25HCB6 Comfortt Series 2---Stage Heat Pump with Puronr Refrigerant 2 To 5 Nominal Tons Wiring Diagrams CONNECTION DIAGRAM BLU *SR BRN 2 1 5 *CHS *SC BLK *CH BLK or RED RED or BLK L1 C BLK YEL 11 21 23 23 S R YEL EQUIP GND BLK RED BLK BLU RVSR R AUXR W2 R RED CTD 30 ORN PNK R CB C Y O W2 R E L PNK DFT INDOOR UNIT TERMINAL BLOCK G INDOOR THERMOSTAT (NOTE #5) NOTES: 1. COMPRESSOR AND FAN MOTOR FURNISHED WITH INHERENT THERMAL PROTECTION. 2. TO BE WIRED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (N.E.C.) AND LOCAL CODES. 3. N.E.C. CLASS 2, 24 V CIRCUIT, MIN. 40 VA REQUIRED, 60VA ON UNITS INSTALLED WITH LLS. 4. USE COPPER CONDUCTORS ONLY FROM DISCONNECT TO UNIT. 5. MUST USE THERMOSTAT AND SUB-BASE AS STATED IN PRE-SALE LITERATURE. 6. IF INDOOR SECTION HAS A TRANSFORMER WITH A GROUNDED SECONDARY, CONNECT THE GROUNDED SIDE TO "C" ON THE CIRCUIT BOARD. 7. IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED, MUST BE REPLACED, USE THE SAME OR EQUIVALENT WIRE. 8. CHECK ALL ELECTRICAL CONNECTIONS INSIDE CONTROL BOX FOR TIGHTNESS. 9. DO NOT ATTEMPT TO OPERATE UNIT UNTIL SERVICE VALVES HAVE BEEN OPENED. 10. USE CONDUCTORS SUITABLE FOR AT LEAST 75ºC (167ºF). DIP SWITCH SETTINGS 30 MINUTES 2 3 1 OR (DEFAULT) 90 MINUTES 60 MINUTES 2 3 60 1 2 OR 120 MINUTES 120 3 1 OR 90 2 3 ON 1 2 *DTS * HPS CTD T2 CONT C LOGIC NOTE YEL WHT BLK ORN RED Y2 * LPS C HK32EA003 C Y O W2 R E L W3 G * UTS RVS ORN DFT C Y O W2 R T1 BRN/YEL O 90 *CS Y Y C SPEED UP 60 LOGIC YEL/BLU T2 LOGIC DFT Y2 Y2 BLU / PNK C 120 DFT AUXR LOGIC C RVSR BLU / PNK T1 SPEED UP O YEL / PNK OF2 OF RVS Y 1 OF1 * HPS RED DR OF1 F CAP BLK * DTS YEL / PNK OFM DR O BLK H C OFM BRN/YEL * UTS * LPS 30 1 * SR * CH * ST +t° *SC 2 5 * CHS YEL YEL/BLU CONT 23 23 S EQUIP GND COMP BRN L2 COMP C R CONT 11 21 BLK *CS BLK BLU F SCHEMATIC DIAGRAM (LADDER FORM) L1 *ST +t YEL C CONT L2 208/230 1Ø POWER SUPPLY H BLK BLK BLU CAP YEL 3 QUIET SHFT OFF (DEFAULT) FIELD SELECTABLE OPTIONS FOR TIME PERIOD BETWEEN DEFROST CYCLES (MINUTES) JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE 1) MOMENTARILY SHORT PINS AND RELEASE TO BYPASS COMPRESSOR OFF DELAY. 2) SHORT FOR 5+ SEC. AND RELEASE FOR FORCED DEFROST. 3) PERMANENT SHORT WILL BE IGNORED. DEFROST WILL TERMINATE IN 30 SEC. IF DFT OPEN. DEFROST WILL TERMINATE NORMALLY IF DFT IS CLOSED. THIS DEFROST CONTROL BOARD CONTAINS A FIVE MINUTE SHORT CYCLE PROTECTOR. A FIVE MINUTE DELAY WILL OCCUR BETWEEN COMPRESSOR OFF/ON CYCLES. -LEGEND- FACTORY POWER WIRING FIELD POWER WIRING FACTORY CONTROL WIRING FIELD CONTROL WIRING CONDUCTOR ON CIRCUIT BOARD COMPONENT CONNECTION 1/4 - INCH QUICK CONNECT TERMINALS FIELD SPLICE JUNCTION PLUG RECEPTACLE AUXR AUXILLARY HEAT RELAY CAPACITOR (DUAL RUN) CAP CRANKCASE HEATER *CH *CHS CRANKCASE HEATER SWITCH COMP COMPRESSOR COMPRESSOR TIME DELAY CTD CONT CONTACTOR CIRCUIT BOARD CB COMPRESSOR SOLENOID *CS DEFROST THERMOSTAT DFT DEFROST RELAY AND CIRCUITRY DR *DTS DISCHARGE TEMPERATURE SWITCH *HPS HIGH PRESSURE SWITCH *LPS LOW PRESSURE SWITCH OFM OUTDOOR FAN MOTOR REVERSING VALVE SOLENOID RVS RVSR REVERSING VALVE SOLENOID RELAY START CAPACITOR *SC START RELAY *SR START THERMISTOR *ST *UTS UNLOADER TEMP SWITCH * MAY BE FACTORY OR FIELD INSTALLED 335977-101 REV. A Fig. 1 – Wiring Diagram — Model sizes 2--5 tons, 208/230--1 Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 09/09 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 2 Catalog No: 25HCB6---1W Replaces: New