MWS D es c r ip tion MWS, Modular Wiring Systems, provides low cost installation of branch circuit wiring for lighting and power. Using modular components that plug together, MWS can be installed in a fraction of the time of hardwiring. Plus, MWS offers the advantage of relocating fixtures and outlets in future renovations. The MWS Fixture Cable (FC) continues power from the Starter or switch drop to the first lighting fixture and between lighting fixtures. The line side connector snaps into any 1/2" knockout and has 6" #18 leads to connect to fixture wiring. ® Type Catalog # Project Date Comments Prepared by Add length to MWS Fixture Cables with an Extender Cable. Des ign Fea tur es • UL Listed under Standard 183 for make or break under load. • Meets requirements of Article 604 of the National Electrical Code. • MWS componenets assembled with 12 AWG/10 AWG conductors rated at 20 amperes with full size ground wire. • THHN insulated conductors rated at 90°C with 16AWG solid TFN fixture leads. All leads come with pushwire connectors • Galvanized steel exterior with integral keying for voltage and amperage. • Positive self-grounding locking clip fits into any 1/2" KO on fixture. • Unique double-blade contact ensures proper mating of electrical components to prevent pushback or pullout. All unused outlets require a MWS dust cover. MWS ST, SP, SD , C T and TC are shipped with one dust cover attached. • Valox 365 constructed contact housing approved for environmental air plenums. FC Fixture Cable Dim ens iona l D a ta Modular Wiring System 1-7/8" [47mm] Front 4-3/8" [112mm] Front 4-3/8" [112mm] Top 5/8" [16mm] Side 3/4" [19mm] SYSTEM VIEW (not to scale) Fixture Cable Fixture Cable Fixture Cable (FC) Feeds power to fixtures and allows circuits to be carried through to other fixtures. Locks into 1/2" KO of access plate, fixture body or J-box. The unit adds 7/8" to overall height of the fixture. Quick Connect MWS AUTOCAD DRAFTING MWS offers AutoCAD drafting to layout MWS, providing the contractor with additional benefits. MWS design layout time is reduced. Typical MWS Wiring System Application shown utilizing Fixture Cable (FC). Bills of material are computer-generated guaranteeing accuracy. Consult MWS Installation, Application and Specification Manual for additional comprehensive system information. Layouts are available on CD or e-mail. MWS drawing symbols and details standardized. To utilize this service and for additional information, contact the MWS Sales Department (888) 487-4887. All electrical boxes, conduit, connections and switches by others. Install dust covers on unused open ends. Scale is exaggerated on fixtures and MWS system applications. YS TEM S S Specifications and dimensions subject to change without notice. ER C Consult your representative for additional options and finishes. D Fixture Cable TIFIE ADF031841 2013-02-05 16:22:49 MWS FC Order ing I nf or m a tion SA MP L E NUMB E R : 2 7 F C 1 2 /3 G 1 1 FC Voltage 12=120V 27=277V 34=347V NOTES: (1) Component FC=Fixture Cable Conductors and Size 12/2G=#12, 2 Conductors Plus Ground 12/3G=#12, 3 Conductors Plus Ground 12/4G=#12, 4 Conductors Plus Ground Cable Length (Feet) 07=7' 09=9' 11=11' 13=13' 15=15' 17=17' Options 2N=2 Neutral (1) 12/4G only. Specifications & dimensions subject to change without notice. Consult your Cooper Lighting Representative for availability and ordering information. MWS AUTOCAD DRAFTING MWS offers AutoCAD drafting to layout MWS, providing the contractor with additional benefits. MWS design layout time is reduced. SH IP P ING D ATA Bills of material are computer-generated guaranteeing accuracy. CableUnitStandard Length Wt.Qty./Carton 7' 2.5 lbs. 10 9' 3.0 lbs. 9 11' 3.5 lbs. 7 13' 4.0 lbs. 6 15' 4.5 lbs. 6 17' 5.0 lbs. 5 MWS drawing symbols and details standardized. Layouts are available on CD or e-mail. To utilize this service and for additional information, contact the MWS Sales Department (888) 487-4887. Specifications and dimensions subject to change without notice. MWS • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770 468.4801 ADF031841 2013-02-05 16:22:49