NEA33 POWER CONVERSION BATTERY CHARGER CLASS Class Chargers MCC’s Battery PKA-H11 400A PKA-M41 PKA-F11 PKC-H13 300A PKC-M43 PKC-F13 PKA-H15 400A PKA-M41 PKC-M43 PKA-F11 PKC-F13 PKB-H12 400A PKB-M42 PKB-F12 PKD-H14 300A PKD-M44 PKD-F14 PKB-H16 400A PKB-M42 PKD-M44 PKB-F12 PKD-F14 See print 01-E-PKA-0001 8 PKA-F11 has four spare cells that are maintained on charge with the spare Battery Charger PKN-H01. “Bitrode” 50 amp, 18 volt (Target Range 8.68 - 9.00 Vdc) Each backup charger has two output breakers to enable them to supply DC power to either bus (A or C and B or D) it serves. A mechanical interlock is provided between the breakers which prevents possible closing of both of the breakers simultaneously. How long can the Class 1E Batteries supply power continuously to class loads ? • The Batteries will provide 2 hours of 125 VDC power continuously to all class IE electrical loads connected to the system. • If the inoperable DC electrical power subsystem cannot be restored to OPERABLE status within the required Completion Time, the unit must be brought to at least MODE 3 within 6 hours and to MODE 5 within 36 hours • During modes 1 through 4, both DC trains consisting of all four control centers consisting of all four batteries and four battery chargers, are operable and energized to meet the Tech Spec requirements. • During modes 5 and 6, at least one train consisting of two control centers, including batteries and battery chargers, is operable and energized to meet the Tech Spec requirements. Design Basis for Class 1E Chargers: • Restore the batteries to their fully charged state condition within 12 hours regardless of plant condition, starting from a minimum battery design charge of 105 VDC. Some of the DC loads for PK: • DC power to the PN Inverters (Vital AC) • DC power to the PK Inverters (Shutdown Isolation Valves) • Reactor Trip Switchgear Control Power • Diesel Generator Control And Starting Circuit • Aux Feedwater Turbine Governor Control Panel • DC Control Power for PB and PG • Auxiliary Feedwater Pump A Turbine Trip And Throttle Valve • Aux Relay Panels • Other critical DC valves 125V DC non class IE power system (NK) The non class IE 125V DC power system consists of three independent non class IE 125V DC subsystems. Each subsystem (E, F, G) has a battery, 125V DC control center and/or 125V DC distribution panels and a battery charger supplied with 3 phase 480V AC power from a different MCC. Supplies 125V DC power to in-plant DC loads through MCC’s NKN-M45 and NKN-M46 and “D” panel NKN-D19. NON-CLASS BATTERY CHARGERS NKN-H17 (E) Battery Charger Norm. Feed NKN-M45 500 amp NKN-H18 (F) Battery Charger Norm. Feed NKN-M46 250 amp NKN-H19 (G) Battery Charger Supply to 50 amp NKN-D19 NKN-H20 (E1) Battery Charger Alt. Feed 500 amp NKN-M45 NKN-H21 (EF) Battery Charger Alternate to M45/M46 500 amp SEE PRINT 01-E-NKA-0001 Normal lineup is the “F” Battery Charger NKN-H18 feeds NKN-M46 and the “E” Battery Charger NKN-H17 feeds NKN-M45. NKN-H18 is a 250 amp charger, smallest charger with the largest Battery (3650 AH) Each non class IE battery has sufficient capacity to independently supply the required loads for 4 hours following the loss of battery charger. NKN-F17 NKN-F18 The backup charger (“EF”) has two output breakers to enable them to supply DC power to either bus (M45 or M46) it serves. A mechanical interlock is provided between the breakers which prevents possible closing of both of the breakers simultaneously. Easy way to remember what 480 volt MCC feeds the swing charger. NHNM21 feeds NKNH21. 14 Some of the DC Loads for NK: Main Turbine Emergency Lube oil Pumps (EBOP) Main Turbine Seal Oil Pumps (SO) Control Power for NA, NB, MA, Switchgear and Transformers. (Includes protection relays). Control power for NG DC Power to the Plant computer (NQ) Control Power to Diesel Generator Trip circuit for Main Turbine Control Power to Aux. Relay panels Feedwater Trip and Reset control circuit (FW) 15 EO02 – Identify the Battery Charger Power Circuit Components. 