L-69-80 LOAD BANK MANUAL CONTAINS OPERATING INSTRUCTIONS PARTS LIST WIRING DIAGRAMS SERVICE INSTRUCTIONS CANNON LOAD BANKS, INC. 502 PARK STREET PALMETTO, GA. 30268 770 - 463 - 0504 This load bank is manufactured and protected under U. S. Patent number 4,445,047 CAUTION THIS LOAD BANK IS DESIGNED FOR THE TESTING AND SERVICING 480/208V 60HZ POWER UNITS. THESE UNITS HAVE THE POTENTIAL OF DELIVERING A LETHAL SHOCK. THIS LOAD BANK SHOULD BE USED ONLY BY TRAINED AND QUALIFIED PERSONNEL. THIS LOAD BANK IS DESIGNED FOR TEMPORARY USE ONLY. THE LOAD RESISTORS ARE ENERGIZED WHEN THE RATE SWITCH IS OFF, THEREFORE DO NOT INSERT ANY OBJECTS IN THE GRILL ASSEMBLY. DO NOT BLOCK THE AIR FLOW OR USE IF THE AIR FLOW IS REVERSED. CANNON LOAD BANKS, INC. MANUAL FOR L-69-80 LOAD BANK TABLE OF CONTENTS SUBJECT SECTION PAGE DESCRIPTION PURPOSE OF LOAD BANK RATING OF LOAD BANK LOAD BANK DESCRIPTION CONTROL PANEL LAYOUT CONTROL DESCRIPTION 1-1 1-2 1-3 1 1-4 1 1 1 2 3 2 2 2 2 2 1 3 5 7 9 3 3 3 3 3 3 3 3 1 2 3 4 5 6 7 8 FIGURE 1 - 1 FIGURE 1 - 2 OPERATION TESTING 120VAC SINGLE PHASE TESTING 240VAC SINGLE PHASE TESTING 208VAC THREE PHASE TESTING 240VAC THREE PHASE TESTING 480VAC THREE PHASE PARTS PARTS INFORMATION CONTROL PANEL PARTS LAYOUT CONTROL PANEL PARTS LIST INTERIOR PARTS LAYOUT INTERIOR PARTS LIST FAN PANEL PARTS LAYOUT FAN PANEL PARTS LIST VENDOR LIST FIGURE 3 - 1 FIGURE 3 - 2 FIGURE 3 - 3 SERVICING GENERAL SERVICING REPLACING FAN FIGURE 4 - 1 4-1 4-2 1 2 WIRING DIAGRAMS INTERIOR W IRING FAN PANEL WIRING SCHEMATIC DIAGRAM FIGURE 5 - 1 FIGURE 5 - 2 FIGURE 5 - 3 5 5 5 1 3 5 CANNON LOAD BANKS, INC. DESCRIPTION 1-1 PURPOSE OF LOAD BANK: The L-69-80 is a portable load bank designed to be used for field servicing and testing 60HZ generators and UPS systems. It can be used for checking cables after they have been replaced or repaired. The load bank can also be shipped to different locations using the carrying case. 1-2 RATING OF LOAD BANK: The L-69-80 is rated at 100 KW full load when the input voltage is 480VAC and 80 KW when the input voltage is 208VAC with all five load steps turned on. The load steps are 12.5KW, 12.5KW, 25KW, 25KW and 25KW at 480VAC, 5KW or 10KW, 10KW, 20KW, 20KW, 20KW at 208VAC. 1-3 LOAD BANK DESCRIPTION: The load bank uses a 120VAC power source to operate other than the power being tested. The different sides of the load bank are shown in fig. 1-1. The air enters the right side (fan side) and exits the left side. <<<< AIR FLOW <<<< LEFT SIDE---------------------------- -------------- RIGHT SIDE (FAN SIDE) FIGURE 1-1 LENGTH WIDTH HEIGHT WEIGH 22 IN. 8 IN. 21 IN. 60 LBS. CANNON LOAD BANKS, INC. PAGE 1 SECTION 1 CONTROL PANEL PARTS VOLTMETER AMMETER L-69-80 100KW AT 480 VAC 80KW AT 208VAC 60KW CONTINOUS AT 208VAC 300 200 100 400 100 500 0 150 50 200 0 250 600 AC AMPS AC VOLTS 60 58 62 55 A B C L1 L2 L3 65 FREQUENCY METER HERTZ POWER INDICATOR LIGHTS L2-L3 L1-L2 L3-L1 480VAC OFF METER SWITCH MAIN MAIN SWITCH 208VAC METER RATE SWITCHES LOAD OFF 12.5KW 12.5KW 10KW 10KW 5KW @20 8V A METER TEST JACKS 25KW 20KW 25KW 20KW OFF B C N N L1 FIGURE 1-2 POWER