x2 - Frame 4 x1 - Frame 5
20-750-EMC1-F1
Frame 1
400…480V AC
20-750-EMC1-F2, F3
Frames 2…3
400…480V AC
Frame 6 shown
20-750-EMC1-F4, F5
Frames 4…5 *
400…480V AC
* Frames 6…7, 400…480V drives do not require
EMC cores or plates to meet EMC requirements.
20-750-EMC3-F3
Frame 3
600V AC
Frame 6 shown
20-750-EMC3-F4, F 5
Frames 4…5
600V AC
20-750-EMC3-F6, F7
Frames 6…7, IP00 (IP20 after installation)
600…690V AC
20-750-EMC5-F6, F7
Frames 6…7, IP54
600…690V AC
IMPORTANT Grounding and power jumper configuration must be appropriate for EMC applications. Refer to “Drive Power Jumper Configuration” in the PowerFlex
750-Series Installation Instructions (Publication 750-IN001 ) for details.
1
L1 L2 L3
I
O
2
DC+ DC–
0V
0V
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
3 4
600…690V – see
Step Frame Procedure
4
1
T20 #1
1.8 N•m (16 lb•in) x 2 (Frame 1)
2 Rockwell Automation Publication 750-IN006G-MU-P - February 2014
Step Frame Procedure
2…5
4 continued
T20 #1
1.8 N•m (16 lb•in) x 2 (Frame 2) x 3 (Frames 3…5)
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
5
All
Frame 2 Shown
Braid
Shield
Drain
Ground (PE)
Drain wires must be pulled back and wrapped in a 360 degree pattern over the shield/braid surface. Do Not fold the shield back.
Clamp
M10
5.6 N•m (50 lb•in)
#2
Environments with Vibration
Support Plate is recommended to provide core support
Rockwell Automation Publication 750-IN006G-MU-P - February 2014 3
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
Step Frame Procedure
6
1
Motor Cable (U, V, W)
Shielded
Input Power (R, S, T)
Shielded or Unshielded to PE Stud to PE Stud
1 Loop
(each wire)
I/O Shields
PE
T20 or F - 6.4 mm (0.25 in.)
1.8 N•m (16 lb•in)
2…3 Frame 2 Shown
I/O Signal Shields
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded to PE Stud
4 to PE Stud
IP20,
NEMA/UL Type 0
Flange Mount
PE
M4 (7 mm) 1.8 N•m (16 lb•in)
4…5 Frame 5 Shown
I/O Signal Wires
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded to PE Stud
I/O Signal Shields
I/O Signal Wires to PE Stud
IP20,
NEMA/UL Type 0
PE
Flange Mount
M6 (10 mm) 5.6 N•m (50 lb•in)
The motor cable ground wire connects to the motor PE stud in the drive, however it should not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives, publication DRIVES-IN001 for further information.
Rockwell Automation Publication 750-IN006G-MU-P - February 2014
Step Frame Procedure
4
3…5
T20 #1
1.8 N•m (16 lb•in) x 2 (Frame 3) x 3 (Frames 4…5)
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
Environments with Vibration
Support Plate is recommended to provide core support
5
6
All
3…4
Braid
Frame 4 Shown
I/O Signal Shields
Shield
Drain
Ground (PE)
Drain wires must be pulled back and wrapped in a 360 degree pattern over the shield/braid surface. Do Not fold the shield back.
Clamp
M10
5.6 N•m (50 lb•in)
#2
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded to PE Stud
I/O Signal Wires to PE Stud
IP20,
NEMA/UL Type 0
PE
Flange Mount
M6 (10 mm) 5.6 N•m (50 lb•in)
The motor cable ground wire connects to the motor PE stud in the drive, however it should not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives, publication DRIVES-IN001 for further information.
Rockwell Automation Publication 750-IN006G-MU-P - February 2014 5
6
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
Step Frame Procedure
6
5 continued
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded to PE Stud
I/O Signal Shields
6
IP00 to PE Stud
I/O Signal Wires
For use on Frame 6 IP00 drives. After installation, the drive achieves an IP20 rating.
IP20,
NEMA/UL Type 0
PE
Flange Mount
M6 (10 mm) 5.6 N•m (50 lb•in)
The motor cable ground wire connects to the motor PE stud in the drive, however it should not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives, publication DRIVES-IN001 for further information.
x6
The cable shield and drain wires must be terminated at the shield clamp on the conduit plate. The ground wire must be connected to the PE stud in the drive; however, it should not pass through the core.
x6 x4
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded
Rockwell Automation Publication 750-IN006G-MU-P - February 2014
T20 #1
2.6 N•m (23.0 lb•in) x6
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
Step Frame Procedure
6
6
IP54 continued The cable shield and drain wires must be terminated at the shield clamp on the conduit plate. The ground wire must be connected to the PE stud in the drive; however, it should not pass through the core.
Cabinet not shown
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded x6 x4
T20 #1
2.6 N•m (23.0 lb•in)
Rockwell Automation Publication 750-IN006G-MU-P - February 2014 7
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
Step Frame Procedure
6
7
IP00
For use on Frame 7 IP00 drives. After installation, the drive achieves an IP20 rating.
continued The cable shield and drain wires must be terminated at the shield clamp on the conduit plate. The ground wire must be connected to the PE stud in the drive; however, it should not pass through the core.
x8 x4 x4 x12
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded x2
M6 (10 mm)
5.2 N•m (46 lb•in)
T30
#1
5.2 N•m (46.0 lb•in)
8 Rockwell Automation Publication 750-IN006G-MU-P - February 2014
Step Frame Procedure
6 continued
7
IP54
PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
The cable shield and drain wires must be terminated at the shield clamp on the conduit plate. The ground wire must be connected to the PE stud in the drive; however, it should not pass through the core.
x4
Cabinet not shown
Adheres to cabinet x6
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded x2
7
6…7
Frame 6 Frame 7
T30
#1
5.2 N•m (46.0 lb•in)
Rockwell Automation Publication 750-IN006G-MU-P - February 2014 9
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone .
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page
, or contact your local Rockwell Automation representative.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
U.S. Allen-Bradley Drives Technical Support - Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, E-mail: support@drives.ra.rockwell.com
Online: www.ab.com/support/abdrives
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
*PN-239113*
PN-239113
Publication 750-IN006G-MU-P - February 2014