Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Traffic Signal Junction Cabling Design Certification for ELV Systems Part no. 667/DS/20664/048 THIS DOCUMENT IS ELECTRONICALLY APPROVED AND HELD IN THE TS DOCUMENT CONTROL TOOL Issue 1 2 3 Change Ref First issue TS006376 TS006919 Date October 2007 March 2012 April 2013 Company/Dept. Name Prepared By Siemens Mobility, Traffic Solutions Dave Brocklehurst Checked and Released Siemens Mobility, Traffic Solutions David Martin Function Senior Product Engineer Product Engineering Manager March 16 March 16 Signature Date COPYRIGHT STATEMENT The information contained herein is the property of Siemens plc. and is supplied without liability for errors or omissions. No part may be reproduced or used except as authorised by contract or other written permission. The copyright and the foregoing restriction on reproduction and use extend to all media in which the information may be embodied Copyright Siemens plc 2016 All Rights Reserved Version Last Editor Document Name 3 Dave Brocklehurst 533574419 Page i of 19 Status Date Doc. No. Draft/Submitted/Issued 13 March 2013 667/DS/20664/048 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Siemens Mobility, Traffic Solutions, Sopers Lane, Poole, Dorset, BH17 7ER SYSTEM/PROJECT/PRODUCT : Site Reference: Site Address: Prepared By: Function : This Document is fully issued when this page is at a FULL numeric issue and all of the following pages are at the same full numeric issue below and is either signed if provided in paper form, or has the name of the person preparing it added above by the person who has edited the detail / designed the junction cabling layout. Issue : Change Ref : Date : dd/mm/yy This is a published work the copyright in which vests in Siemens plc. All rights reserved. The information contained herein is the property of Siemens plc. and is supplied without liability for errors or omissions. No part may be reproduced or used except as authorised by contract or other written permission. The copyright and the foregoing restriction on reproduction and use extend to all media in which the information may be embodied. Site Reference Issue 3 Page 1 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER CONTENTS 1 ....INTRODUCTION .......................................................................................................... 4 1.1 .Purpose ........................................................................................................................ 4 1.2 .Scope ............................................................................................................................ 4 1.3 .Related Documents ...................................................................................................... 4 1.4 .Glossary ........................................................................................................................ 4 1.5 .Use ............................................................................................................................... 4 2 ....GENERAL NOTES ON INSTALLATION WIRING ....................................................... 4 2.1 .Neutral Connections (Ground Returns ELV) ................................................................ 4 2.1.1 Introduction............................................................................................................. 4 2.1.2 Context ................................................................................................................... 5 2.1.3 Procedure ............................................................................................................... 5 3 ....CABLING ...................................................................................................................... 5 3.1 .Cable Maximum Loading (Limited by the heating effect) ............................................. 5 3.2 .Loading limited by Cable Voltage Drop (thus associated with cable length) ................ 6 4 ....DUCTING ................................................................................................................... 11 4.1 .Capacities ................................................................................................................... 11 5 ....CABLE IMPEDANCES ............................................................................................... 13 5.1 .1mm2 Armoured Cable .............................................................................................. 