EcoBreeze™ IEC Modular Indirect Evaporative Cooling Solution APC by Schneider Electric – Ken Baer – 07/27/2010 Outline ● Drivers for Economizers ● ASHRAE 90.1 / TC 9.9 ● Availability of Power ● Custom Systems ● EcoBreeze IEC ● ● ● ● ● Overview and Key Features SKUs and Dimensions Components Electrical Information How it works • Inside the Data Center • Outside the Data Center • Module Function ● Performance ● Competitor Comparison ● Power Usage APC by Schneider Electric – Ken Baer – 07/27/2010 Drivers for Economizers ASHRAE 90.1 ● ASHRAE 90.1 standards are always evolving as technology advances ● ASHRAE TC9.9 revisions expanded the envelope for recommended operating conditions in the data center ● This widened envelope allows for more efficiency and energy savings through more hours of economization 2004 Limits Temp Range: 68-77°F Humidity Range: 40-55% APC by Schneider Electric – Ken Baer – 07/27/2010 2008 Limits Temp Range: 64.4-80.6°F Humidity Range: (DP 42°F) – (60% RH & DP 59°F) Economizer Requirements None > 19kW >40kW APC by Schneider Electric – Ken Baer – 07/27/2010 1a, 1b, 2a, 3a, 4a 3b, 3c, 4b, 4c, 5b, 5c, 6b 2b, 5a, 6a, 7, 8 APC by Schneider Electric – Ken Baer – 07/27/2010 Drivers for Economizers Energy Costs and Constraints ● Data centers are constantly expanding which requires more energy ● Local energy companies place heavy restrictions on gaining more power from the grid ● There is a need to reduce cooling power consumption to allow room for value-added IT equipment APC by Schneider Electric – Ken Baer – 07/27/2010 Drivers for Economizers Custom Economizer Systems Complex System ● Complex infrastructure requires special controls, installation, and maintenance ● Multiple vendors involved ● These systems have a higher chance of failure and emergency maintenance EcoBreeze APC by Schneider Electric – Ken Baer – 07/27/2010 Features and Benefits ●Two forms of Economization ● Air-to-Air Heat Exchange ● Indirect Evaporative Cooling ● Proportional DX refrigeration circuit ●Variable Speed Compressor ● Electronically Commutated Fans ● Zero White Space Solution ● Modular Design for “Pay as you Grow” Philosophy ●Chemical-Free Water Treatment ● 50kW Sensible Cooling Per Module (No Dehumid/Humid) ● IEC Heat Exchanger ● No mixing of IT air and outside air APC by Schneider Electric – Ken Baer – 07/27/2010 EcoBreeze - SKUs SKU ACECFR40100 ACECFR40101 ACECFR40200 ACECFR40201 ACECFR20100 ACECFR20101 ACECFR20200 ACECFR201 ACEC100 ACEC101 ACEC200 ACEC201 ACECCP100 ACECRTN10 ACECDIS10 ACECSJ100 Description 40' ISO Frame 208-230/3/60 40' ISO Frame 400/3/50 40' ISO Frame 480/3/60 40' ISO Frame 600/3/60 20' ISO Frame 208-230/3/60 20' ISO Frame 400/3/50 20' ISO Frame 480/3/60 20' ISO Frame 6003/60 EcoBreeze Module 208-230/3/60 EcoBreeze Module 400/3/50 EcoBreeze Module 480/3/60 EcoBreeze Module 600/3/60 EcoBreeze control panel 20' system IT air return duct 40' system IT air return duct EcoBreeze Screw-Jack Assembly APC by Schneider Electric – Ken Baer – 07/27/2010 40’ Frame contains up to 8 modules (400kW of cooling capacity) 20’ Frame contains up to 4 modules (200kW of cooling capacity) 40’ Frame (4 sections each) 20’ Frame (2 sections each) Module Dimensions 9.5 ft (2.9m) 40’ Frame *Same dimensions as HC (1AAA) ISO shipping container 3.3 ft 9.5 ft (2.9m) 40 ft (12.2m) 8 ft (2.4m) APC by Schneider Electric – Ken Baer – 07/27/2010 (1.1m) 8.6 ft (2.6m) IT Air Intake Isolation Dampers Central Water Trough Electrical Box / Frame Controller Redundant Pump/Pulse power water treatment