Manuscript title : ANALYSIS AND POSSIBILITY OF SOLAR CHIMNEY POWER PLANT IMPLEMENTATION ON THE DALMATIAN COAST Author’s: Dipl.ing. Sandro Nizetic, research assistant ( CORRESPONDING AUTHOR ) Address: Faculty of Electrical Engineering, Mechanical Engineering and Naval Architecture, University of Split, R. Boskovica b.b., 21000 Split, CROATIA mail : snizetic@fesb.hr phone : 0038521305881 mobil phone : 00385915696607 Fax : 0038521305893 Ph.D. Neven Ninic, full professor Address: Faculty of Electrical Engineering, Mechanical Engineering and Naval Architecture, University of Split, R. Boskovica b.b., 21000 Split, CROATIA mail : nninic@fesb.hr phone : 0038521305879 Fax : 0038521305893 1 Abstract: This paper analyses the possibility of solar chimney power plant application – as an environmentally acceptable energy source – in small settlements on the Dalmatian mainland and islands. The analysis was carried out in two characteristic locations in central and southern Dalmatia (Split and Dubrovnik). These areas also have the highest solar irradiation in Croatia. The solar characteristics of the Dalmatian coastal region are shown together with characteristic meteorological data. The existence of a SC power plant, its chimney height being 550 m and its collector roof having 1,250 m in diameter would achieve the mean power of 3.5 MW. The annual SC power plant average electric power production would range between 7.0 GWh/annum and 9.0 GWh/annum. An approximate analysis of costs was done together with the estimate of the total investment. The levelized electricity cost was calculated. Keywords: Solar chimney, Dalmatia region, Electric output, Levelized electricity cost 2 1. Introduction: Solar energy is an inexhaustible and, at the same time, environmentally the most acceptable renewable source of energy. The average annual fall of solar energy as one square metre of earth would be the equivalent to the burning of 100 litres of heating oil – but without any of the damaging emissions. Such energy is free of charge and need not be imported, and most importantly – it does not pollute the environment. Nowadays solar energy, unfortunately, occupies a smaller portion of the total energy generation and its utilisation is still insufficient. Due to the ever decreasing amount of conventional (fossil) fuels, solar energy, being renewable, has become exceedingly important and commercially more affordable. As a proof of this is the European strategic decision on the application of clean technologies – which was confirmed by signing the Kyoto Protocol. In the near future, Europe plans to abandon the fossil technologies and provide for at least half of its energy needs by the application of renewable energy sources. The Mediterranean countries, Croatia being among them, have to foresee the greatest possible portion of renewable energy sources as a basis for their energetic future. Organized and efficient use of solar energy can only see significant growth by the implementation of new clean technologies. One such relatively new technology is the solar chimney power plant (SC), discussed in this paper as a possible electric power source. The basic SC plant concept was designed by Schlaich [1], together with his partners. Basically, the SC plant serves for turning the solar energy into work, i.e. the electric power. The plant main parts are collector roof, solar chimney, and machinery space with turbines and generators for electric power production. Source of power is working potential of heated air defined according to [2]. Working potential is concentrated at the bottom of the solar 3 chimney as pressure difference. The difference in pressures relates to the surrounding atmospheric and the internal heated air at the chimney inlet. The plant chimney intensifies the buoyancy effect which causes the created difference in pressure to start the turbines, which generate the electric power. Croatia is a tourism oriented country with countless natural beauty spots and one of few countries spared from mass tourism. Croatia annually earns an average of 5.0 billion euros from tourism, which is also the main revenue and the basis of commerce. Last year, Croatia was chosen as the most desirable holiday destination in Europe. Each year, an ever increasing growth in visits and greater interest from the leading EU countries is noted. The energy needs have increased, so it is extremely important to provide stable energy sources. Croatian strategic aims are the environment and natural beauty preservation, as well as energetic stability. In this regard, the application of renewable energy sources imposes itself as the right choice, considering Croatia has favourable climatic and meteorological characteristics, i.e. it has significant solar and wind potential. 