14 5.2 .1.5mm2 Armoured Cable ........................................................................................... 14 6 ....COMPLETION OF VERIFICATION CALCULATIONS ............................................... 15 7 ....APPENDIX A VERIFICATION CALCULATIONS ....................................................... 16 8 ....APPENDIX B COMPLEX DUCTING CAPACITIES .................................................... 18 LAST PAGE ...................................................................................................................... 19 Site Reference Issue 3 Page 2 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Issue History Site Reference Issue 3 Page 3 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 1 INTRODUCTION 1.1 Purpose This document is intended to allow an assessment to be made on the suitability of the cabling design for an ELV traffic controlled junction installed by TS using TS provided cable. Providing all of the criteria noted in the subsequent sections and sub sections are complied with within the junction design, the cable and terminations design can be certified as complying with BS7671 and Electrical Installation Certificates signed off. 1.2 Scope This document only applies to cables 998/4/70468 and 4/MC832 supplied by TS, and cable terminations supplied in TS traffic controllers and Pole Caps. 1.3 Related Documents BS 7671 667/SA/20664/000 667/HE/20664/000 1.4 IEE wiring Regulations Design and Manufacturer Supplied Information. Installation and Commissioning Handbook Glossary ELV 1.5 Extra Low Voltage Use The tables in the body of the document allow a quick check of the electrical design. For a more detailed check should one be required or if the values or extent of the tables are exceeded the calculation form in the appendix should be used. The process is to edit the data in this document for the particular customer / site and then provide a paper or magnetic copy to the customer, who should then forward it on to the appropriate installing company. To edit the forms in the appendices of this document, you will need Microsoft Excel, double click on them and they will open up in Excel to allow editing. When you have edited the data, click back on the body of the main word document and the modified tables will be copied back to the word document. Then save the word document in the normal way. Please remember to edit the document series number picking a base number appropriate to your TS base i.e. DEPOT and selecting the next variant in order. The site reference must also be edited in the footer to ensure each page indicates the site for which it is relevant. 2 GENERAL NOTES ON INSTALLATION WIRING The standard size of cable drum used in the field by TS is 250m; anything else is a special order. TSs Recommendations are that ELV and detector cabling are run in separate ducts, where ever possible. 2.1 Neutral Connections (Ground Returns ELV) For the purpose of the following text, for ELV systems the ground return is considered in the same way as a neutral return for a LV system. 2.1.1 Introduction Street wiring faults can sometimes affect the display of traffic signals on-street. Poor connections, for example in pole top termination blocks usually leads to the failure of signals to illuminate properly which may be detected by lamp monitoring where this is implemented. Site Reference Issue 3 Page 4 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 2.1.2 Context Where common neutral connections are used it is possible for the failure of a neutral connection to cause unexpected signal displays, where one or more signals within a given signal head are incorrectly illuminated simultaneously. This lack of neutral connection is not detectable by the controller because the signal voltage presented at the controller terminals does not exceed the required thresholds for conflict or correspondence monitoring. When incandescent signals are used a cable fault of this type usually causes the signals to be illuminated at a low level and is not particularly noticeable. For LED signals however it is possible for the signals to flash, at least at their 'dim' level. Although the rate of signal flashing is such that they are only typically illuminated for a very short time, less than the conflict / correspondence time defined in TR2500, it can be more noticeable than the display seen with incandescent lamps. 