16 Power Circuit 17 The AC input Circuit Breaker CB1 Main transformer (T1) Back View Front View T1A T1C T1B Fuses for the main SCR's (F1-F6) Each of the six power SCR’s are fused to protect it from a high overload. SCR’s Free Wheeling Diode CR7 CR6 CR4 CR5 CR3 Blocking Diode CR8 CR2 CR1 (MOV’s) Metal Oxide Varistor's (D1-D7): Protect SCR’s (CR1 – CR6) and Freewheeling diode (CR7 Dc filter (L1, C1, and R1) R1 C1 L1 RS1 Shunt to Local Ammeter And A2 & A3 boards RS2 Shunt to Remote Ammeter And alarm module The DC output circuit breaker (CB2): Used as a switch only Back-up chargers have two output breakers (CB2A and CB2B) CB1 CB2 EO03 Explain the function of the components in the battery charger’s power circuit. Power is fed to the input transformer (T1). T1 is a three-phase delta to delta transformer. T1 provides power to the main SCR's and the 120VAC power to the Amplifier Board, and the Firing Module. T1 also supplies power to all of the accessories, such as the power on indicator, the AC failure alarm (K3 relay) the three phase power monitor (K1) and the 0-24 hour timer motor. Review Prints E051-00018 and E051-00033 27 The firing module receives the error signal from the Amplifier Board and determines how long the SCR’s need to fire for voltage correction. A1 Control Circuit -10 vdc Common + 10 vdc 120 volt input from T1 30 A3 34 Control Circuit -10 vdc Common + 10 vdc 120 volt input from T1 35 Non-Class Charger Class Charger CHARGER OPERATING CURVE 2.75 VOLTS PER CELL 2.50 EQUALIZE FLOAT 2.25 2.00 102% 1.75 105% 1.50 0 20 40 60 80 100 % CHARGER CURRENT 120 140 38 NOTE: Polarity across the load Resistor (RL) does not change. NEA07 Slide 28 40 Polyphase alternating current, when rectified, gives a much “smoother” DC waveform (less ripple voltage) than rectified single-phase AC. Alarm Module “59” “27C” “37” “32” 45 46 48 Alarm Module The battery charger’s alarm module contains four (4) alarm circuits on printed circuit boards that are connected to a mother board. The DC Relay on each Alarm board actuates the (K-2) Summation Alarm. All of the cards have an LED that indicates as follows: ALARM CARD Reverse Current Charger Failure Low Voltage High Voltage NORMAL LED off LED on LED on LED off ALARM LED on LED off LED off LED on Note: the LED on the Charger Failure Alarm Board will be in alarm condition until the Battery Charger senses a load on the bus. 50 ALARM MODULE RELAY CONTACT SCHEMATIC RCA in alarm, Shunt polarity changed. RCA in Alarm Condition, LED on, Q1 & K1 is picked up. CFA in Non Alarm Condition, LED On, Q1 & K1 is Picked up. Testing SCR’s Lift the white gate lead and red cathode lead on each SCR and take a resistance reading between the two. Reading should be less than 50 ohms. Larger Power SCR’s have a resistor between The Gate and Cathode Used to prevent false triggering SCR’s Cont.. Using a lamp tester, attach the Positive (+) to the anode and the negative to the Cathode. Gate the SCR on by touching the positive to the white gate lead. The lamp should be brightly illuminated. Remove the signal and verify that the SCR stays on. Apply a second gate pulse and verify the SCR stays on. Test SCR’s on the Lab Charger Replacing SCR’s New SCR’s are tested prior to installation SCR leads may have to be extended; splicing instructions are in work package. Observe proper polarity when installing. Apply a thin film of heat sink compound on the conducting surface on the new SCR. Ensure alignment pin in charger is aligned with the indent in the SCR. Perform Torque/Clamping for specific SCR to be replaced. Ensure alignment pin in charger is aligned with the indent in the SCR. SCR’s have been found damaged due to misalignment during clamping. EO09 Given a Fault condition, troubleshoot/rework the Battery Charger and discuss safe work boundaries and electrical safe work practices necessary to perform the task. Human Performance Tools when working on the Battery Charger Follow procedures and work instructions Stop when unsure or in the face uncertainty