LIEBERT® SITEIO-E™ SSW-28IOE™ Product Specification Description The Liebert SSW-28IOE is a general-purpose IO module that can be used to control multiple pieces of equipment simultaneously. The unit comes assembled and installed in an enclosure; see Enclosure Mounting Diagrams on page 2 and 3. The 32-bit microprocessor-based device is designed to monitor up to 28 analog, digital and/or dry contact signals and control up to four outputs. These outputs can be any combination of analog and digital. The outputs are controlled through custom programming defined by the user. These outputs support manual control override capabilities through switches on the module. Individual hardware jumpers set input signal-type selections. Screw terminal blocks are provided to terminate power, input and output signal wiring. Module Dimensions and Layout 11.295" (286.9mm) .23" (5.84mm) .23" (5.84mm) 1.25" (31.75mm) 2.5" (63.5mm) 7.5" (190.5mm) 2.5" (63.5mm) 1.25" (31.75mm) 1 Enclosure Mounting The enclosure may be mounted on a wall or on the floor. Refer to the following diagrams for your application. Enclosure Mounting Diagrams 0.88" (22.2mm) 0.88" (22.2mm) 12.5" (317.5mm) 1" (25.4mm) 1" (25.4mm) A 11" (279.4mm) 11" (279.4mm) 1" (25.4mm) 1" (25.4mm) 12.5" (317.5mm) R 0.107" (2.71mm) 0.88" (22.2mm) 0.4" (10.2mm) DETAIL A 2 R 0.188" (4.76mm) 0.88" (22.2mm) Enclosure Mounting Diagrams (continued) 14.25" (362mm) 12" (304.8mm) 3.35" (85mm) B 3.92" (99.6mm) 1.15" (29.3mm) 1.25" (31.8mm) 1.5" 1.5" (38.1mm) 1.5" (38.1mm) (38.1mm) 5.88" (149.2mm) 5.25" (133.4mm) 2.5" (63.5mm) 1.5" (38.1mm) 1.5" 0.6" 1.5" (38.1mm) (15.1mm) (38.1mm) 5.88" (149.2mm) 3 1.13" (28.6mm) 0.88" (22.2mm) DETAIL B Specifications Power 24VAC ±10%, 50-60Hz, 95VA; 26VDC ±10%, 44W Dimensions W x D x H: in. (mm) Overall: 7-1/2 x 2-3/4 x 11-5/16 (190.5 x 70 x 287) Weight, lb. (kg) 12.2 (5.53) Communication • • • Mounting: 5 x 2-3/4 x 10-13/16 (127 x 70 x 275) One (1) Ethernet 10/100BaseT RJ-45 port for BACnet/IP communication, half duplex BACnet Support: Conforms to the Advanced Application Controller (B-AAC) Standard Device Profile as defined in ANSI/ASHRAE Standard 135-2004 (BACnet) Annex L Rnet: Local laptop and/or BACview access port. Conforms to the BACnet Advanced Application Controller (B-AAC) Standard Device as defined in BACnet 135-2001 Annex L. Inputs 28 Inputs, configurable for 0-5VDC, 0-10VDC, 0-20mA, RTD, thermistor or dry contact Input Resolution 14 bit A/D Input Pulse Frequency 40 pulses per second. Minimum pulse width (on or off time) required for each pulse is 25 msec Outputs 4 outputs for 24VDC relay driver, 0–10 VDC (minimum resistance to ground must be 500 Ohms), or 0-20 mA (maximum resistance to ground must be 800 Ohms) (Device must share same ground as the control module; total output current from all outputs and Aux Power Out connection must not exceed 400 mA at 125°F [52°C] or 300 mA at 140°F [60°C] Output Resolution 12 bit D/A Microprocessor 32-bit Motorola Power PC microprocessor with cache memory, Fast Ethernet controller, high-performance 32-bit communication co-processor and I/O expansion CAN co-processor Memory 16 MByte non-volatile battery-backed SDRAM (12 MBytes available for use) 8 MByte flash memory, 32-bit memory bus Real-Time Clock Battery-backed real-time clock keeps track of time in event of power failure Environmental Operating Range 20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing. Note: Control modules should be installed within the building. Protection Built-in surge and transient protection circuitry for power, network, input, and output connections; Incoming power is protected by a replaceable 3A fuse. Automatically resetting internal solid-state polyswitches protect network connections. The power, network, input and output connections are also protected against voltage transient and surge events. Battery 10-year Lithium CR123A battery provides a maximum of 720 hours data retention during power failures. To extend battery life, battery backup turns off after a number of days defined in the module driver. Agency Listings UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart BClass A, CE EN50082-1997 Wiring Specifications Max. Wire Connection Length, ft. (m) Ethernet 10 BaseT Signal Type Gauge, Min. Signal Type Description 328 (100) (CAT5) N/A Thermistor 1 Precon type 2 (10 kOhm at 77°F). Input voltages should be from 0.489 to 3.825VDC for thermistors. Thermistor Dry Contact 1000 (305) 22 AWG Dry contact A 5VDC wetting voltage detects contact position, resulting in a 1 mA maximum sense current when the contacts are closed 0–5 VDC 1000 (305) 26 AWG 0–5 VDC 0-10VDC Source Output Impedance: <200Ohms Input Impedance: 20kOhm 0–10 VDC 1000 (305) 26 AWG 0–20 mA Input resistance on the positive (+) terminal: 250 Ohms Aux Power Out terminal is capable of supplying 24VDC to multiple 4– 20 mA transducers; total current demanded must not exceed 200 mA Ext. power supply required if voltage measured from the Aux Power Out terminal to Gnd is less than 18VDC 0–20 mA 3000 (914) 26 AWG RTD 1 Platinum - 1 kOhm at 32°F (0°C) Nickel/Iron - 1 kOhm at 70°F (21°C) Balco TS8000 - 1 kOhm at 70°F (21°C) Input voltages should be from 0.6–1.2 V. 100 (30) 22 AWG RTD Pulse Pulse counting up to 40 pulses per second. Minimum pulse width (on or off time) Counter 2 required for each pulse is 25 msec 1. To use a thermistor or RTD not listed above, a custom translation table for the sensor must be set up. 2. Liebert Site IO-E can perform pulse counting for dry contact or voltage inputs if input is assigned to a Pulse to Analog Input microblock. Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com © 2011 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-28081_REV0_12-11 4