounted meters
or field mounted units
where sensor wire is
extended.)
Meter and sensor are not
matching.( applicable for
panel mounted meters)
Reading getting
displayed but not
correct.
During normal service:
Adequate straight run is
not provided upstream
downstream of sensor.
PS: Presence of a pressure
reducing valve very close
(upstream) of the sensor
can result in error
Scale factor disturbed
No display
Action required
Check if any downstream
valve is closed. Open valve.
Remove the sensor from the
fitting and check change in
reading
by
physically
rotating the paddle. If meter
shows reading check the
actual flow. Change the
fitting if the normal flow is
lower than the minimum
sensing velocity.
Ensure that the arrow on the
sensor is in direction of
flow.
Remove the sensor clean the
paddle/pin and ensure free
movement of paddle
Connect the sensor wires as
per wiring connection
details on the meter.
Display remains zero
even when actual
flow is there
Action required
Flow less than the
minimum sensing value.
Check if any downstream
valve is closed. Open valve.
Remove the sensor from the
fitting and check change in
reading
by
physically
rotating the paddle. If meter
shows reading check the
actual flow. Change the
fitting if the normal flow is
lower than the minimum
sensing velocity.
Paddle not moving
Remove the sensor clean the
paddle/pin and ensure free
movement of paddle
Reading getting
displayed but not
correct.
Paddle not moving freely
Remove the sensor clean the
paddle/pin and ensure free
movement of paddle
Scale factor disturbed
No display
Ensure that the meters are
connected
to
its
corresponding sensor and
fitting only.
Provide straight run as per
guidelines. OR adjust the
scale factor to match the
actual flow. Provide a bend
between the valve and the
sensor. Try use of fittings
with strengtheners whenever
possible.
Probable cause
No supply
Check factor. Correct factor
as mentioned on meter
sensor.
Micro-Processor hanged
Checks input supply and
make proper connections.
Switch off supply for 1
minute and then switch ON
supply.
Check factor. Correct factor
as
mentioned
on
meter/sensor.
No supply
Checks input supply and
make proper connections.
16
5
17
VATS FLOW METER
Check Sheet
A ) No Display
General

Date:


Name of Client/Dealer:
Serial Number:
No. of months in use:
Model: Ultraflo Rate Indicator(field mounted) A110
[ ]
Fluid monitor LCD indicator cum totaliser A210
[ ] / J210 [ ]
LED bargraph batcher model A050 [ ]
Flow transmitter model J510 [ ]
OR
Model: Rate Indicator (field Mounted)
IP 110 [ ]
Rate cum electromechanical totaliser IP 210 [ ]
Rate indicator panel mounted JT110 [ ] / JT 111 [ ]
Rate cum total panel JT 210 [ ]


Check for power supply using multi meter/test lamp [ ]
(Use of tester does not confirm proper neutral or adequate voltage)
Water deposition inside the meter housing Y/N
For Ultraflo, remove the front cover and replace the battery by an Alkaline
9VBattery the unit started displaying flow Y/N
The back light gets on (for A110/A210/J210/J510) Y/N
The last led of the BAR Graph ( for A050) blinks when the paddle is rotated Y/N
B ) Reading remains zero





Checked actual flow and found it higher than the minimum capacity of the meter
Y/N
Removed the flow sensor from the fitting and checked free rotation of paddle
wheel Y/N
Meter showed reading when paddle rotated by hand Y/N
For panel mounted meters checked the sensor wiring to the terminal strip. All the
three wires were connected to the respective terminals Y/N
(If the same site has more than one panel meters) Connected another sensor of the
working unit to the meter. Meter shows reading Y/N
The last led of the BAR Graph ( for A050) blinks when the paddle is rotated Y/N
Checked scale factor programmed and found it to be same as written on the
meter Y/N
Installation fitting Type:
Polypropylene wafer fitting [ ] , Plastic Tee fitting [ ] ,
Stainless steel weld on fitting.[ ] , Flow straightened pipe fitting [ ].


Installation/Location: Outdoor [ ] /Indoor [ ]
C ) Fluctuating reading:
Application: Deminraliser [ ], RO [ ], Blending- Mineral water [ ]
Other – specify __________
Line pressure: ________ kg/cm2 max.
Types of Problems
A)
B)
C)
D)
E)
F)
G)
H)
No display [ ]
Reading remains Zero [ ]
Fluctuating reading [ ]
steady but erroneous reading [ ]
Breakage [ ]
Gradual fading of display [ ]
meter shows reading even at no flow (applicable for IP/JT series only)
any other- specify [ ]
18




Is the sensor located just after any valve/reducer? Y/N
Removed the sensor found the paddle moving freely Y/N
Did not find any air bubbles in the water line Y/N
(For panel meters) checked the sensor wiring and tightened all the three wires to the
respective terminals of the strip. Y/N
 Is the sensor wiring is extended. Y/N
 The wiring is properly extended and there is no shorting of wires Y/N
D ) Steady but erroneous reading:






Mention the flow rate indicated w.r.t. actual ____________.
The Serial number of the meter, sensor and fitting were matching Y/N
Line size mentioned on the indicator same as the fitting Y/N
Scale factor of the meter same as that mentioned on the sticker Y/N
There is an adequate straight run on the inlet/ outlet of the sensor ( refer guidelines
enclosed) Y/N
If straight run inadequate adjust scale factor to match the actual flow. Readings
found OK Y/N
19
E)
Breakage:

Specify the component broken and the likely cause for the same-
F)
Gradual fading of display:

The unit is exposed to direct sunlight. Y/N
Vatturkar Industrial
B 14/3 Bandhan Society,
Kothrud Pune-29
TEST REPORT
Standard
Product:
G)


Setting
Meter shows reading even at no flow (applicable for IP and JT series only):
Model:
There is an induction motor/coil very close to meter/sensor Y/N
For JT series.
The T-50/Cal key is in released position Y/N
The extra sensor cable is kept looped near the
Sensor Y/N
The plant piping was properly grounded. Y/N
Sensor removed from fitting. Meter reading
became zero Y/N
Disconnect the sensor wires from meter. Reading
becomes zero Y/N
H ) Any other: Specify_____
S.No:
Size:
This is to certify that the products mentioned above have been tested and
calibrated at our works and have been found working satisfactorily as per the
technical specifications of the product.
GUARANTEE CERTIFICATE
We certify that the instrument mentioned above has been tested by us and is
guaranteed for a period of 12 months from the date of dispatch.
We undertake to make good by replacement or repair defects arising due to
Faulty design, material or workmanship within the above mentioned period.
Provided that the part in respect to which the complaint is made, is sent at the
purchaser`s expense.
The warrantee is valid subject to :
The meter or part there of not being subjecty to alteration, accident abuse
or misuse
The installation having been done as per guide lines in the manual.
Checklist filled by:
Company name:
Manufacturer & Marketed by:
VATTURKAR INDUSTRIAL
B14/3 , Bandhan Society ,
Kothrud, Pune- 29
Tel-091-020-25430897, Telfax- 25432157.
Client:
Date of dispatch:
for VATTURKAR INDUSTRIAL
Authorised Signatory
E-mail-vatsmeter@vsnl.net
WEB- www.vatsmeter.com