2.1.3 Procedure Normally this type of fault only affects a single signal head or pole and due to other signals displaying correctly is unlikely to cause signalisations that could be considered dangerous, so retrospective action is not essential. Therefore we are not mandating retrospective action on existing sites, however if the customer wishes to re-wire then we can do this on a chargeable basis However for new LED sites where it is desired to reduce the likelihood of incorrect displays, particularly involving green signals, it is recommended that individual neutral returns are used for each green signal. For existing incandescent sites where LED signals are being now fitted and spare cables cores are available these may be used to provide additional neutral connections. 3 3.1 CABLING Cable Maximum Loading (Limited by the heating effect) The ST900 ELV LSLS card supplies and monitors up to 8 off ELV signal head aspects, 8 off LED Wait indicators, or 4 off TS Nearsides. The LSLS card can also supply 8 off Demand Indicators The HPU card supplies and monitors up to 8 off ELV Reg Signs. It is therefore not necessary to supply more than 8 off loads through one core, but the following information is shown for completeness. The following is based upon the worst case with all cores carrying the specified current and the maximum number of any type of cable possible, i.e. the worst case condition (thus removing the need to calculate all scenarios),whilst also taking into account the controller maximum load per aspect drive. (See also LIMTS OF LOADING IMPOSED BY MAXIMUM DUCT CAPACITIES). Provided that the loading per core is kept below the maximum number of heads / maximum current value specified below, then the requirements of BS 7671 can be guaranteed. If loadings above these are required then Engineering at Poole should be consulted. This later is extremely unlikely. LOADING Core Size Amps ELV Reg Signs ELV Signal Head Aspects Red/Green Nearsides LED Wait and Demand Indicators 1.00 mm2 1.50 mm2 3.5 4 24 27 14 16 9 10 24 27 Site Reference Issue 3 Page 5 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 3.2 Loading limited by Cable Voltage Drop (thus associated with cable length) The ST900 ELV lamp loads are shown below, and will be used to calculate maximum cable lengths. Bright 48V TS ELV Regulatory Sign 7W TS Helios ELV (Vehicular or Far-Side Ped Signals) 12 W TS CLS Wait Indicator (for Far-Side Ped Signals) 12 W TS LED Wait Indicator (for Far-Side Ped Signals) 7W TS Red/Green Nearside Signals 18 W TS Ped Demand Indicator (for Near-Side Signals) 6W ST900 ELV Lamp Load (Watts) When estimating cable core and controller equipment requirements for the ST900 ELV Controller the maximum cable lengths defined in the following tables must be complied with. The voltage drop in the installation must be no more than 4% of the incoming supply. The tables should be consulted to ensure that the voltage drop is lower than this maximum for the selected core size and loading. If the voltage drop exceeds 4% the cores / conductors must be paralleled up to reduce it. In addition the following guidance should be observed: 1. Where multiple cores are required due to long cable runs it must be noted that this may require additional LSLS Outputs (and possibly an additional LSLS Card) in order to accommodate the additional terminations in the LSLS Backplanes. 2. Where common ground return connections are used it is possible for the failure of a ground return connection to cause unexpected signal displays, where one or more signals within a given signal head are incorrectly illuminated simultaneously. This lack of ground return connection is not detectable by the controller because the signal voltage presented at the controller terminals does not exceed the required thresholds for conflict or correspondence monitoring.It is therefore recommended that individual ground returns are used for each green signal. 