2. Theory review of solar chimney power plant On the figure (1) are three basic parts of the SC plant: collector roof, solar chimney, and turbines with machinery space, which includes the electric power generators. The physical principle on which the plant operation is based is simple and fundamental. The relatively colder surrounding air enters along the circumference of the collector roof in the space below the collector roof. The solar radiation passes through the collector roof (glass or special foil) and heats the ground under it. 4 Figure (1) Schematic overview of solar tower principle The air is heated in the collector from the ambient temperature T0 to the air temperature at the collector outlet Tcoll, which is up to 50 °C at the most, (temperature growth ∆T=Tcoll-T0, is usually between 10 and 30 K). The pressure difference pac (occuring due to different air densities) at the chimney bottom, where the greatest working potential is concentrated (worked out in detail in [2]), is defined according to the expression (1), [3]: pac g Hc at c dz c gH c 0 5 T T0 (1) The total working potential presents the buoyancy force available work, gained by raising the air from the bottom (z=0) to the total chimney height (z=Hc), where most of the available work is consumed by the turbine and electric power production. The role of the plant chimney is to convert the thermal flow brought into the collector Q by the sun, into the turbine work and kinetic energy (buoyancy effect). The rewritten expression for the chimney efficiency is defined according to the expression (2), [1]: sc gH c C pT0 (2) The solar tower plant efficiency is low, just a few percentages, however, solar energy is free, and so the whole investment after all makes sense. In so far the SC plants are analogue with hydroelectric power plants. The total plant efficiency is equal to the product of partial efficiency of each plant component, i.e.: sp sc collt (3) According to the expression (2) it can be clearly concluded that the chimney height Hc has the greatest influence on its efficiency – the higher the chimney, its efficiency increases. Unfortunately, due to techno-economic reasons the chimney height is limited to approximately 1000 m. The chimney is the component of greatest influence on the total low efficiency – which is shown in figure (2), based on the data from [1]. It should be pointed out 6 that the actual thermodynamic efficiency of the chimney is after all considerably greater. Namely the (little) work produced by the chimney, which is proportional to the numerator in (2) is a more quality form of energy than the (great) heat taken by the collector (proportional to the denominator in (2)). The influence of height to the chimney efficiency is shown in figure (3a), and the influence of the ambient temperature in figure (3b). The ambient temperature influence on Efficiency (%) the produced electric power is little, which has been studied in detail in [4]. 90 80 70 60 50 40 30 20 10 0 turbine collector chimney 0 overall 10 20 30 40 50 60 70 80 90 100 Pow er of plant (MW) Figure (2) Influence of SC components on overall efficiency ( sp ) Chimney efficiency,(%) 3,5 3,0 2,5 2,0 1,5 1,0 0,5 0,0 100 300 500 700 Chim ney height Hc, (m ) (3a) 7 900 Chimney efficiency (%) 3,00 2,50 2,00 1,50 1,00 270 280 290 300 Ambient temperature, T0 (K) (3b) Figure (3) Influence on solar chimney efficiency: (3a) influence of solar chimney height, Hc (T0=293K), (3b) influence of ambient temperature T0 (Hc=550 m) It is interesting to observe that the efficiency of the chimney itself as a thermal engine, according to (2) does not depend on the air temperature increase ΔT. According to the efficiency definition, its numerator contains the buoyancy force work up to the chimney top, while the denominator contains the received heat. The reason for independence from temperature difference is the proportionality of work and heat of the same temperature growth ΔT ( gH c T C p T ). T0 The collector, as an important part of the plant has the task of