Induced AC creates problems for pipelines in utility corridors Imbalance in power transmission systems, place operator safety, system integrity at risk John S. Smart III, John Smart Consulting Engineers, Houston, Texas; Dirk L. van Oostendorp, Paragon Engineering Services, Houston, Texas; and William A. "Bud" Wood, ARCO Pipeline Company, Houston, Texas interference on pipelines located in utility corridors is a real and serious problem which can place both operator safety and pipeline integrity at risk. Installing pipelines in energy utility corridors containing high-voltage AC transmission lines subjects the pipelines to induced AC voltages. This can be caused by an imbalance in the transmission system, and by high voltages near transmission tower grounding systems resulting from lightning strikes and phase faults. When a long-term induced AC voltage exists on a pipeline, it can be dangerous and potentially life-threatening for operations personnel to touch the pipeline or appurtenances. In addition, pipe corrosion also can result from AC discharge. To address this problem, the pipelines must be grounded with a system that passes AC, but blocks DC, to both mitigate the AC and maintain the cathodic protection system on the pipeline. Background. Pipelines are now frequently being installed in electric power transmission right-of-ways, commonly referred to as "utility corridors." Installation of electric conductors, such as pipelines, near overhead high-tension lines can result in unusual pipeline problems. The problem of AC interference on buried pipelines has been known for well over 30 years.1 Only in the last 10 years, however, has the problem gained widespread recognition, due to improvements in pipeline technology and the increased tendency to locate pipelines in utility corridors near high-voltage electric transmission lines. When steel pipelines are installed close to overhead electric transmission lines, interference can occur between the electric lines and the pipeline. Electric power is transmitted in three phases; each carried on a separate line held aloft by pylons or towers along the right of way. Each sinusoidal AC power phase is 120° out of phase with the other two. If each phase is equal, the sum of the alternating currents in the three phases and the sum of the magnetic fields resulting from the alternating current in each phase should add up to zero Fig. 1. Phase vector relationship in three phase power transmission leading to induced pipeline potentials Modern pipe coating technology has exacerbated the AC mitigation problem by creating better coatings, leaving fewer defects in the coating for AC to go to ground. In fact, a bare pipeline would be a good answer to the induced AC problem. Both the Fusion Bonded Epoxy coatings used in the U.S. and Three Layer FBE/PE coatings used in Europe have made the problem of AC interference on pipelines more severe. In the past, less well coated pipelines had sufficient grounding, such that induced voltages were not a practical problem. AC interference. Three kinds of interference between AC transmission systems and pipelines can occur: Electrostatic or capacitive interference occurs in the immediate vicinity of the overhead power lines when the pipe is laid on a foundation that is well insulated from the ground. The pipeline picks up a voltage relative to the soil, which is proportional to the voltage in the transmission line. Welded pipe lengths near high-tension lines must be grounded when the nominal voltage in the overhead lines exceeds 110 kV and the length of the welded section exceeds more than a few hundred feet to 1,000 ft. Electrostatic coupling is of minor consequence after construction, since even the best pipe coating will allow sufficient leakage to earth, through defects, to effectively ground the electrostatic charge. Resistive or ohmic interference can occur when lightning strikes a transmission pylon, or when there is a phase-ground fault. When this occurs, a large voltage cone is created around the pylon grounding system. If a pipeline is located within this area, voltage can get onto the pipeline in the area within the voltage cone through coating defects. Anyone touching the pipeline outside the voltage cone could receive a shock from the potential between the pipeline and the surrounding soil. Protective measures for people are required if the contact voltage exceeds 65 V for long-term interference, or 1,000 V for short-term interference. These measures include wearing rubber boots, insulated gloves, or insulated protective padding. On no account, however, can there be any direct bond between the pipeline and the pylon grounding system. Special conditions arise if the pipeline is laid in the vicinity of a power station ground system or a transformer installation. If a lasting or transitory connection with the grounding installation results during a grounding fault, the grounding voltage will be transferred to the pipeline and appear outside the voltage