3. The allowable lamp load per cable run is defined in the following tables. Refer to the above table to determine the total lamp load connected to each drive cable and each return cable. For each ‘out-going’ drive cable, determine the total load of all the signals supplied by that cable. This will typically be a single aspect (e.g. one Helios ELV signal) but could be higher where a green drive also powers a tactile unit for example. A single LED signal return core (equivalent to the neutral in an LV system) is to be provided for each Red, Amber, Green Signal (or Nearside Red / Green Signal). Where a common return core is used, the highest lamp load that may be illuminated at any one time needs to be determined. For a UK traffic signal head, one Helios ELV lamp load 12W is considered the highest for the return cable since only one aspect is ever illuminated; the short red/amber period is ignored. For a near-side pedestrian signal head, the figure is one near-side signal unless it shares the same return with a Demand Indicator or a Tactile Unit. Example, assuming a distance of 180 metres using 1.0mm 2 cable: Near-side ped drive cables: 18W each at 180 metres = 2 cores (each) Ped demand indicator drive cable: 6W at 180 metres = 1 core Site Reference Issue 3 Page 6 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Common return cable: 24W (6W+18W) at 180 metres = 3 cores 4. If required to minimise core usage it is permissible to common signal returns on the same pole as long as the total lamp load dependent on that return is considered and the cable length limitations defined in the table are observed. For example, two 12W RAG traffic signal heads require that a load of 24W is considered with a common return cable. (Note: please also consider the comments given in paragraph 2) 5. Regulatory signs should normally be cabled with a separate drive and return core. Where more than one regulatory sign is fitted to a pole, the drive and return for these may be common, as long as total load dependent on those cables is considered and the cable length limitations defined in the table are observed. If required to minimise core usage it is permissible to common regulatory sign and traffic signal returns on the same pole as long as the total load dependent on that return is considered and the cable length limitations defined in the table are observed. Example, assuming a distance of 100 metres using 1.0mm 2 cable: Reg Sign supply cable: 7W at 100 metres = 1 core RAG traffic signal drive cables: 12W at 100 metres = 1 core each (x3) Common return cable: 19W (12W+7W) at 100 metres = 1 core minimum but 2 cores recommended to allow an individual return for the green signal (see comments given in paragraph 2 ) . 100 metres – 1.0mm2 cable LSLS Card 12W RED DRIVE: 12W at 100m =1 CORE R A AMBER DRIVE : 12W at 100m =1 CORE GREEN DRIVE : 12W at 100m =1 CORE G GREEN RETURN COMMON RETURN: (12W+7W) 19W at 100m = 1 CORE HPU REG SIGN SUPPLY: 7W at 100m = 1 CORE It should be noted from looking at the table that above 100 metres, 2 cores would be required for the 19W common return, and above 160 metres, 2 cores would also be required for each 12W signal drive cable. 6. Tactile units are to be provided with a separate drive and return core. Tactile units driven from the same phase green can share a common drive and return core. For the purposes of assessing acceptable cable run lengths using the table, each tactile unit should be considered to be a 12W load. If required to reduce core usage, tactile units may share a return core with any LED signal return core on the same pole. If this option is exercised each tactile should be considered to be a 45W load for the purposes of assessing acceptable cable run lengths using the table. This figure is much higher than their normal running power, but is typical of the power consumed if the tactile device is physically held, stopping the motor. Site Reference Issue 3 Page 7 RS Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 7. The ELV solar cell should be provided with a drive and return core for connection of the solar cell supply and signal. The solar cell return can be commoned with the LED signal return. Its effect on the voltage drop is so small that it can be ignored. 8. Returns for digital inputs (for above ground detectors and pushbuttons etc on the same pole) may be commoned together, but must remain separate from the LED signal returns. 9. Audible units must be provided with a separate drive and return core. Audible units on the same Audible Driver Module may share a common drive and return core (up to 250m) if required to reduce core usage, but must remain separate from the LED signal returns and digital input returns. Site Reference Issue 3 Page 8 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Note NO MORE than 3 cores should be connected in parallel. The numbers in the cells within the tables indicate the number of cores required to meet the voltage drop requirement. 