RECEPTACLE L3 CANNON LOAD BANKS, INC. 25KW 20KW PAGE 2 L2 SECTION 1 1-4 CONTROL DESCRIPTION: The following is a description of the controls on the control panel (see figure 12 on page 2). VOLT METER - A 600 volt meter used to measure the line to line voltage on the power cable. L1-L2, L2-L3, L3-L1 can be selected using the meter selector switch. The meter should read approximately 480 volts when testing 480VAC systems, and 208VAC when testing 208VAC systems. AMMETER - A 250 amp ammeter used to measure the load being used by the load bank. It monitors “A” phase. FREQUENCY METER - A 55-65 HZ meter used to measure the frequency of the power unit. It should read approximately 60HZ. METER SWITCH - Switch used to select L1-L2, L2-L3, and L3-L1 on the voltmeter. RATE SWITCHES - Switch used to select the desired rate on the load bank. The rates are as follows: 480VAC 1. 2. 3. 4. 5. 12.5 KW balanced load 12.5 KW balanced load 25 KW balanced load 25 KW balanced load 25 KW balanced load 208VAC 1. 2. 3. 4. 5. 5 10 20 20 20 KW KW KW KW KW or 10 KW balanced balanced balanced balanced balanced load load load load load POWER INDICATOR LIGHTS - These lights will light to indicate power on A, B, and C phase. All three lights should be on when testing three phase circuits. METER TEST JACKS - This provides a place to connect an external meter. There is a test jack for each cable pin. POWER RECEPTACLE - The power cable from the equipment to be tested is plugged into the load bank through the receptacle. 120 VOLT POWER RECEPTACLE - A power cable is provided to plug the unit into a 120VAC outlet. (Not shown on drawing) CANNON LOAD BANKS, INC. PAGE 3 SECTION 1 BLANK OPERATION TESTING 120VAC SINGLE PHASE 2-1 SETTING UP THE LOAD BANK - Place the load bank in an area free from fuel, oil, or any other flammable substance. The load bank should be positioned so that any strong wind or air currents will flow with the air flow of the load bank. 2-2 APPLYING POWER - The load bank should be connected to the power unit to be tested with an output of 120VAC single phase. Make sure that the power unit is off before connecting the cable to the load bank. Use L1, L2 and N, the blue and red plug, when testing single phase circuits. L1 should be connected to the line out, L2 should be connected to neutral and the N cable with the green shrink should be connected to the ground of the unit being tested. Make sure the lug on L3 is insulated. Plug the power cable plug in to the load bank. The meter switch should be in the L1-L2 position. Turn on the output of the power unit. 2-3 CHECKING THE POWER - check the following: A. The amber light, “A” should be on. B. The voltmeter should read 120VAC on “A” phase. C. The frequency meter should read approximately 60HZ. D. The ammeter should read 0A. 2-4 APPLYING THE LOAD - If the above steps checked OK, turn on the main switch to 208VAC. The fans should start up and the airflow should be as indicated by the airflow arrow. Next turn on the load switch. Add the load desired with the rate switch. A. Step 1 is 1.7 KW B. Step 2 is 1.7 KW C. Step 3 is 