wiring diagrams 561C, G 561S, W 1 AND 3 PHASE, 60 HERTZ AIR CONDITIONING UNIT Cancels: WD 561C.18.5 WD 561C.18.6 3-99 SCHEMATIC DIAGRAM (LADDER FORM) CONNECTION DIAGRAM (NOTE #9) *CH BLK or RED RED or BLK COMP BLU S BLK C H 21 R C YEL 23 YEL F OFM BRN BLK CONT L1 208/230 1Ø POWER SUPPLY 11 L2 23 EQUIP GND BRN (NOTE #14) BLU BLU BLU CAP 11 *ST BRN 1 YEL BLK BLK *SC (NOTE #8) 2 23 23 CAP CONT *LPS *DTS T2 LOGIC LOGIC T1 T3 T1 T3 * CTD *LLS Y IFR BLK C R G CONT (NOTE #14) BRN Y H OFM C F *HPS *LLS BLK *ST +t *SC 1 * CTD BLU BLU S 2 5 *SR T2 YEL L2 21 5 *SR YEL BLK YEL COMP R C EQUIP GND VIO BLU *CH CONT +t YEL *LPS *DTS *HPS BLU L1 BLK EXTERNAL POWER SUPPLY 24 V (NOTE #3) G R C R INDOOR THERMOSTAT EXTERNAL POWER SUPPLY 24 V R INDOOR BLOWER MOTOR INDOOR THERMOSTAT (NOTE #6) -LEGENDFACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING FIELD POWER WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION -NOTESCAP CAPACITOR (DUAL RUN) *CH CRANKCASE HEATER COMP COMPRESSOR *CTD COMPRESSOR TIME DELAY *DTS DISCHARGE TEMP. SWITCH *HPS HIGH PRESSURE SWITCH IFR INDOOR FAN RELAY *LLS LIQ. LINE SOLENOID VALVE *LPS LOW PRESSURE SWITCH OFM OUTDOOR FAN MOTOR *SC START CAPACITOR *SR START RELAY START THERMISTOR CONT CONTACTOR *ST CAP CAPACITOR (DUAL RUN) * MAY BE FACTORY OR FIELD INSTALLED. 1. Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with lls. 5. Use copper conductors only. 6. Typical cooling only thermostat, for other arrangements see installation instructions. 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN lead. 8. When start relay and start capacitor are installed, start thermistor is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS, DTS or CTD are used. CAUTION 1. Compressor damage may occur if system is over charged. 2. This unit is factory charged with R-22 in accordance with the amount shown on the rating plate. The charge is adequate for most systems using matched coils and tubing not over 15 feet long. The best performance will be achieved when the unit operates with a suction gas superheat at the compressor inlet of 5 °F at normal rating conditions of the air conditioning and refrigeration institute (ARI). This chart may be used to approximate the charge if ARI rating conditions cannot be obtained. ARI rating conditions are equivalent to DOE test "A" conditions. See product data literature for required indoor air flow rates and for use of line lengths over 15 Ft. 3. Carefully relieve refrigerant pressure within this unit before final disposal. 317738-401 REV. C A95084 Fig. 1—561(C, G, S, W)018, 024, 030, 036, 042, 048 208-230v, 1 Phase, 60 Hertz —1— CONNECTION DIAGRAM *CH (NOTE #9) RED or BLK -LEGEND- BLK BLU FACTORY POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING C FIELD POWER WIRING 11 21 YEL BRN 1 2 YEL R 13 23 COMPONENT CONNECTION *SC F 5 YEL (NOTE #8) FIELD SPLICE *SR OFM EQUIP CONT BRN JUNCTION GND BLK CONT CONTACTOR CAP CAPACITOR (DUAL RUN) BLU BRN (NOTE #14) *CH CRANKCASE HEATER BLK VIO COMP COMPRESSOR YEL *CTD COMPRESSOR TIME DELAY *DTS *HPS *LPS T2 *DTS DISCHARGE TEMP. SWITCH BLK YEL BLU BLU BLK LOGIC YEL *HPS HIGH PRESSURE SWITCH T3 T1 IFR INDOOR FAN RELAY *CTD BRN *LLS LIQ. LINE SOLENOID VALVE *LLS *LPS LOW PRESSURE SWITCH BLU BLK BLK EXTERNAL POWER OFM OUTDOOR FAN MOTOR C BLU SUPPLY 24V R *SC START CAPACITOR (NOTES #3 & #6) IFR *SR START RELAY *ST START THERMISTOR * MAY BE FACTORY OR FIELD Y G R INSTALLED. CAP YEL +t° SCHEMATIC DIAGRAM *CH L2 (LADDER FORM) C CONT 21 11 *ST INDOOR BLOWER MOTOR INDOOR THERMOSTAT (NOTE #5) L1 BLU COMP BLU S H BLK C RED or BLK L1 208/230 1Ø L2 POWER SUPPLY 5 EQUIP GND R COMP S 2 1 *SR *ST +t° *SC OFM H C F CONT CAP 23 13 (NOTE #14) *CTD *HPS *DTS *LPS CONT T2 LOGIC T1 T3 *LLS Y G R INDOOR THERMOSTAT IFR R C EXTERNAL POWER SUPPLY 24 V -NOTES- 1. Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. 5. Use copper conductors only. 6. Connection for typical cooling only thermostat, for other arrangements, see installation instructions. 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN lead. 8. When start relay and start capacitor are installed, start thermistor is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS, DTS or CTD are used. 321939-101 REV. B A95018 Fig. 2—561(C, G, S, W)060 208-230v, 1 Phase, 60 Hertz —2— CONNECTION DIAGRAM COMP BLU CONT L1 11 L3 21 13 T2 EQUIP GND T3 YEL 23 EQUIP GND CONT COMP T1 BLK L2 L1 RED or BLK RED or BLK L2 208/230 3Ø POWER SUPPLY SCHEMATIC DIAGRAM (LADDER FORM) *CH (NOTE #8) 11 CAP 21 *CH T3 CAP YEL OFM L3 T2 T1 CONT 13 23 OFM BRN BLK ALERT ! SEE NOTE #11 YEL BRN BLK VIO *HPS *LPS BLU BLU YEL CONT T2 YEL T2 T3 T1 LOGIC T1 CTD BLU *LLS BRN *LLS BLK C R IFR G R INDOOR THERMOSTAT R INDOOR THERMOSTAT (NOTE #5) -NOTES- FACTORY POWER WIRING *CH FACTORY CONTROL WIRING COMP COMPRESSOR *CTD COMPRESSOR TIME DELAY IDF INDOOR FAN *HPS HIGH PRESSURE SWITCH IFR INDOOR FAN RELAY *LLS LIQ. LINE SOLENOID VALVE *LPS LOW PRESSURE SWITCH OFM OUTDOOR FAN MOTOR CRANKCASE HEATER FIELD CONTROL WIRING COMPONENT CONNECTION FIELD SPLICE JUNCTION CONT CONTACTOR CAP CAPACITOR (DUAL RUN) EXTERNAL POWER SUPPLY 24 V INDOOR BLOWER MOTOR -LEGEND- FIELD POWER WIRING C R (NOTES #3 & #6) G T3 CTD Y EXTERNAL POWER SUPPLY 24 V BLK IFR Y *LPS *HPS LOGIC * MAY BE FACTORY OR FIELD INSTALLED. 1. 2. CAUTION Symbols are electrical representation only. 1. Compressor damage may occur if system is over Compressor and fan motor furnished with inherent thermal protection. charged. 3. To be wired in accordance with National Electric 2. This unit is factory charged with R-22 in N.E.C. and local codes. accordance with the amount shown on the rating 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with lls. plate. The charge is adequate for most systems 5. Use copper conductors only. using matched coils and tubing not over 15 feet 6. Typical cooling only thermostat, for other long. The best performance will be achieved when arrangements see installation instructions. the unit operates with a suction gas superheat at 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN lead. the compressor inlet of 5 °F at normal rating 8. If any of the original wire, as supplied must be conditions of the air conditioning and replaced, use the same or equivalent wire. refrigeration institute (ARI). This chart may be 9. Check all electrical connections inside control box for tightness. used to approximate the charge if ARI rating 10. Do not attempt to operate unit until service valves conditions cannot be obtained. ARI rating have been opened. conditions are equivalent to DOE test "A" 11. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize conditions. See product data literature for required between high and low side before starting. indoor air flow rates and for use of line lengths 12. It is imperative to connect 3Ø field power to unit with over 15 Ft. correct phasing. wrong phasing will cause reverse 3. Carefully relieve refrigerant pressure within this rotation of scroll compressor which will result in reduced current draw, elevated noise level and unit before final disposal. improper operation. If rotation is reversed, simply interchange any two of the three power connections 319390-401 REV.C on field side. A94414 Fig. 3—561(C, W)030, 036, 042, 048, 060 208/230v and 561C036, 042, 048, 060 460v, 3 Phase, 60 Hertz —3— SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training © 1999 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 [ ] Classroom Service Training —4— Printed in U.S.A. 561c186 Catalog No. 5356-108