10m 15m 20m 25m 30m 35m 40m 45m 50m 60m 70m 80m 90m 100m 110m 120m 130m 140m 160m 180m 200m 225m 250m 275m 300m 325m 350m 375m 400m 7W 10 W 12 W 18 W 20 W 25 W 30 W 35 W 40 W 45 W 50 W 60 W 80 W 100 W 120 W 5m Lamp Load (Watts) Length of Cable Run (metres) – 1.0 mm2 Cable 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 1 1 1 1 1 1 1 1 1 1 2 2 2 3 3 1 1 1 1 1 1 1 1 1 2 2 2 2 3 3 1 1 1 1 1 1 1 2 2 2 2 2 3 3 1 1 1 1 1 1 2 2 2 2 2 3 3 1 1 1 1 1 1 2 2 2 2 2 3 1 1 1 1 1 2 2 2 2 2 3 3 1 1 1 1 1 2 2 2 2 3 3 3 1 1 1 1 2 2 2 2 3 3 3 1 1 1 2 2 2 2 3 3 3 3 1 1 1 2 2 2 2 3 3 3 1 1 1 2 2 2 3 3 3 1 1 1 2 2 2 3 3 1 1 2 2 2 3 3 1 1 2 2 2 3 3 1 2 2 2 3 3 1 2 2 3 3 1 2 2 3 3 2 2 2 3 3 2 2 2 3 2 2 3 2 2 3 2 2 3 Table 1 – ST900 ELV Cable Lengths: 1.0mm2 Site Reference Issue 3 Page 9 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 10m 15m 20m 25m 30m 35m 40m 45m 50m 60m 70m 80m 90m 100m 110m 120m 130m 140m 160m 180m 200m 225m 250m 275m 300m 325m 350m 375m 400m 7W 10 W 12 W 18 W 20 W 25 W 30 W 35 W 40 W 45 W 50 W 60 W 80 W 100 W 120 W 5m Lamp Load (Watts) Length of Cable Run (metres) – 1.5 mm2 Cable 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 1 1 1 1 1 1 1 1 1 2 2 2 2 3 3 1 1 1 1 1 1 1 1 2 2 2 2 3 3 1 1 1 1 1 1 1 2 2 2 2 2 3 3 1 1 1 1 1 1 1 2 2 2 2 2 3 1 1 1 1 1 1 2 2 2 2 2 3 3 1 1 1 1 1 1 2 2 2 2 2 3 1 1 1 1 1 2 2 2 2 2 3 3 1 1 1 1 1 2 2 2 2 3 3 3 1 1 1 1 2 2 2 2 3 3 3 1 1 1 2 2 2 2 3 3 3 3 1 1 1 2 2 2 2 3 3 3 1 1 1 2 2 2 3 3 3 1 1 1 2 2 3 3 3 1 1 2 2 2 3 3 1 1 2 2 2 3 3 1 2 2 2 3 3 1 2 2 3 3 3 1 2 2 3 3 1 2 2 3 3 Table 2 – ST900 ELV Cable Lengths: 1.5mm2 Site Reference Issue 3 Page 10 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 4 4.1 DUCTING Capacities Based on BS 7671 ‘Selection and Erection’ Appendix A Cable capacities on conduit and trunking section e) the following tables and rule of thumb has been produced. Duct Cable Cores 50mm 50mm 50mm 50mm Armoured Armoured Armoured Armoured 8 12 16 20 Number of cables allowed 3 2 1 1 50mm 50mm 50mm 50mm Un Armoured Un Armoured Un Armoured Un Armoured 8 12 16 20 4 3 2 2 100mm 100mm 100mm 100mm Armoured Armoured Armoured Armoured 8 12 16 20 13 8 7 6 100mm 100mm 100mm 100mm Un Armoured Un Armoured Un Armoured Un Armoured 8 12 16 20 19 13 11 10 It should be ensured that none of the conduits in the installation exceed these recommendations. Ducts should not be over filled with a visual check of the above it would appear as a maximum of 50% filled. Site Reference Issue 3 Page 11 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER For Detector Feeder Cables the following applies Duct Cable 50mm 50mm 50mm 50mm 100mm 100mm 100mm 100mm 1 Pair Armoured 2 Pair Armoured 1 Pair Unarmoured 2 Pair Unarmoured 1 Pair Armoured 2 Pair Armoured 1 Pair Unarmoured 2 Pair Unarmoured Number of cables allowed 4 3 7 5 17 13 31 23 A mixture of cable sizes i.e. a number of cables in a duct with different numbers of cores in the cables, becomes complex calculation (and appendix B can be used), however a rule of thumb without referring to the spreadsheet in appendix B, would be as follows Cable Type Armoured Duct 50mm Un Armoured 50mm Armoured 100mm Un Armoured 100mm 1 20 Core + 1 other lower size Cable + 2 other lower size Cable + 7 other lower size Cable + 11 other lower size Cable 1 16 Core + 1 equal or lower size Cable + 2 equal or lower size Cable + 7 equal or lower size Cable + 11 equal or lower size Cable 1 * 12 Core + 1 equal lower size Cable + 2 equal lower size Cable + 9 equal lower size Cable + 14 equal lower size Cable NOTE some customers have there own requirements for DUCT capacities and these must be complied with on contracts with those customers, check with customers and / or their requirements’ specifications. An Example would be. 50mm ducts should have no more than 2 armoured cables or 4 non armoured cables. If used in combination in the duct it can be taken that an armoured cable is equivalent to 2 non armoured. 