3.3 KW D. Step 4 is 3.3 KW E. Step 5 is 3.3 KW Total load at 120VAC is 13.3KW. Check to see that the voltage and frequency does not drop beyond acceptable limits under load. 2-5 SHUTTING DOWN - Turn the load switch and rate switches to the off position and allow the load bank to cool down before turning the main switch to off. Turn the power unit off and disconnect the power cable plug. CANNON LOAD BANKS, INC. PAGE 1 SECTION 2 BLANK OPERATION TESTING 240VAC SINGLE PHASE 2-1 SETTING UP THE LOAD BANK - Place the load bank in an area free from fuel, oil, or any other flammable substance. The load bank should be positioned so that any strong wind or air currents will flow with the air flow of the load bank. 2-2 APPLYING POWER - The load bank should be connected to the power unit to be tested with an output of240VAC single phase. Make sure that the power unit is off before connecting the cable to the load bank. Use L1, L2 and N, the blue and red plug, when testing 240VAC single phase circuits. Plug the power cable plug in to the load bank and connect the L1 cable to L1 on the power unit, the L2 cable to L2 on the power unit and N to the ground on the power unit. MAKE SURE THE COPPER LUG ON L3 IS INSULATED. The meter switch should be in the L1-L2 position. Turn on the output of the power unit. 2-3 CHECKING THE POWER - check the following: A. The amber light, “A” and “B” should be on. B. The voltmeter should read 240VAC on “A” and “B” phase. C. The frequency meter should read approximately 60HZ. D. The ammeter should read 0A. 2-4 APPLYING THE LOAD - If the above steps checked OK, turn the main switch to 208VAC. The fans should start up and the airflow should be as indicated by the airflow arrow. Next turn on load switch. Add the load desired with the rate switch. A. Step 1 is 6.6 KW B. Step 2 is 6.6 KW C. Step 3 is 13.2 KW D. Step 4 is 13.2 KW E. Step5 is 13.2 KW Total load at 240Vac single phase is 52.8KW Check to see that the voltage and frequency does not drop beyond acceptable limits under load. 2-5 SHUTTING DOWN -Turn the load and rate switches to off. Allow the load bank to cool down before turning the main switch to off. Turn the power unit off and disconnect the power cable plug. CANNON LOAD BANKS, INC. PAGE 3 SECTION 2 BLANK OPERATION TESTING 208VAC THREE PHASE 2-1 SETTING UP THE LOAD BANK - Place the load bank in an area free from fuel, oil, or any other flammable substance. The load bank should be positioned so that any strong wind or air currents will flow with the air flow of the load bank. 2-2 APPLYING POWER - The load bank should be connected to the power unit to be tested with an output of208VAC 3 phase, plug in the 120VAC power cord. Make sure that the main switch and the load switch is set to off before connecting the cable to the load bank. Use L1, L2, L3 and N, the blue and red plug, when testing 208VAC 3 phase circuits. Plug the power cable plug in to the load bank. Turn on the output of the power unit. 2-3 CHECKING THE POWER - check the following: A. The amber light, “A”, “B”,”C” should be on. B. The voltmeter should read 