cone as a contact voltage. Depending on the pipeline and its coating, the contact voltage decreases more or less quickly at greater distances. Electromagnetic or inductive interference on pipelines occurs when there is extended and close parallel routing with three-phase HVAC overhead transmission lines. The voltage is due to any phase imbalance in the lines Fig. 2. Different distances between the pipeline and each phase transmission line, along with phase imbalance, lead to induced AC interference on the pipeline (Fig. 2). The likelihood of interference increases with rising operating currents in the overhead lines, with increasing quality of the coating on the pipeline, and with the length of line parallel to and close to the HVAC transmission lines. Voltages are induced in the pipeline by magnetic coupling with the high-voltage lines, and results in currents flowing in the pipeline. These currents result in a voltage difference between the pipeline and the surrounding soil. Contact voltages. When a long-term induced AC voltage exists on the pipeline, resulting from long sections of parallelism with overhead electric transmission lines, it may not be safe to touch the pipeline or appurtenances. This "contact" voltage, or the difference between the line and the earth, can cause AC current to flow to ground through a person touching the line. When a metal structure, such as a pipeline, is under the influence of electrical fields and a person touches it, a current passes through their body to the earth. The amount of that current depends upon the electrical resistance through their body and how well he is grounded. The effects of AC current flowing through the body are given in Table 1 (NACE RP-01-77 (95), Table 3). Table 1. 60 Hz Alternating Current Values Affecting Human Beings (Table 3, NACE RP-01-77-95) Current Effects 1 mA or less No sensation — not felt 1–8 mA Sensation of shock — not painful. Individual can let go at will, muscular control not lost 8–15 mA Painful shock — Individual can let go at will, muscular control not lost 15–20 mA Painful shock — Individual cannot let go, muscular control lost 20–50 mA Painful shock — Severe muscular contractions, breathing difficult 50–100 mA (possible) Ventricular fibrillation — Death will result if prompt cardiac massage not administered 50–100 mA (certain) Defibrillator shock must be applied to restore normal heartbeat, breathing probably stopped 200 mA and greater Severe burns — Severe muscular contractions; chest muscles clamp heart and stop it during shock (ventricular fibrillation prevented). Breathing stopped — heart may start following shock, or cardiac massage may be required The upper limit on safe contact voltage is about 67 V AC. This is enough to potentially cause heart defibrillation, if the body is not protected through insulation. For safety’s sake, this voltage level has been reduced to 15 V AC in NACE RP-01-77 (95) as the maximum AC voltage permitted on the line, and is now generally accepted as the safe AC contact voltage allowed on a line. Lightning. Lightning is the discharge of charged particles between earth and clouds, or between clouds. Recently, it was discovered that the discharge follows a path of air ionized by cosmic rays, giving lightning its well-known jagged appearance. The lightning bolt voltage is in the range of 10,000,000 to 20,000,000 V, and the current discharged varies between 1,000 and 200,000 A. Total discharge takes from 50 to 100 microseconds. Typically, the total charge amounts to a few coulombs over multiple 20-microsecond discharges. When lightning strikes a transmission tower, a voltage cone is created around the tower grounding system which can affect a pipeline within the cone. The pipeline initially will have the potential of the ground, and current will flow across defects in the pipe coating. This creates an arc which can severely damage the pipeline. With the solid-state grounding system in place, the pipeline is shorted to the tower grounding system. The spacing of the solid-state devices is in part determined by the ability of the pipeline to carry the current from lightning strikes to the grounding system in between the grounding devices.2 Fault currents. A fault current is a current that flows from one conductor to ground, or to another conductor, due to an abnormal connection, including an arc, between the two. A fault current flowing to ground may be called a ground fault current. Fault currents can occur when insulation in the transmission network breaks down, such as when a lightning strike causes insulators on a transmission tower to break down, or if a wire breaks and falls to ground. If this occurs, there is a huge, but short-term, imbalance in the transmission system, and a high-ohmic voltage placed on the pipeline. When this occurs, there is a huge power imbalance, causing two things to happen: 1. There is a huge induced AC voltage on the pipeline, over the entire section affected by the phase imbalance 2. A huge voltage