Liebert® IntelliSlot® Webcard Version 5.300.2_082246 Firmware Release Notes February 6th, 2014 This document outlines: 1. Version and Compatibility Information 2. What’s New 3. Upgrade Instructions 4. Known Issues =================================================================================== 1. Version and Compatibility =================================================================================== This release contains the following firmware version: IS-WEBCARD_HID9_5.300.2_082246 This release is compatible with the following Liebert IntelliSlot communication cards: IS-WEBCARD This release is compatible with the following Liebert power and thermal management equipment: Liebert GXT™ Liebert GXT4™ (new) Liebert GXT2U™ Liebert Nfinity® Liebert GXT3™ Liebert PowerSure PSI™ (prior to July 2008) This release supports the following communication interfaces: Communication Protocol Communication Card HTTP/ HTTPS SNMP v1,v2c,v3 Email SMS Telnet Modbus/ BACnet Emerson Protocol Remote Service Delivery IS-WEBCARD -- -- -- =================================================================================== 2. What’s New =================================================================================== This release contains the following enhancements: Support for the Liebert GXT4/GXT4 Dual Inverter UPS product family with ECO Mode and Outlet Control Supports display of the IS-WEBCARD’s network address on the GXT4 UPS’s local display 1 This release also contains fixes for the following issues: Component SNMP Web Card HTTP Email HTTP Description The ifDescr OID now has a populated value. A small memory leak has been corrected that in rare cases may cause the Web Card to become unresponsive or automatically reboot. This has been corrected. Enhancements have been made to the UPS Power Flow display. An incorrect Email configuration setting could lead to the Web card refusing TCP connections. This has been corrected. Corrected a number of browser-related support issues for Chrome, FireFox, and Internet Explorer. =================================================================================== 3. Update Instructions =================================================================================== The IS-WEBCARD may be updated to this firmware version using the web-based Firmware Upload feature. Please refer to the Firmware Updates section of the Liebert IntelliSlot Web Cards Firmware Upgrade Manual (SL-52625). =================================================================================== 4. Known Issues =================================================================================== Component Description 2