24ANB7 Infinityt 17 2---Stage Air Conditioner with Puronr Refrigerant 2 to 5 Nominal Tons Wiring Diagram SCHEMATIC DIAGRAM (LADDER FORM) CONNECTION DIAGRAM CS L1 RED BRN TRAN 24V COM 11 21 OFM *SC YEL OFM YEL BLK VS VR YEL ODF CCH L1 L2 BLU FACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION CAPACITOR CIRCUIT BOARD CRANKCASE HEATER CRANKCASE HEATER SWITCH SYSTEM COMMUNICATION COMPRESSOR CONT CS HPS LPS * LS OAT OCT OFM RVS * SC SEV * SR STATUS TRAN * UC BLU PL1 C 1 RVS 2 SEV 3 C 4 1 OCT 2 3 OAT 4 5 PL6 1 PL4 T1 OCT BRN BRN BLK CS BLK PL8 CONT OAT C LO HI TIME (MIN) SR LED DEFROST TIME LED 123 TO INDOOR UNIT 2 1 PL3 3 CB 30 LEGEND HPS PWM1 PWM2 VIO BLK RED BLU BRN YEL BLU PL1 C 1 RVS 2 SEV 3 C 4 OCT ON OFF 4 (DEFAULT) QUIET 3 SHIFT 2 COMM STATUS 1 PL5 AS PROVIDED BY MANUFACTURER FORCED SEE NOTE #11 A B C D R C W1 Y1 Y2 O DEFROST PL7 RED WHT YEL GRN 4 ON OFF 3 2 COMM STATUS (DEFAULT) QUIET SHIFT 1 PL5 AS PROVIDED BY MANUFACTURER FORCED SEE NOTE #11 A B C D R C W1 Y1 Y2 O DEFROST PL7 2 1 PL2 30 120 60 LED RED WHT YEL GRN OPTIONAL NON-COMMUNICATING CONTROL SEE NOTE #10 R C W1 Y1 Y2 O LED DEFROST TIME 123 T1 C LO HI 30 SR 30 120 60 TIME (MIN) LPS YEL PWM1 PWM2 90 CB 90 2 1 PL3 3 ODF CCH VIO BLK RED BLU BRN YEL 2 1 PL2 60 BLU/PNK BLU/PNK L1 L2 60 YEL/PNK YEL/PNK BRN BRN/YEL RED/WHT BLU 1 OCT 2 3 OAT 4 5 PL6 OAT PL8 MODEL PLUG MODEL PLUG * UC (WITH INFINITY/EVOLUTION ONLY) CONNECT TO R AND Y2 ON CONTROL BOARD CONTACTOR COMP HIGH CAP SOLENOID HIGH PRESSURE SWITCH LOW PRESSURE SWITCH LIQUID SOLENOID THERMISTOR (OUTDOOR AIR) THERMISTOR COIL OUTDOOR FAN MOTOR REVERSING VALVE SOLENOID START CAPACITOR SOLENOID EXPANSION VALVE START RELAY SYSTEM FUNCTION LIGHT TRANSFORMER UTILITY CURTAILMENT * MAY BE FIELD INSTALLED 1. 2. 3. 4. 5. 23 F H 1 2 5 YEL 1 PL4 NOTES: 23 CAP S YEL VS VR CAP CB CCH CHS COMM COMP R COMP YEL C C BRN/YEL HPS C 21 11 BLU BLK BLK CONT C H 23 23 RED/WHT LPS EQUIP GND *SR VIO CONT L1 208/230 1Ø L2 POWER SUPPLY EQUIP GND F CONT COMP R C S C BLK BLK BLK BRN CHS YEL BLK CCH CAP BLK 208V C 230V YEL 2 1 5 230V TRAN 230V *SC *SR BRN CHS CCH L2 BLU RED TRAN 24V BLU Compressor furnished with inherent thermal protection. To be wired in accordance with National Electric Code (N.E.C.) and local codes. Outdoor unit control requires a minimum of 27 VA, 24 VAC control power. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF). If indoor section has a transformer with a grounded secondary, connect the grounded side to “C”. 6. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 7. Check all electrical connections inside control box for tightness. 8. Do not attempt to operate unit until service valves have been opened. 9. In case of a communicating indoor system, USE WITH INFINITY / EVOLUTION USER INTERFACE AS LISTED IN PRE-SALE LITERATURE. 10. In case of non-communicating indoor system disconnect factory provided wires from A, B, C, and D terminals. Use factory provided wires to connect to Y1, R, C, and Y2 as required by Installation Instructions. Cap or remove unused factory provided wires. 11. For Communicating Control only. TO INDOOR UNIT MODEL PLUG CHART MODEL MODEL PIN RESISTANCE (K ) PLUG SIZE HK70EZ 1 - 4 (R1) 2 - 3 (R2) 18 75 040 024 18 042 120 036 18 044 180 048 18 046 270 060 FLASH CODE On, No Flash 1, Pause 2, Pause 3, Pause 4, Pause 5, Pause 6, Pause 16 25 31 32 45 46 FAULT DEFINITION FLASH CODE Standby Low Stage High Stage ODU Fan Delay Defeat Not Active ODU Fan Delay Defeat Active Brown out is Disabled Brown out is Active System Communications Failure Invalid Model Plug High Pressure Switch Trip Low Pressure Switch Trip Control Fault Brown out (230V) 47 53 55 56 71 72 73 74 81 82 83 84 COMPONENT ARRANGEMENT CONTROL BOARD TRANSFORMER CAPACITOR CONTACTOR FAULT DEFINITION No 230v with Call to Run Outdoor Air Temp Sensor Coil Temp Sensor Temp Sensor Range Error Low Stage Thermal Cutout High Stage Thermal Cutout Contactor Shorted Contactor Open (No 230v to Comp) Low Stage Thermal Lockout (4 HRS) High Stage Thermal Lockout (4 HRS) Low Pressure Lockout (4 HRS) High Pressure Lockout (4 HRS) Short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the status code. UNIT OPERATION This control board contains a five minute short cycle protector. A five minute delay will occur between compressor OFF/ON cycles. To bypass delay, short forced defrost pins for 1 second then release. The crankcase heater is energized during off cycle below 65ºF. Fig. 1 – Wiring Diagram — Model sizes 2 -- 5 tons, 208/230--1 337894-101 REV. B Copyright 2011 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 05/11 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 2 Catalog No: 24ANB7---1W Replaces: New