cone is set up where the fault goes to ground. The fault current can be several thousand amperes at several hundred thousand V, creating a considerable energy discharge. Fortunately, this lasts for only a few cycles. Any pipeline in the route is a preferred path for the current to follow, and it will develop a high voltage up and down the line as the fault current seeks to go to ground. Anyone touching the line at this time, such as operating a valve, or taking a cathodic protection reading, will sustain serious (even fatal) injuries, unless the voltage can be adequately grounded. Phase faults are the main reason that using sacrificial anodes or grounding rods for AC pipeline grounding is not a perfect solution. If a phase fault were to hit a zinc anode, it would be destroyed, and unable to ground the pipeline adequately. The pipeline would no longer be adequately grounded for future AC mitigation. There has been at least one reported instance in which a pipeline has been severely damaged by an electric arc. Undoubtedly, there are additional unreported cases.3 Faults can be protected against using circuit breakers on the power lines, which usually activate within a few cycles. Standards and references. In the U.S., NACE has recognized the problem of induced AC on pipelines, and originally issued a Standard Recommended Practice to control corrosion and safety issues in 1977. This standard has been updated and re-issued in 1995 as Standard RP01-77-95 "Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems," (NACE International, Houston, Texas, March 1995). Canada also has issued a standard, CAN/CSA-C22.3 No. 6-M91, "Principles and Practices of Electrical Coordination Between Pipe lines and Electric Supply lines," (Canadian Standards Association, 1991). Standards also exist in Europe, such as DIN VDE 0141, DIN VDE 0141 (Beuth-Verlag, Berlin, 1976). The NACE and Canadian standards recommend that the potential on a pipeline from AC be reduced to less than 15 V AC. Grounding systems. Grounding the pipeline to earth discharges the induced AC current, and reduces the potential on the line. The line can be grounded to earth by use of zinc anodes or galvanized steel grounding rods installed at periodic intervals, and this solution has been used extensively in the past. Using zinc anodes for grounding is effective, provided enough anodes or grounding rods are installed, and the system is not required to dissipate fault currents and lightning. Either extruded zinc ribbon can be laid in the ditch with the pipe, or deep rods can be driven into the ground. When the ground resistance decreases with depth, deep rods are preferred. Deep rods also are more convenient to install after construction. If the pipeline enters or leaves the transmission right-of-way, or has an insulating joint, grounding must be installed in close proximity to these locations. Interestingly, the better the coating on the line, the more grounding is required, as current does not leak as easily from a well coated line. Using fusion-bonded epoxy and three layer FBE/PE coatings has made the problem of AC interference on pipelines more severe due to capacitive effects. Cathodic protection. If grounding systems are used, they add load to the line’s cathodic protection system. The load is small, since the potential of zinc coated rods is close to the cathodic protection potential of the pipeline, and the area of the grounding rods is small. AC grounding, however, must be decoupled from the cathodic protection system. Otherwise, the cathodic protection will not be maintained on the line. De-coupling is achieved using polarization cells or new solid-state devices which pass AC over a pre-set threshold voltage, but which block DC current. (Top Photo) Typical polarization cell replacement installation, showing Kynar lead cable to pipeline and overhead electric tower. (Bottom Photo) Typical AC mitigation installation, showing lockable enclosures and cattle guard for protection. Polarization cells. These cells are passive devices that act as electrochemical safety switches. The magnitude and direction of current flow across a polarization cell depends on the electromagnetic field (EMF) applied across the cell. The cell consists of multiple pairs of stainless steel sheets immersed in a potassium hydroxide solution.4 DC current flow through a polarization cell causes a gas film to develop on the plates, offering a high resistance to low-voltage DC current. As the applied voltage across the cell increases, current flow through the cell also increases, causing the thickness of the polarization gas film to increase. The blocking voltage of a polarization cell is in the range of 1.2 to 1.7 V. When the leakage threshold is exceeded, the film starts to break down, and the cell resistance quickly decreases as the applied voltage increases. AC voltages and higher DC voltages see a polarization cell as a "dead short." Current passing through a polarization cell consumes water and potassium