208VAC. C. The frequency meter should read approximately 60HZ. D. The ammeter should read 0A. 2-4 APPLYING THE LOAD - If the above steps checked OK, turn the main switch to 208VAC. The fans should start up and the airflow should be as indicated by the airflow arrow. Next turn on the load switch. Add the load desired with the rate switch. A. Step 1 is 10 KW UP or 5KW DOWN B. Step 2 is 10 KW C. Step 3 is 20 KW D. Step 4 is 20 KW E. Step 5 is 20 KW THIS UNIT SHOULD NOT BE RUN FOR MORE THAN ONE HOUR CONTINOUS AT 208VAC, 80KW. THE RECEPTACLE IS RATED ONLY AT 63KW FOR CONTINOUS RUNNING. Check to see that the voltage and frequency does not drop beyond acceptable limits under load. Return the rate switch to the off position. 2-5 SHUTTING DOWN - Return the load and rate switches to the off position and, allow the load bank to cool down before turning the power unit off. Turn the power unit off and disconnect the power cable plug. CANNON LOAD BANKS, INC. PAGE 5 SECTION 2 BLANK OPERATION TESTING 240VAC THREE PHASE 2-1 SETTING UP THE LOAD BANK - Place the load bank in an area free from fuel, oil, or any other flammable substance. The load bank should be positioned so that any strong wind or air currents will flow with the air flow of the load bank. 2-2 APPLYING POWER - The load bank should be connected to the power unit to be tested with an output of 240VAC 3 phase, plug in the 120VAC power cord. Make sure that the main switch and the load switch is set to off before connecting the cable to the load bank. Use L1, L2, L3 and N, the blue and red plug, when testing 240VAC 3 phase circuits. Plug the power cable plug in to the load bank. Turn on the output of the power unit. 2-3 CHECKING THE POWER - check the following: A. The amber light, “A”, “B”,”C” should be on. B. The voltmeter should read 240VAC. C. The frequency meter should read approximately 60HZ. D. The ammeter should read 0A. 2-4 APPLYING THE LOAD - If the above steps checked OK, turn the main switch to 208VAC. The fans should start up and the airflow should be as indicated by the airflow arrow. Next turn on the load switch. Add the load desired with the rate switch. A. Step 1 is 12.5 KW B. Step 2 is 12.5 KW C. Step 3 is 25 KW D. Step 4 is 25 KW E. Step 5 is 25 KW Check to see that the voltage and frequency does not drop beyond acceptable limits under load. WHEN OPERATING AT 240 THREE PHASE, THE LOAD BANK SHOULD NOT BE OPERATED MORE THAN THIRTY MINUTES AT MAXIMUM LOAD. THE LOAD BANK CAN OPERATED CONTINUOUS AT 70KW. 2-5 SHUTTING DOWN - Return the load and rate switches to the off position and, allow the load bank to cool down before turning the power unit off. Turn the power unit off and disconnect the power cable plug. CANNON LOAD BANKS, INC. PAGE 7 SECTION 2 BLANK OPERATION TESTING 480VAC THREE PHASE 2-1 SETTING UP THE LOAD BANK - Place the load bank in an area free from fuel, oil, or any other flammable substance. The load bank should be positioned so that any strong wind or air currents will flow with the air flow of the load bank. 2-2 APPLYING POWER - The load bank should be connected to the power