transforming the overall available sun irradiance G (W/m2), on the collector area Acoll (m2) into useful thermal (W). By definition, the collector efficiency is as follows: flow Q coll Q AcollG m C p T AcollG 8 c vc Ac C p T AcollG (4) According to [5], and the data from [1] the collector efficiency for a single glass roof, ΔT and G being given, can be calculated as follows: T T coll G, T 13.116 6.3364 0.72 2G 2G 2 coll (5) A traditional SC power plant uses axial turbines, where, according to their features, they can be categorised between wind turbines and gas turbines. The turbine assembly main task is the efficient power transformation of the part of the available working potential. The main turbine loss in the SC power plant is the exit kinetic energy (besides the internal fluid friction loss) where the appropriate turbine efficiency t is defined as follows: 2 t Ptc Plc Ptc v m C p T sc m c m C p T sc 2 1 vc2 / 2 C p T sc (6) The overall turbine assembly efficiency differs with various authors. According to the reference, [1], [6] and [7] turbine efficiency varies from 40 up to even 90 % for the plants of great nominal power. Too high velocities of air flow are not suitable as they unfavourably influence the turbine efficiency. The whole SC power plant working regime is the one in which the greatest produced electric power Pwt . max can be achieved for the given weather conditions. In such a regime only 2/3 of the turbine theoretical power are allowed, as according to [1] for such a working regime the mass flow and specific work product per 1 kg of air is the highest. Then, according to [1] and taking in account blade, transmission and generator loss, included in wt , Pel can be calculated as follows: 9 2 g Pel Pwt . max wt coll H c AcollG wt 3 C pTo (7) It should be mentioned that, by the extension of plant dimensions Hc and Dcr, the exit power increases. For various solar chimney height combinations Hc and collector areas Acoll, the same exit power can be gained. 3. Solar characteristics of Croatia and Dalmatia region Croatia has a Mediterranean and continental climate. Forty-three weather stations have recorded solar irradiation averages over the years, having completely covered the Croatian territory. Most weather stations do not measure the total irradiation or insulation but the sun shining hours. The Croatian coastal area (the Adriatic coast) is divided into the northern, central (central Dalmatia) and southern Adriatic (southern Dalmatia). The total sun irradiation on a horizontal surface in central and southern Dalmatia is registered by 13 weather stations. Table (1) compares the irradiated sun power in various Croatian regions. Location in Croatia Dubrovnik ( south Dalmatia ) Istra (north Adriatic ) Split ( middle Dalmatia ) Slavonija (continental region) Zagreb (continental region ) Annualy average kWh/m2day 4.4 3.4 4.2 3.4 3.2 January-average kWh/m2day Julay-average kWh/m2day 1.8 1.2 1.7 1.0 0.9-1.0 7.0 6.0 6.6 6.0 5.7 Table (1) Annual average solar irradiance for different regions of Croatia (averages for decade), [5] 10 In table (1), we can notice that daily-irradiated sun energy on a horizontal surface, for the Adriatic has values between 1.2 and 1.8 kWh/m2 in January, and between 6.0 and 7.0 kWh/m2 in July. The great advantage of the climate is in winter months. In January, the continental part of Croatia receives a double amount of solar energy than northern Europe. The southern part of Dalmatia receives 3 to 5 times more solar energy than northern Europe, twice more than central Europe. In the continental part of Croatia there is the annual average of approximately 1200 kWh/m2, while in the coastal area it exceeds 1600 kWh/m2. For the optimal surface inclination, the average irradiated amount of sun energy increases for about 20 % in relation to the data given in table (1). It can be concluded that the difference between the irradiated amount of sun energy for central and southern Dalmatia is small. The continental parts of Croatia – e.g. the area of the city of Zagreb – gets up to forty percent less solar energy (annual average) in comparison with Dalmatia. In figure (4) are shown monthly mean air temperatures for central Dalmatia. In January, the daily mean air temperature is 8.8 °C, while in July it is 24.5 °C. In figure (5), the distribution of the irradiated solar energy (W/m2) on horizontal surface is shown. The data record a typical day in the hottest (July) and coldest (January) month for the area of central Dalmatia. The overall irradiated amount of energy is even up to 70 % greater than in most parts of central and particularly northern Europe for the optimally inclined surface. For example, the sunniest parts of the Croatian coast do not fall behind Greece at all. The sunniest parts of Europe receive only slightly more solar energy ranging from 4 to 8%. 