hydroxide. It also gradually absorbs carbon dioxide from the atmosphere. Polarization cells, therefore, require periodic maintenance to check fluid levels and maintain proper concentration. Electrolyte should be changed periodically to insure proper operation, as follows: Every four years, if experience shows that quarterly or annual checks are required Every year, if monthly checks are required. In addition, the strong caustic solution in the cell may be spilled by lightning strikes or fault currents, and these must now be reported as chemical spills. Solid-state DC blocking. Recently, new solid-state devices have become available, which have a number of distinct advantages over polarization cells.5 For example, there are the advantages of eliminating maintenance, and the potential chemical spills associated with polarization cells. Moreover, the use of solid-state devices gives a much wider operating range, especially to the DC blocking voltage. While polarization cells have a DC blocking voltage of 1.2 to 1.7 V, the solid state device can have the blocking voltage independently set to any level. A 10 V blocking level is usually selected to prevent the loss of DC current from the cathodically protected structure, and to prevent stray DC current from accessing the cathodically protected structure. For example, rapid transit systems, a common source of stray DC, have voltages greater than the 1.7 V blocked by polarization cells. The capability of solid-state devices ranges from 3.7 to 15 KA, giving them greater fault current capacity than the 5 KA polarization cells that they replace. A 3.7 KA device is limited to use in areas of limited AC fault current capability. The current rating is for 30 cycles duration, while most fault currents are limited to 6 to 10 cycles. The DC blocking voltage rating is based on field measurements of the optimal DC current leakage for the system. From the performance characteristics of the solid-state device, this sets the maximum allowable DC blocking voltage that can be put on the system. For the pipelines dealt with in the case history herein, the DC leakage current was selected to be 0.1mA, resulting in a blocking voltage of two volts. In comparison to a polarization cell, the leakage current of a polarization cell is about 50 A at 2 V. To reduce the leakage current to 0.1mA across a polarization cell would require a maximum voltage of only 0.15 V across the cell. Corrosion. Safety considerations have drawn most of the attention to date with HVAC, but some serious problems also may exist with corrosion caused by AC grounding. Corrosion caused by alternating current is certainly less than that experienced by DC. However, various results have been experienced in the field, and the subject has been quite controversial. Since the metal surface at the point of current discharge alternates between oxidizing and reducing conditions with each voltage cycle, the corrosion rate decreases in severity as the frequency increases. Copper suffers much less damage than steel.6 Damage caused on active-passive metals, such as stainless steel and aluminum, is greater than damage on non-passive metals, such as steel, copper or zinc. The alternating reduction and oxidation of the surface layers caused by the AC may cause passive layers to become porous and layered. Studies conducted at the University of Illinois for the American Gas Association revealed that low frequency (60Hz) AC accelerated the corrosion of steel under all soil conditions. The highest net corrosion rate was approximately 2 mils per year for a current density of 500 mA/in2 in neutral soil.1 Although this current density appears to be high for a well-coated pipeline, they could occur at small defects in the coating. Further, the presence of AC in an electrical circuit consisting of different metals, normally steel and magnesium, increases the corrosion rate substantially over the normal anode material consumption rate. Severe metal loss can be experienced to both metals if the alternating current discharge is increased to approximately 25 mA/in2. It is normally found that to offset the effects of the alternating current on cathodically protected pipe, an increase in cathodic protection current will be required to maintain the same protection level. Consequently, the life of sacrificial anode beds will be reduced and the current output of impressed current systems is increased. Corrosion caused by AC discharge has a different appearance than other types of corrosion in soils, such as is produced from galvanic cells or microbiologically influenced corrosion (MIC). AC corrosion has a dendritic appearance, with small "mountains" in the centers of the pits. In one case, corrosion resulted from AC discharge on a 4180 V 3 no-ground motor on a downhole electric submersible pump (ESP) motor, with a known phase imbalance of about 10% at the surface, and a three-parallel wire flat cable to a depth of about 4,000 ft. This motor casing was located in a well stream