unit to be tested with an output of 480VAC 3 phase, plug in the 120VAC power cord. Make sure that the main switch and the load switch is set to off before connecting the cable to the load bank. Use L1, L2, L3 and N, the blue and red plug, when testing 480VAC 3 phase circuits. Plug the power cable plug in to the load bank. Turn on the output of the power unit. 2-3 CHECKING THE POWER - check the following: A. The amber light, “A”, “B”,”C” should be on. B. The voltmeter should read 480VAC. C. The frequency meter should read approximately 60HZ. D. The ammeter should read 0A. 2-4 APPLYING THE LOAD - If the above steps checked OK, turn the main switch to 480VAC. The fans should start up and the airflow should be as indicated by the airflow arrow. Next turn on the load switch. Add the load desired with the rate switch. A. Step 1 is 12.5 KW B. Step 2 is 12.5 KW C. Step 3 is 25 KW D. Step 4 is 25 KW E. Step 5 is 25 KW Check to see that the voltage and frequency does not drop beyond acceptable limits under load. 2-5 SHUTTING DOWN -Return the load and rate switches to the off position and allow the load bank to cool down before turning the power unit off. Turn the power unit off and disconnect the power cable plug. CANNON LOAD BANKS, INC. PAGE 9 SECTION 2 BLANK PARTS INFORMATION The following pages list the parts used in the load bank. All of the major parts are shown. Wire, screws, bolts, and small miscellaneous hardware are not listed. Parts that are purchased from a vendor will show a vendor name. These names refer to the vendor list is on page 8. Parts manufactured for or by Cannon Load Banks will not show a vendor name. A part number can be found by first locating the part on a drawing. After finding the part use the number to refer to the parts list on the opposite page. Each part will have a drawing number, Cannon Load Banks part number, description and the number used for each load bank. Parts should be ordered from the address below giving the machine model number, part number and the description. CANNON LOAD BANKS, INC. 502 PARK STREET PALMETTO, GA. 30268 PHONE: 770-463-0504 FAX: 770-463-2717 EMAIL: clbi@bellsouth.net CANNON LOAD BANKS, INC. PAGE 1 SECTION 3 CONTROL PANEL PARTS 1 2 200 300 100 400 100 150 50 200 500 0 0 250 600 AC AMPS AC VOLTS 4 60 58 62 55 A B C L1 L2 L3 65 3 7 HERTZ L2-L3 L1-L2 L3-L1 480VAC OFF MAIN 5,6 8 208VAC 10 METER 9 LOAD OFF 12.5KW 12.5KW 10KW 10KW 25KW 20KW 5 KW @20 8V 25KW 20KW 25KW 20KW OFF A B C N 11 N L1 12 FIGURE 3 - 1 13 L3 CANNON LOAD BANKS, INC. PAGE 2 L2 SECTION 3 CONTROL PANEL PARTS FIGURE 3-1 DRAWING NUMBER PART NUMBER DESCRIPTION VENDOR NO. NUMBER USED 1 MR-62 0 - 600V VOLT METER 1 2 MR-25 0 - 250A AMMETER 1 3 MR-60 55-65 HERTZ FREQUENCY METER 1 4 HD-25 HANDLE 2 5 KN-48 POINTER KNOB 1 6 SW-48 ROTARY SWITCH 3 POSITION METER SWITCH (KRAUS & NAIMER CA11 A23-000 E SOG521) 1 7 LT-25 250VAC AMBER LIGHT 3 8 SW-69 TOGGLE SWITCH DPDT, DELAY 1 9 SW-22 TOGGLE SWITCH DPST 6 10 SW-23 TOGGLE SWITCH DPDT, MID OFF 1 11 TP-10 TEST PIN 4 12 SB-13 SB CONNECTOR -2PIN-BLUE 1 13 SB-11 SB CONNECTOR-2PIN-RED 1 CANNON LOAD