11 The solar irradiation values we will be using further on have been chosen for two characteristic locations; Split-central Dalmatia and Dubrovnik-southern Dalmatia. The recorded data regard the following weather stations: SPLIT – Marjan – WMO* (14445) – Latitude 43° 31’; Longitude 16° 26' DUBROVNIK – Gorica – WMO (14472) – Latitude 42° 39’; Longitude 18° 5' The data are according to [8], [9], and [10] and represent 30-year average measurements by the Croatian Weather Bureau, completed by the Croatian Energetic Institute ''Hrvoje Požar''. Average temperature of air, °C 30 25 20 15 10 5 0 1 2 3 4 5 6 7 8 9 10 11 12 Month Figure (4) Monthly average air temperature for Dalmatia region _______ * WMO – World Meteorological Organisation 12 Horizontal solar radiation, W/m 2 800 700 Julay January 600 500 400 300 200 100 0 5-6 6-7 7-8 8-9 9-10 10-11 11-12 12-13 13-14 14-15 15-16 16-17 17-18 18-19 Daily Hours Figure (5) Daily hourly average radiated energy, W/m2, for horizontal surface and central Dalmatia region 4. Annual production of electric energy for Dalmatian region For the calculation of the annual amount of electric power produced by the SC power plant the following technical features have been adopted: SC power plant basic technical features: - collector roof diameter, Dcr = 1250 m - solar chimney height, Hc= 550 m - chimney diameter, dc= 82 m - distance from the ground to the cover, 2,5 m - single glass collector roof 13 - without additional thermal energy storage - chosen temperature difference ΔT from 7 K to 25 K - blade, transmission and generator efficiency : wt 0.8 The plant average annual achieved power Pav.an is calculated from the optimal monthly Pj , according to the following expression: P j Pav.an j j (8) i i It is assumed that the optimally achieved monthly powers are those that give the highest electric power production for the considered month. The conditions for choosing the optimal power are: constant temperature increase in the collector ΔT and maximum produced amount of electric power. In figure (6) such calculation of the maximum electric power production in Split in June for ΔT=15 K ( Popt Pjune 5215 kW ) is shown. 9000,0 Pel.max= 8000 kW Electric pwer output, P el (kW) 8000,0 7000,0 6000,0 Popt=5215 kW 5000,0 4000,0 Popt=5215 kW 3000,0 d= 7.8 h Eel.max=40674 kWh/day 2000,0 1000,0 0,0 5-6 6-7 7-8 8-9 9-10 10-11 11-12 12-13 13-14 14-15 15-16 16-17 17-18 18-19 Hours d= 7.8 h Figure (6) Monthly optimal achieved electric power output Popt (Split, June, ∆T=15K) 14 By this way of monthly calculation, the highest annual electric power output Eel.an is gained for the achieved ∆T. The optimum air temperature increase ∆Topt is the one with which there is maximum annual electric power output Eel.an. Further on in economic analysis this power will be called nominal. The Eel.an calculation results for Split and Dubrovnik are shown in figure (7). Produced electric energy, Eel.an (MWh/y) 9500 9000 8500 8000 7500 7000 Split 6500 Dubrovnik 6000 5 10 Topt 15 20 25 Tem perature difference T (K) Figure (7) Annual produced electric energy for central and south Dalmatia region The highest mean annual electric power output for Split is Eel.max = 9058 MWh/annum for ΔTopt = 11.3 K, while for Dubrovnik it is Eel.max= 9154 MWh/annum for ΔTopt = 11.5 K. Previously stated values for power and electric power are related to the average power defined according to the expression (8). The physical reason for the existence of optimum air temperature increase in the collector ΔTopt is of two kinds. Namely, with very small ΔT values the collector efficiency is extremely high, but the turbine efficiency is very low, and vice versa. The reason for the low turbine efficiency lies in high air flow velocities due to which kinetic energy losses dominate. 