Consistency Meeting May 7, 2008 INSPECTORS

advertisement
Consistency Meeting
May 7, 2008
INSPECTORS
GERALD HARVELL
704-336-3523
WILLIAM.HARVELL@MECKLENBURGCOUNTYNC.GOV
ANGELA MILLER
704-432-1775
ANGELA.MILLER@MECKLENBURGCOUNTYNC.GOV
JOE WEATHERS
704-336-3521
JOSEPH.WEATHERS@MECKLENBURGCOUNTYNC.GOV
ANDY SCOGGINS
980-722-8195
HOWARD GINDSTAFF
704-201-5798
SARRAH KELLY
704-719-7114
JIM ELLIS
704-336-3810
DAVID SELLERS
704-719-7048
CONTRACTORS
DANNY SIMPSON
JIM LONG
BRUCE SAIMES
RONALD JUDSON
RUSSELL SANTOS
PATRICK KOSMELA
DREW GOAN
MIKE TISDELL
RON HEGGMAN
704-821-5200
704-553-7552 ext.113
704-596-2525
704-400-1048
704-821-5200
704-426-0047
CELL: 704-363-0234
CELL: 704-361-2226
CELL: 704-634-3020
CELL: 704-400-5067
CELL: 704-999-3771
csimp12@aol.com
jim.long@fryeelectric.com
bsaims@andersenservices.com
rjudson@carylelectrical.com
russellsantos@carolina.rr.com
pat@obelectric.com
agoan@carolina.rr.com
Tisdell-electric@carolina.rr.com
RonHeggman@yahoo.com
ATTENDANCE AT PREVIOUS MEETING
Present: Gerald Harvell, Angela Miller, Joe Weathers, Sarrah Kelly, David Sellers, Jim
Long, Ronald Judson, Russell Santos, Patrick Kosmela, Drew Goan, Patrick Blackwelder,
Randy Neill, Jim Guffy, Buster Beaver, Errol Cooper, Bob Hartman
Absent: Andy Scoggins, Howard Grindstaff, Jim Ellis, Danny Simpson, Bruce Saimes,
Mike Tisdell
CODE ISSUES FROM PREVIOUS MEETING
 680.74 Bonding. If a hydro massage tub is non-metallic, has plastic water
pipes and has a double-insulated motor - what exactly will
the equipotential bond apply to?
The bonding is not required to be connected to a double insulated circulating pump
motor. The number 8 AWG or larger solid copper bonding jumper shall be required
for equipotential bonding in the area of the tub but it is not required to be
extended or attached to any remote panelboard, service equipment or any
electrode.
 When using GFCI receptacles for the two required kitchen circuits, is it
possible to use 12/3 AWG NM_B cables to achieve this? What if I were to
use GFCI breakers?
No. As far as we know, there are no GFCI devices designed to work in this manner.
 FYI: 2008 Code Change/ Art. 338.10(B)(4)(a)
Due to the change in Article 338.10 (B) 4 (a), SE cable can only be sized per the 60
degree column for interior wiring. If it is a main power feeder it may still be sized
per table 310.15(B) 6.