100mm ducts should have no more than 5 armoured cables or 10 non armoured cables. If used in combination in the duct it can be taken that an armoured cable is equivalent to 2 non armoured. Site Reference Issue 3 Page 12 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Bend Radii in a Traffic Signal Junction Installation meet the requirements of IEE Regs On Site Guide, provided a) the conduits are not over filled (see earlier paragraphs with reference to duct capacities and, b) standard ‘Slow bends’ are fitted in conduits (e.g. for 50mm conduits 350mm radius, 100mm conduit 450mm radius), or chambers are fitted at such bend points allowing cable minimum bend radii to be met. Allowable bend Radii are For Armoured cable min bend radius is 6 X Dia For Un Armoured Cable min bend radius is 4 X Dia Cores 8 12 16 20 1 Pair 2 Pair 5 Armoured Cable Diameter 15.4 18.6 20.2 21.1 13.5 15 Min Bend 93.00 112.00 122.00 127.00 81.00 90.00 Un-armoured Cable Diameter 12.6 15.8 17.4 18.3 9.9 11.4 Min Bend 76.00 95.00 105.00 110.00 60.00 69.00 CABLE IMPEDANCES The ELV system only requires an Earth Loop Impedance test to be done on the Mains electrical supply to the controller cabinet, and not on the supply from the controller, which is less than 50VAC nominal. Consideration of ELI offers a degree of protection against an accidental short-circuit from a third party’s mains supply. Any third party LV supply must be separated from the TS ELV supply in all instances; it is recommended that the installation is entirely ELV. The approporiate impedances below should be combined and added with the Ze (earth loop impedance at origin) supplied by the Electricity supply authority or Local Authority. The combined value should not be greater than the required ELI value for a 10A fuse. Then, these values should be used to cross check the Earth Loop Impedances measured during the testing of the installation. The tables assume 1 core used, at measured at 20˚C, this allows comparison with the max values allowed in 667/HE/20664, as the max values have been reduced by the IEE regs ‘Rule of Thumb’, 0.8 to take into account being measured at 20˚C. Note the impedances below are the loop of 1 core plus the armouring. Site Reference Issue 3 Page 13 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 150 160 170 180 190 200 210 220 230 240 250 3.89 4.14 4.40 4.66 4.92 5.18 5.44 5.70 5.96 6.22 6.48 3.39 3.62 3.85 4.07 4.30 4.53 4.75 4.98 5.20 5.43 5.66 3.33 3.55 3.77 3.99 4.22 4.44 4.66 4.88 5.10 5.33 5.55 3.27 3.49 3.71 3.93 4.15 4.37 4.58 4.80 5.02 5.24 5.46 150 160 170 180 190 200 210 220 230 240 250 2.89 3.09 3.28 3.47 3.67 3.86 4.05 4.24 4.44 4.63 4.82 2.45 2.61 2.78 2.94 3.10 3.27 3.43 3.59 3.76 3.92 4.08 2.29 3.06 2.70 3.11 140 3.17 2.12 3.63 2.51 1.96 140 130 2.31 1.80 2.84 120 2.12 1.63 2.88 110 1.93 1.47 2.94 100 1.74 1.31 3.37 90 1.54 130 1.96 80 2.62 2.00 1.75 0.65 1.14 0.77 0.49 1.35 40 0.58 0.41 70 2.66 2.04 1.78 1.53 30 0.48 0.33 0.98 25 0.39 0.24 1.16 20 0.29 0.16 60 2.72 2.33 1.81 1.55 1.31 15 0.19 0.08 0.82 10 0.10 0.96 5 50 3.11 90 2.07 1.58 1.33 1.09 120 80 1.81 1.36 1.11 0.87 2.40 70 1.55 1.13 0.89 0.65 2.44 60 1.30 0.91 0.67 0.55 2.49 50 1.04 0.68 0.55 0.44 2.85 40 0.78 0.57 0.44 0.33 110 30 0.65 0.45 0.33 0.22 2.18 25 0.52 0.34 0.22 0.11 12 Number of Cores in the cable 8 Page 14 Issue 3 Site Reference 2.22 20 0.39 0.23 0.11 20 2.26 15 0.26 0.11 16 2.59 10 0.13 12 100 5 8 Number of Cores in the cable 1.5mm2 Armoured Cable 5.2 1mm2 Armoured Cable 5.1 Length of Cable Run Length of Cable Run Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 1.28 1.43 1.59 1.75 1.91 2.07 2.23 2.39 2.55 2.71 2.87 3.03 3.19 3.35 3.51 3.67 3.83 3.99 1.09 1.24 1.40 1.55 1.71 1.86 2.02 2.17 2.33 2.48 2.64 2.80 2.95 3.11 3.26 3.42 3.57 3.73 3.88 0.62 1.12 0.64 0.47 0.93 0.48 0.39 0.96 0.40 0.31 0.78 0.32 0.23 0.80 0.24 6 0.16 0.08 20 0.16 0.08 16 COMPLETION OF VERIFICATION CALCULATIONS It is required that the Verification calculations sheet in appendix A is filled out for the longest cable run and the shortest cable run. Double Click on the form (this will open it in EXCEL to allow editing), answer yes to macros. Once completed, Click back on the Word document page to save it back to the Word document. Once completed, the sheets should be checked for the following. NB The TARGET ELI value given in the blank form is that for use with a 10A fuse. a) b) c) Volt drop does not exceed max limit shown. MAX ELI does not exceed target max ELI. Minimum conductor size is less than the size of the cores used (The Steel wiring Armouring will also sufficient). Note for all of the above extra cores may be used to assist in bringing the design within requirements (no more than 3 cores in parallel). The completed sheets should be signed and filed with the design. Site Reference Issue 3 Page 15 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 7 APPENDIX A VERIFICATION CALCULATIONS Conductor Size 1.50 CABLE USED giving at 20 Celcius core resistance of giving at 20 Celcius armour resistance of