of about 20,000 bbls fluid per day, 65% of which was salt water, and inside casing. Similar results have been reported on other large (500 hp and up) motor casings on ESPs.8 The same effect has been found on a large-diameter gas line located near a 345 kV transmission system. The pipeline supplied fuel to a power plant, and was located parallel to a set of electric transmission lines for 10 mi coming into the generating plant. Pits were found at a defect in the coating located closest to the tower where the pipeline left the transmission right-of-way to enter the plant. The pits were shiny, and found to have dendritic formations similar to the appearance of the aforementioned motor casing.8 The discharge rate of a pipeline depends on the pipe-to-soil voltage. Above a few hundred Volts, a glow discharge occurs at defects and pores in the coating. If induced AC is not grounded, two potentially serious corrosion problems from AC discharge can occur on a pipeline: 1. AC grounding can interfere with the application of cathodic protection. 2. Amount of corrosion caused by AC discharge to ground does not cause as much corrosion as DC discharge, but it does cause some. The amount is somewhere in the range of about 0.1% to 1% as much, and depends on the capacitance of the metal surface at the point of discharge. AC discharge to ground can, in the long term, cause serious metal loss on the pipe wall and leaks. Analysis of AC problems. As discussed above, induced AC voltages can represent safety and integrity risks on buried pipelines. Fortunately, research on this topic has advanced present understanding of this phenomenon (Table 2). Recently, a PC-based program to calculate AC inductance on pipelines was produced from a research project by PRC International Fig. 3. Analysis of HVAC on a theoretical pipeline using the PRC software. Table 2. Important aspects regarding the causes and mitigation of induced AC on pipelines in utility corridors. 1. Induction • Coating resistance • Coating quality • Depth of cover • Soil resistivity • Phase imbalance • Offset (distance) from power lines • Length of parallelism 2. Steady state • During construction (new pipelines) • Buried and in service 3. Transient state • Lightning strike • Fault current 4. “Touch” potential 5. “Step” potential 6. Mitigation (via low resistance path to ground) • Zinc cells and ribbon • Polarization cells • Solid-state devices Further research and testing will be needed to better determine exactly how AC voltage affects cathodically-protected structures. However, results from a safety standpoint are far better understood. Operating personnel can be exposed to electrical shock whenever the induced AC exceeds either the "touch" potential, meaning the potential difference that exists between hand and foot; or the "step" potential, meaning the potential difference that exists between both feet while walking. The calculation of induced AC voltage (the parameters of which can be seen in Fig. 4) on buried pipelines is dependent on a number of variables, namely: Fig. 4. Significant parameters in analysis of HVAC interference on pipelines Pipe diameter Soil resistivity Coating resistivity, dielectric strength and quality Depth of cover Phase configuration of overhead transmission system Offset between center of pipe and centerline of electric transmission system AC coupling coefficient Electric transmission system phase imbalance Length of parallelism. Using the PC-based software discussed above, it is possible to rapidly predict the levels of induced AC, based upon knowledge of numerous variables. Once the voltage levels are approximated, it is possible to devise mitigation measures to reduce the AC potentials to acceptable levels. From an operational and safety standpoint, there are three major concerns that need to be addressed individually: Induction during construction and pipe stringing Steady-state condition that exists once the pipeline is constructed and commissioned Transient state that exists in the case of a phase fault or lightning strike. The results of the transient state calculations are extremely important when sizing mitigation equipment. Although the loads that occur during fault conditions only exist for a short duration, it is precisely this type of "spike" that causes damage to most electrical equipment. By designing the system to handle the fault load currents, one is certain the system will remain operational and safe, even after a lightning strike or phase fault. A typical example of results calculated using the PRC software is seen below for a theoretical test case. One point worthy of note is the magnitude of difference between the steady and transient states. Case history. Paragon Engineering Services designed the corrosion protection system for two pipelines installed in a utility corridor, parallel with 345 kV electric transmission lines. The electric lines crossed under several other HVAC transmission lines that intersected the pipeline route. One end