15 In the reference [1], the so-called Capacity factor ''f'' is defined. It represents the ratio between the actual annual number of working hours τs for the given conditions and the overall annual number of hours τsan, i.e. f(%) s s 100 san 8760 (9) For the solar tower plant of chosen technical features, a number of working hours was simulated for the given conditions and chosen locations in Dalmatia. Based on this, factor f was defined for given conditions. The data are shown in table (2) depending on the achieved temperature difference ∆T. T(K) SPLIT DUBROVNIK 7 33.9 32.9 10 27.5 27.6 Capacity Factor f (%) 15 20 25.6 24.4 25.4 24.2 25 24.0 23.2 Table (2) Simulation of capacity factor By the analysis and simulation carried out for the chosen locations in Dalmatia (Split, Dubrovnik) an average of 5.5 to 8 solar tower plant-working hours per day can be expected. It has been established that, for the given meteorological conditions and chosen geographical locations, a SC plant can produce an annual average of electric power between 7.0 and 9.0 GWh, depending on the achieved temperature difference ∆T. Cumulative annual production of electric power simulated monthly, for Split and ∆T=15°C, is shown in figure (8). 16 T = 15 K, Location: Split 10000000 Monthly energy production, kWh/m 9000000 8000000 Annual results : Annual energy production: 8.79 GWh Operating hours: 2338 h Capacity factor: 25.6 % 7000000 6000000 5000000 4000000 3000000 2000000 1000000 0 136 287 473 683 919 1153 1388 1604 1796 1970 2108 2238 Operating hours Figure (8) Simulation example of annual produced electric energy for Dalmatia region 5.0 Economic aspect of produced electric energy The solar tower plant capital investment consists of the chimney, collector roof, and turbine assembly building construction costs. The costs structure in relation to the overall investment is the following: the chimney bears approximately 30 – 50 % of costs, while the collector roof bears about 20 - 40 %. Medium orientation price for the collector roof made of single glass amounts to 6.0-9.0 €/m2, while for the chimney made of reinforced concrete, it amounts to 200-500 €/m2. If the collector roof is produced in special plastic film, an investment about 30 % lower compared to the traditional glass covering, can be expected. The turbine assembly costs are more complex to analyse, therefore their portion jumps up with the decrease of nominated power. For the nominated power of 200 MW, for example, the overall specific turbine expenses amount 210 €/kWel, while for 5 MW, they amount 1000 17 €/kWel. Besides capital costs, it is necessary to mention the testing and commissioning which approximately amount 6 - 10 % of the total investment. The abovementioned costs for solar power plant individual components are for orientation purposes and depend on the plant nominal power and on particularly designed collector roof performance. The stated costs include costs of labour. For the plant of chosen technical features in accordance with chapter (4), based on the reference [8], an estimate of investment costs was done. Overall investment: - collector roof: approx. 9.3 Mio. € - chimney: approx. 34.7 Mio. € - turbines: approx. 6.0 Mio. € - engineering, tests, misc.: 3.5 Mio. € --------------------------------------------------Total invested capital: K0= 53.5 Mio. € Average costs of produced electrical energy are calculated according to [3]. kw K0 Eel .an n fw n 1 r i 1 i rb (10) where factor fw n 1 p p fw 1 p n 1 18 (11) Based on the analyses carried out in chapter (4.0) depending on the chosen temperature difference ∆T, the SC electric power plant annual energy production, Eel.an is as follows: For SPLIT 7.26 - 8.93 GWh/per annum For DUBROVNIK 7.02 - 8.97 GWh/per annum For the calculation of produced electrical energy price, the necessary parameters have been established as follows: - rate of inflation: r = 6.0 % p.a. - maintenance and repair cost: rb = 2.0 % p.a. - calculated interest rate: p = 6.0 % p.a. - period of amortization: n = 20 years Using previously adopted data and the expressions (10) and (11) the price of produced electrical energy (€/kWh) can be calculated. The calculation results for the two characteristic chosen locations, depending on the average annually produced electrical energy are shown further on: SPLIT 0.29 - 0.36 €/kWh DUBROVNIK 0.29 - 0.37 €/kWh Through the analysis carried out we can conclude that the average price of electrical energy kWh produced by a SC electric power plant in Dalmatia, would be 0.33 €/kWh. 19 Levelized electricity cost, €/kWh 0,35 0,3 0,25 0,2 0,15 0,1 20 25 30 35 40 45 50 Amortization years Figure (9) Influence of amortization period on levelized electricity cost Assuming an amortization period of 40 years, the average levelized electricity price would be 0.16 €/kWh. The amortization period influence on the mean price of levelized electricity is shown in figure (9). Analysis and estimate of costs were done based on the data about prices according to [3] and [11]. 