Use operating experience to prevent errors Perform a good pre-job brief Perform a 2-min drill Use self-check and peer-check Three-Way communication Provide good turnovers Perform a post job brief On Non-Class Chargers, ensure the force paralleling wire is lifted prior to working on the charger. Troubleshooting Techniques: Battery Charger symptoms A symptom is a sign or indicator of some malfunction of the equipmen Use your senses of hearing, sight and smell Perform a visual inspection Check alarm condition Check voltage/current output of Battery Charger Document findings Localizing the Faulty Function: Think Block Diagram when troubleshooting Is it a Control or Power problem? Power Circuit: Power Fuses SCR’s/Diodes Tripped AC Breaker Filter network ,Capacitors, R1 resistors and inductor L1 Transformer Control Circuit: Float/Equalize voltage network Sensing & Current Limit board Amplifier Board Firing Modules Control Fuses Alarm Circuit What drops out the K2? Some of the tools used for troubleshooting: Fluke DVOM Fluke Scope or Astro-Med Amp Probe SCR test light Mini grabber test leads Flashlight Small pin point test leads Load Bank if required 64 During troubleshooting use the provided table to compare voltage readings taken at various points on the Sensing and Current Limit Board and the Amplifier Board. AMPLIFIER BOARD VTD P319-002 TERMINAL BOARD POINT APPROXIMATE DC VOLTAGE AS FOUND DC VOLTAGE REMARKS 6, 7, 8 Common Common Common 10 1.7 to 2.9 Vdc 9 10.25 Vdc 5 4.0 to 4.3 Vdc 11 13 14 12 -10 Vdc -2.91 Vdc + 30mv to -10mv 2-4 Vdc Varies With output voltage Effects output voltage Varies With Float or Equalize Voltage Adjust (R3,R6) Effects Current Limit Varies With Current Limit Setting (R9) Varies Directly With Output Current Varies With Output Current and Input Voltage (Line) SENSING AND CURENT LIMIT BOARD PIN NUMBER APPROXIMATE DC VOLTAGE AS FOUND DC VOLTAGE REMARKS 4 -2.91 Vdc 5 COMMON Across CR9 5.3 Vdc Any deviation indicates a faulty sensing module. Across CR11 5.3 Vdc Any deviation indicates a faulty sensing module. Across R5 14.1 Vdc Any deviation indicates a faulty sensing module. Current Reference Depending on R9 Settings COMMON COMMON 8 10.25 Vdc Develops Voltage Reference 7 1.7 to 2.9 Vdc Voltage Variable 2 + 30mv to - 10mv 3 10 12 - 10 Vdc Current Variable Develops Current Reference 4.0 to 4.3 Vdc Voltage Reference 4.7 Output voltage to Cabinet mounted Components Voltage Problem Example: No DC output Check pin 12 (output to the firing modules), should be between 2-4 Vdc Check A2 Amp board for power supply voltages, +10.25 and – 10 vdc Check voltage reference at pin 5 to common, should be approx. 4.3 Vdc Check common on the Float/Equalize Switch, reading should be approx. 4.3 Vdc. Check pin 12 on the S&C Limit board Check R8 on the S&C Limit board Check control fuses Ask the class if they can think of any thing else Regulation Problem Example: Charger noisy when loaded SCR’s may not be firing properly Check gate signals to SCR’s on each module Check AC input to each firing module Check soldering connections Check current through main fuses Alarm Problem: Example: Summation Alarm in the Control Room K2 relay should be dropped out Verify alarm condition of alarm cards Check 3 phase power monitor Check control fuses Check K4 relay During outages it is not uncommon for one of the DC buses not to have a load. The CFA alarm will come in if current is less than 5 Amps. CRDR 3233151 found incorrect fuses installed in 1ENKNF17, fuses F11, F12, F13 and F14 size 1/8 Amp fuses instead of 1 Amp. Current Limit Problem: Check verify R9 setting (S & C Limit board) Check verify Current variable during operation P3 may have to be adjusted on the Amp board Check current reference (- 2.9 Vdc or lower) Check verify output on pin 12 to firing modules (2-4 Vdc) SME – It helps to monitor current reference at point 13 on the amp board while adjusting R9. This helps the tech determine direction of adjustment. The lower the setting, the lower the current limit. 71