BANKS, INC. PAGE 3 SECTION 3 INTERIOR PARTS LAYOUT 1 2 10 16 14 15 7 5 4 3 6 13 12 9 8 11 FIGURE 3 - 2 CANNON LOAD BANKS, INC. PAGE 4 SECTION 3 INTERIOR PARTS FIGURE 3-2 DRAWING NUMBER PART NUMBER DESCRIPTION VENDOR NO. NUMBER USED 1 HD-10 FOLDING HANDLE 1 2 BX-27 20" X 21" X 8" ALUM BOX 1 3 SB-11 SB CONNECTOR-2PIN-RED-175A 1 4 SB-13 SB CONNECTOR-2PIN-BLUE-175A 1 5 FS-62 250 FUSE, 600V 3 6 FT-10 GLIDES 8 7 RC-12 100Ω, 5W RESISTOR 2 8 RY-35 RELAY, 120VAC, 30A, MAGNACRAFT 16 9 RC-75 7.5KΩ, 25W RESISTOR 1 10 RY-21 RELAY, 120VAC, 2PDT, 10A 1 11 SW-11 AIR FLOW SWITCH 1 12 CT-15 250:5 CURRENT TRANSFORMER 1 13 LR-25 25Ω RESISTOR 48 14 ZN-20 200V, 5W ZENER DIODE 2 15 RC-14 12KΩ, 11W RESISTOR 1 16 RC-39 39KΩ, 2W RESISTOR 2 * GL-24 RESISTOR GRILL 1 CANNON LOAD BANKS, INC. PAGE 5 SECTION 3 FAN PANEL PARTS LAYOUT 9 1 8 3 2 4 5 6 7 FIGURE 3 - 3 CANNON LOAD BANKS, INC. PAGE 6 SECTION 3 FAN PANEL PARTS FIGURE 3-3 DRAWING NUMBER PART NUMBER DESCRIPTION VENDOR NO. NUMBER USED 1 FS-11 FUSE 10A GLASS 1 2 TM-20 8 POSITION TERMINAL STRIP V-BEAU PRODUCTS (78008) 1 3 PS-30 30VDC 400W POWER SUPPLY RICHARDSON (NL3271) 1 4 FP-57 ALUM. FAN PANEL 1 5 GL-10 FAN GRILL CHROME V-MERRILL (B-22662) 12 6 FN-25 24VDC FAN EBM (W2G110-AK43-31) 12 7 TS-15 THERMAL SWITCH GEMLINE (L-155) 1 8 SW-12 TILT SWITCH 1 9 AC-12 120VAC PLUG CONNECTION 1 CANNON LOAD BANKS, INC. PAGE 7 SECTION 3 VENDOR LIST The following is a list of vendors for parts shown in the parts list. VENDOR Anderson Power Products 145 Newton St. Boston MA. 02135 Allied Electronics, Inc. 3425 Corporate Way, Suite A Duluth, Ga. 30136 Bussmann Manufacturing Distributed by Allied Control Design Supply 1939-F Parker CT Stone Mountain, GA. 30087 Cutler-Hammer Distributed by Peerless EBM Industries, Inc. Distributed by Peerless E.F. Johnson Distributed by Peerless Electric Supply Co. 433 Bishop St. Atlanta, Ga. 30325 Gemline Products, Inc. 12472 Edison Way Garden Grove, Ca. 92641 Merrill Manufacturing Corpation 236 South Genesee Street Merrill, WI. 54452 Peerless Radio Corporation 3101 towercreek Pkwy, Suite 590 Atlanta, GA. 30339 Syrelec Electronics Corp. Distributed by Control Design Vemaline Products 333 Strawberry Field Rd. Warwick, RI. 0288 CANNON LOAD BANKS, INC. PAGE 8 SECTION 3 GENERAL SERVICE There is no regular maintenance required on the load bank. There are no adjustments inside the load bank. It should however be checked periodically for defective fans, burned out light bulbs, and defective meters. To remove the fan panel, remove the screws around the outer edge. The meters can be removed and replaced from the front panel. The fan grills should be kept free of any trash. Do not place any objects in the fan or resistor grill. CANNON LOAD BANKS, INC. PAGE 1 SECTION 4 FAN REPLACEMENT The following are steps to take to replace a defective fan. 1. Remove the screws holding the fan panel to the load bank. 2. Remove the wires on the terminal strip coming from the load bank. 3. Drill out the rivets holding the fan (four on each side). 4. Lift up the fan and unplug the wires to the fan. Connect the plug to the new fan. 5. Rivet the new fan back to the fan panel and install the fan guard. 