Consistency Meeting July 11, 2007 INSPECTORS

advertisement
Consistency Meeting
July 11, 2007
INSPECTORS
GERALD HARVELL
ANGELA MILLER
JOE WEATHERS
ROGER BROWN
MICKEY DOBY
LAURAN JORGENSEN
BILLY PAYNE
ROGER WARD
DEBRA PARRIS
ANDY SCOGGINS
HOWARD GINDSTAFF
SARRAH KELLY
GARY MULLIS
704-336-3523
704-432-1775
704-336-3521
980-722-3594
704-634-8853
980-722-1249
980-722-3668
980-722-3622
980-722-7300
980-722-8195
704-201-5798
704-719-7114
704-336-4364
WILLIAM.HARVELL@MECKLENBURGCOUNTYNC.GOV
ANGELA.MILLER@MECKLENBURGCOUNTYNC.GOV
JOSEPH.WEATHERS@MECKLENBURGCOUNTYNC.GOV
CONTRACTORS
DANNY SIMPSON
JIM LONG
BRUCE SAIMES
MATT CURRAN
RICK METCALF
RONALD JUDSON
RUSSELL SANTOS
JASON BANKS
704-821-5200
704-553-7552 ext.113
704-596-2525
704-926-0047 ext.0045
704-400-1048
704-821-5200
704-331-9300
CELL: 704-363-0234
CELL: 704-361-2226
CELL: 704-634-3020
CELL: 704-361-6441
CELL: 704-201-5867
csimp@aol.com
jim.long@fryeelectric.com
bsaims@andersenservices.com
rmetcalf@lanehart.com
rjudson@carylelectrical.com
russellsantos@carolina.rr.com
JBanks@wbmoore.com
ATTENDANCE AT PREVIOUS MEETING
Present: Gerald Harvell, Angela Miller, Joe Weathers, Mickey Doby, Lauran Jorgensen,
Roger Ward, Debra Parris, Sarrah Kelly, Bruce Saimes, Jim Long, Matt Curran, Howard
Grindstaff, Russell Santos Jr, Andy Scoggins, Roger Brown, Ronald Judson, Danny
Simpson,
Absent: Rick Metcalf, Gary Mullis, Billy Payne, Jason Banks.
CODE ISSUES FROM PREVIOUS MEETING
Bonding of CSST piping.
The following was discussed at the consistency meeting; however this is not
effective until all issues have been resolved. Tentative date: 9/1/2007
CSST bonding is required by the manufacture of the CSST piping system.
CSST bonding is not required by the NEC
Bonding of CSST piping systems shall be installed using each manufactures
instructions of each specific type of CSST piping.
The following requirements apply to all installations of CSST piping (residential,
commercial, industrial, and intuitional)
The bonding of CSST piping shall be done by a licensed electrical contractor
holding a NC state electrical license in the SP-SF, Limited, Intermediate, or
Unlimited category.
SP-PH electrical license is not qualified to bond CSST piping.
The building or electrical permit issued for the connection of A/C units and
dwelling units do not provide for the connection of bonding of the CSST piping.
This is an additional requirement not included in the normal scope of work.
Additional permit(s) are required for the bonding of CSST piping.
It shall be the responsibility of the Mechanical contractor to provide the electrical
contractor and the electrical inspector the installation instructions for each and
every CSST piping installation.
Each piece of CSST piping shall be required to be bonded back to the service per
the manufactures instructions, even if this means bonding each piece separately and
individually. Care should be taken to read and follow the manufactures
instructions.
It is the Mechanical contractor’s responsibility to hire an Electrical contractor to
perform the bonding of the CSST pipe or inform the customer of this requirement
by the manufacture.
Effective ( ) all CSST piping will be required to be permitted and inspected per the
manufactures instructions, no matter when it was installed.
Does the water have to be running through the water system for temporary
power?
Many years ago because of the death of a CMUD employee to assure that no
additional accidents would happen; CMUD requested that we make sure that the
water pipe system was a completed system. It was agreed that the inspection
department would require water on the system to assure that it had been tied into the
city.
Wirenut approval:
Wire range (size and number of conductors) should be installed per the
manufactures specifications.
AGENDA
Delta Hi Leg Systems: Roger Brown
What is the policy on replacing a damaged meter can when the old existing SE
cable exceeds the permissible length of unfused conductor? Is replacing the
meter can only sufficient or should a panel also be installed so that the old SE
will have overcurrent protection?
Is it permissible to use Table 310.15 (B) (6) on a feeder to a sub panel at a
single family residence?
Is a new circuit required to be run on a water heater replacement that is fed
with an existing non-grounded circuit or is it permissible to run a separate
ground wire to the nearest grounding electrode?
Next Meeting: August 1, 2007
Download