Energy Seminar Emerson Process Management June 22/23, 2010 Final Control Element Best Practices for Efficient Energy Use Mike Lewis Novaspect, Inc. Emerson Process Management Energy Management Seminar Agenda Process variability defined and its effect on energy waste Control valve shut-off defined and its effect on energy waste How to engineer improvement Variability, defined by a Real Life Example Acceptable shower temperature Probability of Occurrence Perfect shower temperature Cardiac arrest 2nd degree burns Mean Value = Shower Temperature Causes of Variability Loops The Cause 20% Design Increases Variability 30% Tuning As Many As 80% of Loops Actually Increase Variability 30% 20% Source: Entech---Results from audits of over 5000 loops in Pulp & Paper Mills Control Valve Performance A Typical Control Valve Specification You specify … – Fluid properties – Sizing requirements – Design pressure and temperature – Allowable leakage when closed – Failure mode – Connecting pipe size – End connections We engineer … – Valve size – Valve trim Cv versus % open characteristic – Valve type – ANSI P/T rating – ANSI leak class – Actuation system – Materials of construction – Special characteristics for noise, cavitation, flashing, corrosion An Industrial Example Main Steam Temperature Control ΔT = 50 F 1005 F 0.75% NPHR Setpoint = 955 F MS design temp 0.30% load !! PV Distribution +/-1-Sigma +/-2-Sigma +/-3-Sigma Control Loop Objective … Reduce Process Variability Upper Specification Limit Set Point PV Distribution 2-Sigma 2-Sigma Set Point Reduced PV Distribution 2-Sigma2-Sigma SUPERHEAT TEMP. Main Steam Temperature Control Decreased Variability = Increased Profit Upper Limit NPHR = 0.75% Reduction Set Point Increased Temp. Set Point Reduced Process Variability Provides the Opportunity for Setpoint Change = ( NPHR) X Fuel cost X KW-HR generated/year = Savings = .75% x 11,000 BTU/KW-HR X $2.22/MM BTU X 320,000 KW X 8760 hours / year = $516,517 per operating year !! Dynamic Valve Performance We’ve demonstrated value in reducing variability in critical control loops Poor control valve dynamic performance contributes to variability Let’s discuss … – A specification for performance – Designing for performance – Testing for performance – Maintaining performance A Dynamic Control Valve Specification Combined backlash and stiction should not exceed 1% of input signal span Speed of valve position response to input signal changes from 1% to 10% shall meet specific Td, T63 and T98 times Overshoot to step input changes of 1% to 10% shall not exceed 20% Loop process gain should fall between 0.5 and 2.0 … Entech “Control Valve Dynamic Specification” March 1994 Achieving Dynamic Performance by Design Friction Positioner design Machining accuracy Positioner gain adjustability Clearances Flow geometry designed for stability Positioner tuning matched to the valve assembly Air delivery system Plug/stem connection Transducer design Lost motion linkages Soft part flexibility Actuator spring flatness and stiffness Testing for Performance Open-Loop Fixed position – constant load Signal generator flow Control valve FT Transmitter Pump Open Loop Valve Performance Open Loop Step Test 4" Segmented Ball Valves with Metal Seals and Standard Actuators/Positioners Tested at 600 gpm in the 4" Test Loop 70 65 Fisher V150HD / 1052(33) / 3610J 0.5% Steps 1% Steps 2% Steps 5% Steps 10% Steps 60 55 (%) 50 45 40 35 0.5% Steps 1% Steps Neles R21 / QP3C / NP723 70 65 2% Steps 5% Steps 10% Steps 60 55 (%) 50 45 I/P Input Signal Actuator Travel Filtered Flow Rate 40 35 0 50 100 150 200 250 Time (seconds) 300 350 400 450 Testing for Performance Closed Loop Load disturbance z flow Control Valve FT Transmitter Controller Pump Closed-Loop Valve Performance Closed-Loop Random Load Disturbance Summary Tested at 600 gpm in the 4" Test Loop Controller Gain, Kc for the Fisher 4" ED / 667(45) / 3582 1 0.1 6 V DG F 5 Valtek 4" Mark I / Spring Cylinder(50) / Beta Fisher 4" ED / 667(45) / DVC5010 G Tuning Fisher 4" ED / 667(45) / 3582 Manual Variability (%) 4 V 3 V V V V 2 DG F F F F DG F DG F DG V F V DG F DG F Minimum Variability 1 Faster Tuning Slower Tuning 0 1 10 Closed-Loop Time Constant, (seconds) Sustaining Performance Through On-Line Diagnostics G H D E A F B C Plugging of I/P transducer Travel Deviation Insufficient Air Supply Calibration Changes Diaphragm Leaks Piston Leaks O-ring Failures in Actuators Packing condition Friction and Deadband External Leaks Insufficient Seat Load for Shut-off Many others Control Valve Shut-off Decreasing leakage Increasing first cost Increasing maintenance cost An Industrial Example – a Feedwater Heater Emergency Level Valve Shell & tube heat exchanger …. In heater: 31 psia, 215 F., 183.1 BTU/# In the condenser: 1” Hg abs., 79 F., 47.1 BTU/# Leakage worth 136 BTU/# Difference in leakage between an ANSI Class II and Class IV is 1653-33=1620 #/hr Result: 220,320 BTU/hr At 3415 BTU/hr/KW: 64 KW! At $1.58/MBTU coal cost: $4,284 / op. year! Typical Power/Boiler Plant Energy Efficiency Opportunities Aux boiler mode steam Air preheating Aux steam header pressure balancing Blowdown and sampling Condenser performance Feedwater heater efficiency Superheat attemperation Reheat attemperation Emergency heater drain valve leakage Sootblowing steam system Station heating Steam and water loss Turbine cycle condition Throttle pressure Throttle temperature Other Energy-related Variability Examples Fuel/air ratio control Load change responsiveness Steam header pressure balancing Ramp rate improvement Burner light-off Drum level stability Conditioned steam temperature stability and turndown The Takeaway The undesirable behavior of control valves is the biggest single contributor to poor control loop performance and energy waste … spend your money in the basement!