6. Install the wires back on the terminal strip and place the fan panel back on the load bank. Make sure that the wires are on the proper terminals. WHITE G-RED W-RED FAN 7,8,9, 10,11,12 FAN1,2 3,4,5,6 FAN 7,8,9, 10,11,12 + FAN1,2 3,4,5,6 + FIGURE 4 - 1 CANNON LOAD BANKS, INC. WIRES TO LOAD BANK PAGE 2 SECTION 4 L-69-80 INTERIOR WIRING RESISTOR PANEL 106 WHT 10 GRY 138 RED 5 VLT 105,106 WHT 1 GRY 4 BRN 2 ORG 3 BLU 7 GRN 5 VLT 6 YEL 9 RED 8 WHT 16 GRN LR1 115 W-GRY 140 YEL K3 13 BRN 2 ORG 114 BRN 139 BLU K2 8 WHT LR2 10 GRY LR3 101,102 WHT LR7 LR8 K6 19 GRY LR9 21 BLU 117,118 W-ORG LR14 28 GRY 30 BLU K9 K8 LR20 43 GRN 39 BLU 53 WHT 167 YEL 47 ORG LR31 48 BLU 50 VLT 49 BRN 176 YEL 56 O RG 127,128 GRN 62 WHT LR38 64 BLU LR43 LR39 LR44 61 GRN LR45 36 RED LR24 45 RED LR30 54 RED LR36 180 RED 62 WHT LR40 LR41 68 GRN 66 VLT LR18 53 WHT LR35 60 YEL 65 BRN 63 ORG 52 GRN 59 VLT 27 RED 44 WHT LR29 LR34 58 BRN 181 GRY 43 GRN 51 YEL LR33 57 BLU 56 ORG K15 175 BLU 94,95 WHT 59 VLT 68 GRN 173 YEL 174 RED 65 BRN K14 181 GRY 172 BLU 125,126 W-GRN 171 RED 93,94 WHT 55 GRY LR23 LR28 LR12 35 WHT 42 YEL LR27 LR32 34 GRN 41 VLT LR26 47 ORG 123,124 VLT 166 BLU K12 50 VLT 38 ORG 124 VLT 164 YEL 165 RED K11 44 WHT 163 BLU 46 GRY LR17 LR22 18 RED 26 WHT 33 YEL 40 BRN LR25 25 GRN LR16 LR21 38 ORG 95,96 WHT 41 VLT 96,97 WHT 158 YEL 29 ORG 162 RED 119,120 ORG 155 YEL 37 GRY LR11 32 VLT LR6 17 WHT 24 YEL 31 BRN LR19 16 GRN 15 YEL 23 VLT LR15 29 ORG 121,122 W-VLT 40 BRN LR13 LR5 LR10 22 BRN 20 ORG LR37 LR4 12 BLU 14 VLT 13 BRN 11 ORG 100,101 WHT 157 BLU 149 YEL 34 G RN 37 GRY 31 BRN 156 RED 148 BLU 32 VLT 99,100 WHT 35 WHT 25 GRN 154 BLU 118 W-ORG 153 RED 28 GRY K5 22 BRN 146 YEL 147 RED 19 GRY 102,103 WHT 145 BLU K13 61 GRN L3 C 126 W-G RN L2 B 170 YEL 6,15,24,33,42,51 FS3 ,60,67,134,137, 140,143,146,149, 152,155,158, 161,164,167,170, 173,176,179,103 YEL RP1 FS2 58 BRN 73 GRN N L1 A 55 GRY TP1 FS1 180,93 WHT TP2 71 RED 52 GRN TP3 75,77 BLU 122 W-VLT TP4 79 YEL 168 RED 169 BLU 3,12,21,30,39,48 , 57,64,133,136, 139,142,145,148, 151,154,157,160, 163,166,169,172, 175,178,102 BLUE 83 GRN 129 BLK 161 YEL 9,18,27,36, 45,54,70,101, 132,135,138, 141,144,147, 150,153,156, 159,162,165, 168,171,174, 177,180 RED 92 WHT K10 SW3 115 W-GRY 125 W-GRN 121 W-VLT 113 W-BRN 117 W-ORG 127 GRN 114 BRN 119 ORG 123 VLT 116 GRY 49 BRN SW4 SW5 46 GRY SW6 SW7 97,98 WHT 91 WHT 109 BRN SW8 20 ORG 110 ORG 120 ORG 80,82 YEL 54,55YEL 160 BLU 6 5 159 RED 152 YEL 112 G-RED 109 BRN 8 144 RED 3 76,78 BLU 137 YEL 7 SW1 136 BLU 4 135 RED 108 ORG 107 W-RED K7 26 WHT 1 K4 151 BLU 2 72,74 RED SW2 23 VLT 150 RED 87,130 WHT 81,85 BLK 98,99 WHT D4 D3 11 ORG 74 RED 116 GRY 78 BLU 143 YEL 82 YEL 14 VLT L3 142 BLU L2 17 WHT L1 131 WHT 141 RED M1 81 BLK 103,104 WHT 129 BLK K1 87 WHT 7 GRN 86 BLK 134 YEL 89 WHT 113 W-BRN 88 BLK 4 BRN M3 1GRY 133 BLU M2 104,105WHT 132 RED FRONT PANEL 67 YEL 69 WHT LR46 LR47 LR42 70 RED LR48 RELAY PANEL K16 92,180 WHT 112 G-RED 5 107 W-RED 6 86 BLK 90 WHT 7 85 BLK R7 69 WHT 63 ORG 177 RED 178 BLU 179 YEL R6 D2 84 W-RED TO T5 ON FAN