Greengate Technical Data LRM – Lighting Relay Module Catalog# Prepared by Project Date Comments Type Overview The Lighting Relay Module (LRM) is available in 347 VAC input voltage. The LRM is designed to force all relays in a lighting control panel to an ON or Closed state, regardless of the control panel programmed relay status. This allows the closure of relays during loss of normal (grid) power to allow an alternate power source to drive the lighting loads. Once the LRM senses the normal power returning, the control panel will return to the normal programmed operating mode. Features UL 924 Listed Accessory Detects loss of normal power and automatically sends signal to lighting control panel Allows Greengate panels to be listed as UL 924 when LRM is connected LRM – Lighting Relay Module July 2015 Specifications Connections Power Sources Compatibility Standards Connects to normal power Lighting Control Panels must be fed from alternate power ControlKeeper M, ControlKeeper MB UL Approved UL 924 Listed Description/Operation The LRM provides a dry contact closure to the ControlKeeper M and MB panels when normal (grid) power is lost. This contact closure forces a hardware override of all relays in the enclosure to the ON state. This override condition takes priority over any relay commands from the system controller and will remain in effect until the contact closure from the LRM is removed. Installation The LRM can be installed next to the lighting control panel enclosure. 2 www.eaton.com/lightingsystems LRM – Lighting Relay Module July 2015 Wiring Diagrams ControlKeeper M ControlKeeperMotherboard M Motherboard RS485 RS485 TB2 MOR/LRM On R35 +24 Off 232 OPT DISPLAY LED6 LED7 LEFT RELAYS ALL-OFF ALL-ON NET NET HEART TX RIGHT RELAYS J9 NET-RX 1 S1 1 RESET A J11 C B U35 J6 1 U37 SW2 SW4 SW3 1 SW6 MOR/LRM U34 A B HEART BEAT U32 RS232 Boot Mode The LRM needs to provide a dry contact maintained closure to the On and +24 terminals on the ControlKeeper M motherboard MOR connector. J7 C67 D SW5 For Emergency panel configurations, ensure the ControlKeeper M lighting control panel is fed from an emergency power source. ON +24 MOR/RIM OFF +24V CAN-H SHIELD CAN-L USB USB HOST DEVICE GND RS-232 ETHERNET + SH + - J14 - SH CCM PWR TO CCM NET ADDRESS +5 R25 Yellow (18 AWG) On C158A PG +24 8 16 32 64 128 GND 4 GND J15 2 +24 LED11 SCM PWR C149 1 Off SW1 5001-000006-05 To override On: Connect dry contact between the On terminal and the +24 VDC terminal. When contact closes, all relays are forced On. Contacts within the LRM will automatically close when normal power is lost NC LRM Lighting Relay Module C NO To Normal Power Circuit 347 VAC = Brown Neutral = White www.eaton.com/lightingsystems 3 LRM – Lighting Relay Module July 2015 Ordering This is an accessory for the ControlKeeper M and ControlKeeper MB lighting control panels. When ordering, specify the LRM as a separate system accessory. Catalog # Descriptoin Rating LRM347 Lighting Relay Module 347 VAC Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, GA 30269 coopercontrol.com © 2014 Eaton All Rights Reserved Printed in USA Publication No. TD503036EN July 27, 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.