LRM – Lighting Relay Module Greengate Technical Data Overview

Greengate
Technical Data
LRM – Lighting Relay Module
Catalog#
Prepared by
Project
Date
Comments
Type
Overview
The Lighting Relay Module (LRM) is available in 347 VAC input
voltage. The LRM is designed to force all relays in a lighting control
panel to an ON or Closed state, regardless of the control panel
programmed relay status. This allows the closure of relays during
loss of normal (grid) power to allow an alternate power source to
drive the lighting loads. Once the LRM senses the normal power
returning, the control panel will return to the normal programmed
operating mode.
Features
UL 924 Listed Accessory
Detects loss of normal power and automatically sends signal to
lighting control panel
Allows Greengate panels to be listed as UL 924 when LRM is
connected

LRM – Lighting Relay Module


July 2015
Specifications
Connections
Power Sources
Compatibility
Standards
Connects to normal power
Lighting Control Panels must be fed from alternate
power
ControlKeeper M, ControlKeeper MB
UL Approved
UL 924 Listed
Description/Operation
The LRM provides a dry contact closure to the ControlKeeper M and
MB panels when normal (grid) power is lost. This contact closure
forces a hardware override of all relays in the enclosure to the ON
state. This override condition takes priority over any relay commands
from the system controller and will remain in effect until the contact
closure from the LRM is removed.
Installation
The LRM can be installed next to the lighting control panel
enclosure.
2
www.eaton.com/lightingsystems

LRM – Lighting Relay Module


July 2015
Wiring Diagrams
ControlKeeper M
ControlKeeperMotherboard
M Motherboard
RS485
RS485
TB2
MOR/LRM
On
R35
+24
Off
232 OPT
DISPLAY
LED6
LED7
LEFT RELAYS
ALL-OFF ALL-ON
NET NET
HEART TX
RIGHT RELAYS
J9
NET-RX
1
S1
1
RESET
A
J11
C
B
U35
J6
1
U37
SW2
SW4
SW3
1
SW6
MOR/LRM
U34
A
B
HEART
BEAT
U32
RS232 Boot Mode
The LRM needs to provide a dry
contact maintained closure to
the On and +24 terminals on the
ControlKeeper M motherboard
MOR connector.
J7
C67
D
SW5
For Emergency panel configurations,
ensure the ControlKeeper M lighting
control panel is fed from an emergency
power source.
ON
+24
MOR/RIM
OFF
+24V
CAN-H
SHIELD
CAN-L
USB
USB
HOST
DEVICE
GND
RS-232
ETHERNET
+
SH
+
-
J14
-
SH
CCM PWR
TO CCM
NET ADDRESS
+5
R25
Yellow
(18 AWG)
On
C158A
PG
+24
8 16 32 64 128
GND
4
GND
J15
2
+24
LED11
SCM PWR
C149
1
Off
SW1
5001-000006-05
To override On:
Connect dry contact between the On terminal and
the +24 VDC terminal. When contact closes, all
relays are forced On.
Contacts within the LRM will automatically close
when normal power is lost
NC
LRM
Lighting Relay
Module
C
NO
To Normal Power Circuit
347 VAC = Brown
Neutral = White
www.eaton.com/lightingsystems
3

LRM – Lighting Relay Module


July 2015
Ordering
This is an accessory for the ControlKeeper M and ControlKeeper
MB lighting control panels. When ordering, specify the LRM as a
separate system accessory.
Catalog #
Descriptoin
Rating
LRM347
Lighting Relay Module
347 VAC
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, GA 30269
coopercontrol.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. TD503036EN
July 27, 2015
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.