Commercial Consistency Land Use and Environmental Service Agency (Code Enforcement) 4th Quarter Q&A 2011 General: 1. (Q) Is FRT alone an acceptable structural floor in a type I and II building? (A) No, see section 603.1. All structural elements must be noncombustible. (10/05/2011) 2. (Q) Is a tenant space or building with an assembly use with less than 50 occupants a B occupancy? (A) Yes, see section 303.1 exception 1. The occupant load, however, of the space is based on the use of the space not the occupant group. (10/05/2011) 3. (Q) What is the required floor rating for a floor supporting a shaft wall? (A) The floor must have the same rating as the shaft it supports. (10/05/2011) 4. (Q) Are guards required on green roofs? (A) No, if the roof is only accessed for maintenance. This would be covered by OSHA. (10/05/2011) 5. (Q) Are closures required on restroom entrance doors? (A) No, ANSI A117.1 section 404.1 requires the closures to be on stall doors. (11/02/2011) 6. (Q) Can sound proofing be applied over fire proofing? (A) Yes, there are products that have been approved to be applied over fire proofing. A letter of approval must be supplied from UL and the fire proofing manufacture. (12/07/2011) 7. (Q) Can the controls for a lavatory be mounted higher than the bowl? (A) Yes, the bowl must be located per ANSI A 117.1 section 606 and the controls may be located per the reach range requirements of section 309. (12/07/2011)