Backup Power Solutions for: Emergency Lighting Applications UL 924 Emergency Lighting UPS Underwriter’s Lab 924 standard has long applied to emergency lighting and power equipment, intended for connection to branch circuits of 600 volts or less. Such equipment shall automatically supply illumination or power or both to critical areas and equipment in the event of failure of the normal electrical supply, in accordance with Article 700 or 701 of the National Electrical Code, NFPA 70, the Life Safety Code, NFPA 101, the Fire Code, NFPA 1, the International Building Code, IBC, and the International Fire Code, IFC. Compliant building lighting must provide at least 90 minutes (UL924) of battery powered illumination, even under extreme conditions such as electrical surges and full loads, to ensure building occupants are provided time to evacuate. Emergency lighting shall engage automatically and immediately after a primary power failure. In applications with an appropriate utility backup, such as a generator, UL924A may qualify and shorten the UPS/inverter battery time to 30 minutes or less. It should be noted that UL924 and UL924A are nationwide standards and that differing state/local codes have jurisdiction. UL924 Compliant Liebert UPS Systems Emerson offers numerous alternatives to address almost any facility’s back-up power needs. Below are the Liebert UL compliant UPS systems for emergency lighting and power. Please refer to the appropriate UPS information page for details. UPS Product Name Phase Compliant Capacity Output Voltage UL Standards Liebert® eXM™ Three Phase 10 – 60 kVA/kW 208V/120V UL924 UL924A UL1778 Liebert APM™ Three Phase 15 – 60 kVA/kW 208V/12 0V UL924 UL1778 Liebert NX™ Three Phase 40 – 120 kVA/kW 480V/277V UL924 UL1778 Emerson Network Power - Global Headquarters 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 United States Of America 800 877 9222 Phone (U.S. & Canada Only) 614 888 0246 Phone (Outside U.S.) 614 841 6022 FAX Contact@EmersonNetworkPower.com EmersonNetworkPower.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2015 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2015 Emerson Electric Co. All names and logos referred to herein are trade names, trademarks or registered trademarks of their respective owners. ® Liebert is a registered trademark of the Liebert Corporation. SL-70104 (R11/15) Printed in USA