Number of Cores 1 mm 2 8 12.1 ohms per km 7.19 ohms per km Note 1 VOLTAGE DROP Cable run length is Signal Load Watts Return Load Watts 250 meters 12 Number of paralleled Signal cores 12 Number of paralleled Return cores 1 Note 2 1 Note 2 Volt Drop From first principles is equal to the formula expressed on the next line ((Supply core *current)+(Return core *current)) * (Length of run *(core resistance per KM *70C factor 1.20)/1000)) voltage drop first principles using table 4D4B (IEE Regs BS7671) 1.815 Volts 1.813 Limit @ 48 votls 1.92 Note 3 MAXIMUM LOOP IMPDENCE CALCULATED Ze declared by supplier ( or County Council) Single Core Zs Zs 5.7775 5.1725 0.35 Ohms temp 70 celcius temp 20 celcius Note 4 If a single core does not give a low enough impdence the use of up to 3 can be tried n Cores where n= 1 5.7775 5.1725 Zs Zs temp 70 celcius temp 20 celcius Note 4 FAULT CURRENT (Maximum Earth loop impedence to achieve disconnect time) TARGET i.e. Max loop impedence Limit for controller as defined in 667/HE/20664/000 iss 13 to disconnect within the 5 seconds required. IS == 6.19 Note 5 (including rule of thumb reduction) for measurement at 20 celcius Note - Values obtained during commissioning testing are the values against which the installation is accepted MINIMUM CONDUCTOR SIZE (BASED ON FAULT CURRENT) If 32.22168519 Amps Minimum conductor size =Square root of ( I squared * Time) / K=115 K for standard PVC Minimum conductor size = 0.626520682 mm2 cross sectional area Based on 10 amp BS88 or equivalents used on ST800 and ST700 controllers and the disconnect times banded for 0.1,0.2,0.4 and 5 secs according to the time/current curves Prepared By Name……………………………..… Signature……………………………………………….. Job / Function: ……………………………………….. For and on behalf of Siemens plc, Trading As Siemens Traffic Controls (STC), Sopers Lane, Poole BH17 7ER Issue History 1 Site Reference Date? Issue 3 Page 16 Note 6 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER Notes on Design Certification:Note 1 Cabling and armouring impedances are based on worst case figures from TS cable suppliers. Note 2 For the Voltage drop for the designed installation to be acceptable it should be less than 4% as noted in section 525 of the IEE Regs BS7671. The calculations for voltage drop in this document are based on the worst case current for the aspects used in the installation. The currents assume the maximum power ratings shown in Section 3.2. Note 3 As noted in Note 1 above the IEE Regs sets the voltage drop limit within an installation at 4% (section 525) and the value highlighted in red (1.92 volts) is 4% of the nominal 48 volt supply. Note 4 For the earth loop impedance of the design to be acceptable, the calculated Earth Loop impedance must be less than the target impedance based on a 10A fused Mains supply, which is considered to be an appropriate fuse value for a third party supply. R1 Circuit Phase Conductor Resistance Ze Supply Impedance Circuit Earth Loop Impedance = Ze + R1 + R2 Short Circuit R2 Circuit Protective Conductor Resistance In the IEE regs all earth loop impedance calculations are normalised to the likely measurement temperature of 20 Celcius (as this allows for comparison when measuring this value during the test and inspection phase of an installation), hence the values calculated here are normalised to this same 20 celcius. The figures calculated include the impedance as for the supply as given by the electricity board supplier, and thus are higher by this same amount than the loop impedances given in section 5 of this document. Note 5 For the earth loop impedance of the design to be acceptable, the calculated Earth Loop impedance must be less than the target impedance based on a 10A fused Mains supply, which is considered to be an appropriate fuse value for a third party supply. Note 6 The minimum cross sectional area for a conductor is calculated as noted in the IEE regs 543-01-03, and provided the conductor size in the cable used is greater than this calculated figure, this part of the design is acceptable. Site Reference Issue 3 Page 17 Siemens Mobility, Traffic Solutions Sopers Lane, Poole, Dorset BH17 7ER 8 Duct 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 APPENDIX B COMPLEX DUCTING CAPACITIES Detector Feeder Armoured Unarmoured Armoured Unarmoured Allowed ? Size 8 12 16 20 8 12 16 20 1 Pr 2 Pr 1 Pr 2 Pr 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 100 1 Site Reference Issue 3 Page 18