Neutral earthing in low voltage Sector Energy PTI NC Theodor Connor Copyright © Siemens AG 2008. All rights reserved. Content Neutral earthing principle Load flow Fault conditions For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 1 01.2008 Th. Connor PTD SE PTI Types of system earthing (Fault Protection) according to IEC 60364-1 (2005-11) (part1) The system earthing is a essential part of protection against faults Source (Protection against indirect contact) L1 L2 L3 Exposed conductive parts of installation N Installation Earth For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 2 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (part2) The types of system earthing are defined via the relationship of power system and of exposed conductive parts to earth. The first letter shows the relationship of power system to earth. T: Direct connection of one point to earth I: All live parts isolated from earth The second letter shows the relationship of exposed conductive parts to earth T: Direct electrical connection of exposed conductive parts of the installation to earth, independently of the earthing of any point of the power system N: Direct electrical connection of the exposed conductive parts to the earthed point of the power system. Subsequent letter if any shows the arrangement of neutral and protective conductor: S: separated protective and neutral conductor (5wire); C: Neutral and protective function combined in a single conductor (4wire) For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 3 01.2008 Th. Connor PTD SE PTI Low voltage systems TN-S-System IT-System L1 L2 L3 N Impedance1) PE Exposed conductive part Earthing of system TT-System Definitions according IEC 60364-3 For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 4 01.2008 Th. Connor PTD SE PTI Low voltage systems Separated PE – and Neutral conductor in the whole interconnected LV-system TN-S-System TN-C-SSystem PE- and Neutral conductor combined in the feeding part of LV- system For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 5 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (TN-S System) Three phase load : Load current Source PE Installation Exposed conductive parts of installation For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 6 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (TN-S System) Single phase load : Load current Source PE Installation Exposed conductive parts of installation For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 7 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (TN-S System) Single phase short circuit : Fault current Source PE Installation Exposed conductive parts of installation For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 8 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (TN-C-S System) Single phase short circuit : Fault current Source Exposed conductive parts of installation For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 9 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (TT System) : Fault current Source Exposed conductive parts of installation Local earth For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 10 01.2008 Th. Connor PTD SE PTI Types of system earthing according to IEC 60364-1 (2005-11) (IT System) : Fault current Source Exposed conductive parts of installation Local earth For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 11 01.2008 Th. Connor PTD SE PTI Low voltage supply by TN-C PEN L1 Socket I L1 IN Screen Tokenring Socket I PEN Transformer IL1 = phase current IN = neutral conductor current IPEN = PEN conductor current Structure of building, pipe For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 12 01.2008 Th. Connor PTD SE PTI Low voltage supply by TN-C PEN L1 Socket On I L1 IN Istray Screen I L1 Istray Tokenring >0 Socket ΔU Istru Istray IPEN I L1 IL1 = phase current Transformer IN = neutral conductor current Istru = part returning via structure IStray= stray current via communication cable ΔU = voltage drop Structure of building, pipe For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 13 01.2008 Th. Connor PTD SE PTI Low voltage supply by TN-S PEN L1 Socket IN On I L1 Screen Tokenring ΔU =0 Socket IPEN IL1 = phase current Transformer IN = neutral conductor current ΔU = voltage drop Structure of building, pipe For internal use only. / Copyright © Siemens AG 2008. All rights reserved. Page 14 01.2008 Th. Connor PTD SE PTI