Access Redundant Water Inlets Weight (40’ frame): 8,000 lb (3,628 kg) Max Weight (40’ frame, 8 modules, ducting, misc.): 33,500 lb (15,195 kg) APC by Schneider Electric – Ken Baer – 07/27/2010 Central Water Trough Redundant Water Inlets APC by Schneider Electric – Ken Baer – 07/27/2010 Chemical-Free Pulse power Water Treatment System Water Sump Tank Redundant Water Pumps Intake Fans Water Spray Nozzles / Drifdec Condenser IEC / Heat Exchanger Compressor Outside Air Fan Weight: 2,650 lb (1202 kg) 50 kW Cooling Capacity APC by Schneider Electric – Ken Baer – 07/27/2010 Water Collector Evaporator Coil / Filters Outside Air Fan (Scavenger Fan) 7,000 CFM per Module 5,000 CFM = 8495 m3/h IT Air Intake Fans 5,000 CFM per Module (40,000 CFM Fully Populated Frame) APC by Schneider Electric – Ken Baer – 07/27/2010 7,000 CFM = 11893 m3/h 40,000 CFM = 67960 m3/h EcoBreeze IEC Electrical Information ● Variety of Voltages ● 208-230/3/60 ● 460-480/3/60 ● 575-600/3/60 ● 400/3/50 ● ● ● ● ● Amp Draw less than 25A (per module based on 460V) Schneider Electric Controller Redundant Frame Electronics: RIM & MIM ModBUS RTU Interface Single Point Power Connection APC by Schneider Electric – Ken Baer – 07/27/2010 How it works High Level Application ● Mandatory Clearance: ● 4ft on ends of the frame ● 8ft between systems APC by Schneider Electric – Ken Baer – 07/27/2010 1. Hot air from the servers is controlled through Hot Aisle Containment (HACS) 2. The hot air is then rises to the ceiling plenum and fed into the return ducting of the EcoBreeze 3. The IT air is then cooled and supplied back to the data center through a raised floor plenum or cold aisle diffusers 4. The cool air is forced through the perforated tiles in front of the server racks and used to keep the servers at a safe operating temperature APC by Schneider Electric – Ken Baer – 07/27/2010 1. Hot air from the servers is controlled through ducting connected to the racks (VED) 2. The hot air is then rises to the ceiling plenum and fed into the return ducting of the EcoBreeze 3. The IT air is then cooled and supplied back to the data center through cold aisle diffusers. The diffusers have a bowling alley type discharge that sends the air down the cold aisle APC by Schneider Electric – Ken Baer – 07/27/2010 Hot ambient air is expelled through the condenser to the atmosphere Hot Air is returned from the Data Center 98°F102°F (37°C-39°C) Cool Ambient Air is brought in by the Scavenger Fan APC by Schneider Electric – Ken Baer – 07/27/2010 Cool IT Air is Supplied through the evaporator coil and back to the Data Center 77°F (25°C) Indirect Heat exchange between the IT and ambient airstreams (Evaporative or Air-to-Air) How it works Cooling Module – Air to Air Heat Exchange ● When ambient air drops below 45°F (setpoint adjustable) ● System water is dumped to prevent freezing and/or dumped after 24 hours (user adjustable) of spray free operation ● Only requires power of fans to move the air (If DX assist is not needed) ● Cool air passes over the outside of the heat exchanger channels, cooling the hot IT air flowing inside. APC by Schneider Electric – Ken Baer – 07/27/2010 How it works Cooling Module – Evaporative Cooling ● Heat is removed from the IT air by evaporating water on the outside of the heat exchanger channels ● Water is supplied evenly over the heat exchanger channels via spray nozzles ● Maintains the adjustable IT supply air set point APC by Schneider Electric – Ken Baer – 07/27/2010 How it works Cooling Module – Proportional