6. Conclusions For a SC power plant of chosen technical features, an overall technical analysis was carried out for the purpose of possible application in the electrical energy production for Dalmatia and Dalmatian islands. The following conclusions may be drawn based on the analysis carried out: 20 SC electrical power plant of technical features as in chapter (4.0) would produce an average of 7.0 - 9.0 GWh /per annum in Dalmatia, depending on the achieved air temperature difference ΔT. The plant nominal power would be 3.5 MW, while the ''peak'' would be reached in July, e.g. 8.1 MW for ΔT=20 K. Annually, an average of 5.72 kWhel/m2annum - 7.36 kWhel/m2annum could be expected per m2 of collector surface. The levelized electricity mean price would be 0.33 €/kWh. The present electricity price in Croatia is 0.1 €/kWh. Obviously, a construction of SC electric power plant in Dalmatia is not profitable now. Taking into consideration the time still to come and a broader context of the energy issue overall, here are a few interesting reflections. a) As already mentioned in the introduction to this paper, the main Croatian revenue is tourism, which has been growing, year after year. The consequence of this is the exceeding need for electricity whereby the maximum Croatian need does not come in winter but in summer (the summer maximum for 2005 began in late July and was about 2400 MWh/h, while the winter maximum began in early February and was about 2300 MWh/h). It quite often happens that in summer, due to overloading, the electric energy system collapses, which is particularly the case on Dalmatian islands during the holiday season. b) When Croatia joins the EU we expect a rise of electric energy price of up to 20% compared to the present market price. For example, the electric energy price in Germany is 0.15 €/kWh. c) State subsidies for stimulation and popularisation of renewable energy sources would lower the levelized electricity price. 21 d) Croatian strategic orientation is preservation of the environment and natural beauties. This strategic objective can actually be realised by the application of renewable energy sources in as much as possible. e) In future, the amounts of fossil fuel will decrease which will finally result in favourable investment conditions for the application of renewable energy sources. f) SC electric power plant’s great advantage is its long life of up to 60 years. Regarding this - in [3] - there is a comparison between the life of a SC electric power plant and a traditional fossil fuel driven power plant. A conclusion has been made that, taking a long-term view, the SC electric power plants are much more favourable. A traditional fossil driven plant has a shorter life, about 20 years on average (it may be longer, but the maintenance costs jump up with the years), high maintenance costs, and variable but nowadays most influential fuel costs. In future, fossil costs will most certainly change their prices in an upward direction only and after shorter and shorter periods, which does not say much for the traditional plants. g) The possibility of SC electric plants application in integrated energy systems, which would additionally lower the levelized electricity price. Based on the presented reflections and carried out analyses, we can conclude that at this moment building solar chimney electric power plants in Dalmatia is profitable over the long term only. If, however, the previously presented facts and conclusions are acknowledged, the building of such electric power plants becomes a serious and likely option. 