PANEL D1 79,80 YEL 75,76 BLUE 71,72 RED R3 130 WHT 88 BLK 89 WHT 103 YEL R2 R4 102 BLU R5 101 RED GND 91 WHT NC 77 BLU CANNON LOAD BANKS, INC. BOTTOM PANEL 108 ORG COM 73,83 GRN SW9 NO CT1 SIDE PANEL 131 WHT R1 9,18,27,36, 45,54,61,70, 132,135,138, 141,144,147, 150,153,156, 159,162,165, 168,171,174, 177,101RED 110 ORG FIGURE 5-1 LEGEND 128 GRN 66 VLT 90 WHT CT1 D1-D2 D3-4 FS1-3 K1-16 K17 L1-3 LR1-48 M1 M2 M3 RP1 R1 R2 R3-5 R6,7 SW1 SW2 SW3 SW4 SW5-8 SW9 TP1-4 CURRENT TRANSFORMER 250:5 ZENER DIODE , 200V, 5W ZENER DIODE , 150V, 5W FUSE, 250A, 600V RELAY, 120VAC 3PDT 30A, MAG RELAY, 120VAC 2PDT MIDTEX LIGHT, NEON 250V LOAD RESISTOR 25 METER,55-65 HERTZ METER, 0-250A METER, 0-600 VOLT RECEPTACLE, 4 POLE 175A 7.0K RESISTOR 25W RESISTOR, 12K 11W RESISTOR, 100 , 5W RESISTOR 39K , 2W SWITCH, ROTARY 3 POS METER SWITCH, TOGGLE DPDT, DELAY SWITCH, TOGGLE SPST SWITCH, TOGGLE DPDT MID OFF SWITCH, TOGGLE DPST SWITCH, AIR FLOW TEST PINS 84 W-RED PAGE 1 SECTION 5 BLANK FAN PANEL WIRING 8 W-R ED 9 G-GR N 3 G-GR N FS4 +F1,F2,F3, F4 ,F5,F6 +F7 ,F8 ,F9, F10 ,F11,F12 -F1,F2 ,F3 , F4,F5,F6 -F7 ,F8,F9, F10 ,F11,F12 2 ,4 RED 6 ,7 BLK FROM L OAD BAN K V W-R ED 8 W-R ED G-R ED 1 G-R ED WH T 10 WHT AL L WIR ES FR OM FAN S ARE BL AC K 1 0A F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 3 G-GR N 5 G-GR N SW 11 11 WH T 1 G-R ED 5 G-GR N N L PS- 1 – + 6,7 2,4 BL K R ED F12 SW1 0 1 0-WH T 11 -WHT FIGURE 5 - 2 CANNON LOAD BANKS, INC. PAGE 3 SECTION 5 BLANK L-69-80 SCHEMATIC AC1 RP1 Ln1 FS1 Ln2 FS2 Ln3 N FS3 L2 L1 L3 GND FS4 GND CT1 M2 R5 K2 LR 1 LR 2 K2 LR 3 LR 4 K2 LR 5 LR 6 K4 LR 7 LR 8 K4 LR 9 LR 10 K4 LR 11 LR 12 K7 LR 13 LR 14 D2 K1 R4 K1 TP4 TP1 TP2 K17 TP3 R3 K1 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 K3 K3 -+ K3 PS-1 N L SW2 K5 K5 L3 SW1 L2 L1 SW11 SW10 M3 K5 D4 R6 L3 L1 K6 K6 K9 K9 K17 L2 SW4 12.5KW(10 KW) K1 K2 SW5 12.5KW(10 KW) K3 K4 K9 K10 SW6 25KW(20 KW) K5 K6 K7 K10 K8 K10 SW7 25KW(20 KW) K9 K10 K13 K11 K13 K13 M1 SW3 R7 K6 R1 SW9 D3 K7 LR 15 LR 16 K7 LR 17 LR 18 K8 LR 19 LR 20 K8 LR 21 LR 22 K8 LR 23 LR 24 K11 LR 25 LR 26 K11 LR 27 LR 28 K11 LR 29 LR 30 K12 LR 31 LR 32 K12 LR 33 LR 34 K12 LR 35 LR 36 K15 LR 37 LR 38 K15 LR 39 LR 40 K15 LR 41 LR 42 K16 LR 43 LR 44 K16 LR 45 LR 46 K16 LR 47 LR 48 D1 R2 LEGEN D AC 1 CT1 D1 -D2 D3 -4 FN1-1 2 FS1-3 FS4 K1 -16 K1 7 L1-3 LR1-4 8 M1 M2 M3 Ps1 RP1 R1 R2 R3 -5 R6 ,7 SW1 SW2 SW3 SW4-8 SW9 SW10 SW11 TP1-4 12 0VAC RECEPTACLE CU RREN T TRAN SFORMER 25 0:5 ZENER DIODE, 2 00V, 5W ZENER DIODE, 1 50V, 5W FA N 2 4VDC FUSE, 2 50A , 60 0V FUSE, 1 0A RELAY, 1 20VAC 3 PDT 30 A RELAY, 1 20VAC 4 PDT 5A LIGHT, NEON 250 V LOA D RESISTOR 25 METER,50-6 5 HERTZ METER, 0 -250 AMP METER, 0 -600 VOLT POWER SU PPLY REC EPTACLE, 4 POLE RESISTOR,7.0K ,25 W RESISTOR, 12K , 11W RESISTOR, 100 , 5W RESISTOR, 39K , 2W SWITCH , ROTAR Y 3 POS METER SWITCH , TOGGLE DPDT, DELAY SWITCH , TOGGLE DPDT, MID OFF SWITCH , TOGGLE DPST SWITCH , AIR FLOW THERMA L SWITCH 15 5° MERC URY SWITCH TEST PINS K12 SW8 25KW(20 KW) K13 K14 K14 K15 K14 K14 CANNON LOAD BANKS, INC. K16 ( ) IND IC ATES KW AT 20 8 VOLTAGE FIGURE 5-3 PAGE 5 SECTION 5 BLANK