ABB PPMV Lake Mary, Florida Advance 27® 27kV Metal-Clad Switchgear Customer Training © ABB Group April 8, 2015 | Slide 1 Advance 27® Metal-Clad Switchgear 27kV Metal-clad Air Insulated Switchgear Tested to IEEE C37.20.2-1999 UL Certified Quoted and built in Lake Mary, FL Seismic Certified to IBC Region D Ratings: Rated Voltage Rated Continous Current 27kV 1200, 2000A Rated Symmetrical Current 25kA Rated Short-time 2 sec Rated Peak Current 65kA Close & Latch capability 65kA Rated Lightining Impulse (BiL)Voltage 125kV Rated Power Frequency Voltage 60kV Advance 27® Layout 36” : Wide 95” : High (W/O Vents) 92” : Deep Options: 10” Front Extension 10” Rear Extension 1200A BRKR. COMPT OR 38” PT COMPT OR FUSE COMPT INSTR. COMP BREAKER COMPT. 1200A 2000A MAIN BUS. COMP VENT CHAMBER CABLE COMP. Advance 27® Features Standard Features Galvanized construction Hem bending Modular design Bolted frame Instrument compartment Breaker compartment PT/Fuse compartment Bus and cable compartment Additional Safety Features Closed door racking Snuffer contact design – PT’s/Fuse Modular Design Breaker Compartments Breaker Compartment Porcelain primary bushings Lexan shutters Position indicator Automatic secondary disconnect Sealed Lexan CT covers with skirt boot Isolated terminal blocks Instrument Compartment Isolated design Available in 19” or 57” PT and Fuse Compartments PT Compartment Up to 3 PTs - all configurations Delrin snuffer contact technology Closed door racking 38” only Fuse Compartment Fuse drawout for fixed mount CPT 25, 37.5 or 50kVA single phase Remote mounted Delrin snuffer contact technology Closed door racking Delrin Snuffer Contacts Utilizes an epoxy primary bushing Encapsulated fixed contact to prohibit access through accidental contact – no shutters required PT Compartment Fuse Compartment Bus and Cable Compartment Copper bus with Epoxy insulation Porcelain standoff insulators (7.5”) Single rear bolted door Molded vinyl boots with re-useable nylon hardware Bus and Cable Compartment - Options Tin plated bus Cable supports Surge arrestors Ground studs Ground sensor CT’s Bus duct entry IR viewports (IRISS or Fluke) on rear door Bus and Joint Covers Bus Sizes 1200A - 3/8” x 4” 2000A - 3/4” x 4” Joint Covers Black Plastisol material Requires an internal skirt on each bus Requires the application of silicon AMVAC Model 4 Drawout Circuit Breaker Ratings: Rated Voltage 27kV Rated Continuous Current 1200, 2000A Rated Interruption 16, 25kA Close and Latch 42, 65kA Interruption Time Rating 83ms (5-cycle) Rated No-load Op. Endurance 15,000 Rated Reclosing Sequence O-0.3s-CO-15s-CO 5 Year Standard Warranty Accessories Racking crank Manual open handle Test cabinet Test jumper Ground & test device SmartRack electric racking device Lift truck Breaker release handle Applications Indoor installations Outdoor installations Outdoor Non-Walk In (ODNWI) enclosure Outdoor Walk-in/Sheltered Aisle (ODWI) enclosure Power Distribution Center (PDC) Questions?