DX Circuit ● Variable speed compressor allows for optimal efficiency of DX cooling ● Supplements evaporative cooling to maintain the supply air set point ● Designed for 60% of full load ● 410a Refrigerant APC by Schneider Electric – Ken Baer – 07/27/2010 Competitive Analysis 1MW Design Data Center @ 60% Load System Architecture EcoBreeze Air Econ w/ Heat Wheel Water Cooled Chiller w/ Econ Air Cooled Chiller w/ Econ Fresh Air Econ DX Fluid Cooled CRAC w/ Econ Partial PUE kW-Hr/Yr 1.09 1.10 1.14 1.16 1.14 1.20 466,518 503,999 728,195 846,039 718,159 1,044,073 Relative Power 45% 48% 70% 81% 69% 100% 1) Hot Aisle Containment 101.5°F Return to A/C 2) Supply Air / Cold Aisle 77°F 3) Bin Weather Data Saint Louis, MO 4) Does not reflect humidification losses 5) All system have fan control proportional to IT load % of design 55% more efficient than a perimeter CRAC w/ Economizer solution! APC by Schneider Electric – Ken Baer – 07/27/2010 Performance Indirect Evaporative Cooling Economizer EcoBreeze ™IECs (Seattle, WA) 1,2,3,4,5 ● Seattle, Washington ● Full economizer 8,550 hours per year ● Partial performance from econ balance of year ● Worse case DX percentage of IT load 10.4% ● Annualized COP ≈ 22 ● Water use 47% of Year Power Consuming Component Pump [kW-Hr/Yr] IT Fan [kW-Hr/Yr] Comp [kW-Hr/Yr] OA Fan [kW-Hr/Yr] Total [kW-Hr/Yr] COP 1) 102°F return air temperature to cooling system from IT load 2) 75°F supply air temperature back to data center 3) Actual EcoBreeze IECs airflow is proportional to load factor 4) Data is analytical and presently not validated by imperical test 5) Data is subject to revision without notice 60% Load Factor, 75°F Supply Set-point, 102°F Return APC by Schneider Electric – Ken Baer – 07/27/2010 IT Actual Load (10MW Design) 100% 80% 60% 40% 78,604 61,017 38,307 7,989 7,237,350 3,874,642 1,731,423 556,349 232,816 65,527 13,138 1,058 1,974,809 1,236,388 616,827 217,026 9,523,579 5,237,574 2,399,694 782,422 9 13 22 45 2,399,694 (kW hr) x .08 ($/kW) = ~$191,975/year mechanical operating costs for 30 systems Comparison Indirect Evaporative Economizer to Chilled Water Plant with Economizer Bin Weather Data - Seattle, WA 10000 Air to Air CW Plant 5000 0 Full Econ 100% Air to Air CW Plant 50% 0% Return Air 102.3°F (38.8°C) Supply Air 75°F (23.8°C) Design Capacity 10 MW Actual Load 6 MW (60%) Max DX CW Plant Tower: 10°F Range, 7°F Approach (95°F DB / 78°F WB). Chiller COP of 8 ≈3°F Approach Econ Plate Frame Heat Exchanger APC by Schneider Electric – Ken Baer – 07/27/2010 EcoBreeze Tools being developed •Design Standards (Based on existing MW designs replacing the cooling architecture with EcoBreeze). Partnering with a consulting engineering firm to develop this standard. •Performance tool that allows the customer to load their conditions based on location. Out puts performance and operating costs for power and water. Provides COP and partial PUE performance based on load conditions. •Submittal Drawing package showing Electro/Mechanical, Piping, One-Line, Cad Blocks, Site Preparation Dwgs. •EcoBreeze Video showing need for product based on changes to IT environments which allow cooling through economization. Shows application and airflow movement through the system. •White paper being developed by Victor Alvelar •Physical Models being created to show the application of the EcoBreeze. •Micro site that provides link to collateral generate for EcoBreeze APC by Schneider Electric – Ken Baer – 07/27/2010 Questions?? APC by Schneider Electric – Ken Baer – 07/27/2010