22 Nomenclature: Ac Cross sectional area of solar chimney, m2 Acoll Solar collector area, m2 Cp Specific heat capacity of air, kJ/kg°C Dcr Diameter of collector roof, m dc Diameter of chimney, m dz Differential element of chimney height, m Eel.an Annual produced electric energy, MWh/y Eel.max Maximum annual produced electric energy, MWh/y f Capacity factor g Acceleration of gravity, m/s2 G Solar irradiance, W/m2 Hc Solar chimney height, m i Years kw Levelized electricity cost, €/kWh K0 Total invested capital, Mio. € m Mass flow rate of air, kg/s n Amortization period, years p Calculated interest rate, % p.a. Pav.an Average annual electric output from the solar chimney, kW Popt Optimal average electric output from the solar chimney, kW Pel Electric output from the solar chimney, kW Pel.max Maximum electric output, kW 23 Pj Average monthly electric output, kW Plc Power loss due to exit kinetic energy, kW Ptc Power of theoretical air cycle, kW Pwt.max Maximum mechanical power taken up by the turbine, kW r Rate of inflation, % p.a. rb Maintenance and repair cost, % p.a. Q Heat gain of the air in the collector, kW T0 Ambient temperature, K Tcoll Temperature of air at collector outlet, K vc Inlet air velocity of solar chimney, m/s z Level from the ground, m 24 Greek symbols: coll Solar collector efficiency sc Solar chimney efficiency sp Overall efficiency t Turbine efficiency wt Blade, transmission and generator efficiency at Density of ambient air, kg/m3 c Density of air at inlet in solar chimney, kg/m3 d Daily working hours of solar chimney power plant, h/day j Monthly working hours of solar chimney power plant, h/month s Working hours of solar chimney power plant, h/year i Total working hours of solar chimney plant for optimal electric output, h/year i pac Pressure difference produced between chimney base and the surroundings, Pa T Temperature rise between collector inflow and outflow, °C Topt Optimum temperature rise between collector inflow and outflow, °C 25 References: [1] Sclaich J. The solar chimney: Electricity from the sun. In: Maurer C, editor. Germany: Geislingen; 1995. [2] Ninić N. Available energy of the air in solar chimneys and the possibility of its ground level concentration. Solar Energy 2006 (Article in press). [3] Sclaich J, Bergermann R, Schiel W, Weinrebe G. Desing of commercial solar updraft systems-Utilization of solar induced convective flows for power generation. Germany: Stuttgart; 2004. (unreleased text) [4] Y.J.Dai, H.B. Huang, R.z. Wang N. Case study of solar chimney power plants in North-western regions of China. Renewable Energy 2003; 28: 1295-1304 [5] Group of authors. SUNEN, Croatian Energetic Institute ''Hrvoje Požar''; 1997 [6] Backstrom T.W., Ganon A.J. Solar chimney turbine characteristics. Solar Energy 2004; 76: 235-241 [7] Haff W. Part II: Preliminary test results from the Manzanares pilot plant. International Journal of Solar Energy 1983; 2:141-161 26 [8] Z. Matić, ''Solar radiation in Republic of Croatia'', Croatian Energetic Institute ''Hrvoje Požar''.Croatia: Zagreb; 2005. [9] Climate and solar characteristic of Croatia. Meteorological and Hydrological service of Croatia [10] Actual real-time measured data, Meteo-ocean station ''Punta Jurana'', Institute of Oceanography and Fishers, Split, Croatia [11] Haff W, Friedrich K, Mayr G, Sclaich J. Solar chimneys: Part I: Principle and construction of the pilot plant in Manzanares. International Journal of Solar Energy 1983; 2(1):3-20 27 Figure Captions: Figure (1) Schematic overview of solar tower principle Figure (2) Influence of SC components on overall efficiency ( sp ) Figure (3) Influence on solar chimney efficiency: (3a) influence of solar chimney height, Hc (T0=293K), (3b) influence of ambient temperature T0 (Hc=550 m) Figure (4) Monthly average air temperature for Dalmatia region Figure (5) Daily hourly average radiated energy, W/m2 horizontal surface and central Dalmatia region Figure (6) Monthly optimal achieved electric power output Popt (Split, June, ∆T=15K) Figure (7) Annual produced electric energy for central and south Dalmatia region Figure (8) Simulation example of annual produced electric energy for Dalmatia region Figure (9) Influence of amortization period on levelized electricity cost 28 Tables: Location in Croatia Dubrovnik ( south Dalmatia ) Istra (north Adriatic ) Split ( middle Dalmatia ) Slavonija (continental region) Zagreb (continental region ) Annualy average kWh/m2day 4.4 3.4 4.2 3.4 3.2 January-average kWh/m2day Julay-average kWh/m2day 1.8 1.2 1.7 1.0 0.9-1.0 7.0 6.0 6.6 6.0 5.7 Table (1) Annual average solar irradiance for different regions of Croatia (averages for decade), [5] 29 T(K) SPLIT DUBROVNIK 7 33.9 32.9 10 27.5 27.6 Capacity Factor f (%) 15 20 25.6 24.4 25.4 24.2 Table (2) Simulation of capacity factor 30 25 24.0 23.2