of the pipeline was located near a power plant, and the electric transmission lines were highly loaded. Field measurements were made to determine the level of induced AC expected to be found on the lines. The pipeline system was mathematically modeled to predict the induced AC behavior expected in the two parallel pipelines as they approached the power line ROW, paralleled the power lines, and finally left the power line corridor. The analysis provided specifications for location of the solid-state AC grounding — DC blocking solid-state devices. The specifications allowed reductions in the induced AC voltages on the line and allowed keeping contact voltages well below the 15 V level recommended in NACE standard. The calculations required installing three devices on one pipeline, and four on the other, due to different routes taken by the two pipelines. The co-operation of the power company was solicited as part of implementing the AC mitigation system. The company was informed of the proposed AC mitigation program, and permission was requested to directly connect the mitigation equipment to the grounding systems of the power company’s transmission towers. Permission was granted, and the grounding system brought into conformance with the specifications of the power company as far as equipment requirements. This was the first time that the power company had given permission for the installation of these devices to be directly connected to their facilities. After installing the pipeline, the corrosion personnel from the pipeline operating company made a number of field measurements of the effect on the pipeline by induced AC, before the grounding system was connected. The findings were consistent with the results of the mathematical modeling, confirming the basic accuracy of the model used. Some of the more interesting results included: Cathodic protection rectifier. The CP rectifier for the two lines was connected to a deepwell anode groundbed, drilled vertically between the two pipelines (due to rightof-way restrictions), and connected to the two parallel pipelines using resistive bonds to balance current flow between both pipelines. Before the transformer-rectifier was connected to AC line power, the gauge readings showed 5.6 V and 2 A on the primary side of the transformer. AC voltages. At the location of one of the grounding devices, the AC voltage on the large-diameter line was 6 V AC, and 4 V AC on the smaller diameter line. After connection of the grounding device, the potential on both lines was reduced to 1.6 V. AC voltages on small line. On the end of the small diameter line, where the pipeline left the utility corridor, 15 V AC was measured at a CP test station prior to connecting the grounding device. Just upstream of this location, still in the utility corridor, 24 V AC was measured at a valve station. After connection of the grounding system, the potentials were reduced to 2 V. Conclusions. Induced AC voltage is clearly identified as a potential hazard, from both safety and corrosion standpoints, for all buried pipelines sharing common rights-of-way with overhead electric transmission systems. Fortunately, it is possible to simulate the conditions that is expected to exist on these pipelines, and calculate anticipated levels of induced AC voltage and current. Armed with this information, it is possible to design mitigation systems that will increase the overall pipeline integrity, and make the pipeline and appurtenances safe for operating personnel. LITERATURE CITED 1. Peabody, A. W., and A. L. Verhiel, "The Effects of High Voltage Alternating Current (HVAC) Transmission Lines on Buried Pipe Lines," Paper No. PCI-70-32, Presented at the Petroleum and Chemical Industry Conference, Tulsa, Oklahoma, Sept. 15, 1970; Kirkpatrick, E. L. "Induced AC Voltages on Pipe Lines May Present a Serious Hazard," Pipe line and Gas Journal, October, 1997; Dabkowski, J., "A Statistical Approach to Designing Mitigation for Induced AC Voltages on Pipelines," Materials Performance, August, 1996. 2. "Lightning Phenomena," Electrical Transmission and Distribution Reference Book, 4th Ed., Westinghouse Electric Corp., East Pittsburgh, PA, 1964; Lichtenstein, Joram, "AC and Lightning Hazards on Pipe Lines," Materials Performance, December, 1992. 3. Gleekman, L. W., Materials Performance, Vol. 12, No. 8, August, 1973. 4. Kirk Engineering Company, Inc., "The Kirk Cell." (Manufacturer’s technical literature.) 5. "The Polarization Cell Replacement — PCR," Dairyland Electrical Industries Bulletin, No. 1100 (manufacturer’s technical literature); Von Baeckmann, W., et. al., Handbook of Cathodic Corrosion Control, Gulf Publishing Company, Houston, Texas, 1997. 6. Metals Handbook, Ninth Ed., Vol. 13: Corrosion, ASM International Metals Park, p. 87, Ohio, 1987. 7. Hoestenbach, Roger Doyle, "Large Volume / High Horsepower Submersible Pumping Problems in Water Source Wells," SPE, No. 10252, AIME, 1980. 8. Van Oostendorp, D.L., unpublished field results, 1992.