ECE 576 – Power System Dynamics and Stability Lecture 16: Governors, Multimachine Simulations Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign overbye@illinois.edu 1 Announcements • • • • Exam average was 85 Homework 5 is assigned today; due on April 3 Read Chapter 7 A useful reference is B. Stott, "Power System Dynamic Response Calculations," Proc. IEEE, vol. 67, pp. 219241 2 IEEEG1 • A common stream turbine model, is the IEEEG1, originally introduced in the below 1973 paper In this model K=1/R Uo and Uc are rate limits It can be used to represent cross-compound units, with high and low pressure steam IEEE Committee Report, “Dynamic Models for Steam and Hydro Turbines in Power System Studies,” Transactions in Power Apparatus & Systems, volume 92, No. 6, Nov./Dec. 1973, pp 1904-15 3 IEEEG1 • • • Blocks on the right model the various steam stages About 12% of WECC governors are currently IEEEG1s Below figures show two test comparison with this model with one matching well and one not Image Source: Figs 2-4, 2-6 of IEEE PES, "Dynamic Models for Turbine-Governors in Power System Studies," Jan 2013 4 Deadbands • • Before going further, it is useful to briefly consider deadbands, with two types shown with IEEEG1 and described in the 2013 IEEE PES Governor Report The type 1 is an intentional deadband, implemented to prevent excessive response – Until the deadband activates there is no response, then normal response after that; this can cause a potentially large jump in the response – Also, once activated there is normal response coming back into range – Used on input to IEEEG1 5 Deadbands • The type 2 is also an intentional deadband, implemented to prevent excessive response – Difference is response does not jump, but rather only starts • once outside of the range Another type of deadband is the unintentional, such as will occur with loose gears – Until deadband "engages" there is no response – Once engaged there is a hysteresis in the response 6 Deadband Example: ERCOT • • Prior to November 2008, ERCOT required that the governor deadbands be no greater than +/- 0.036 Hz After 11/3/08 deadbands were changed to +/- 0.0166 Hz ERCOT Frequency Profile Comparison 525,600 One Minute Periods per Year 45000 One Minute Occurances 40000 35000 30000 25000 20000 15000 10000 2008 did have two months with the lower values 5000 60 60 .0 1 60 .0 2 60 .0 3 60 .0 4 60 .0 5 60 .0 6 60 .0 7 60 .0 8 60 .0 9 60 .1 59 .9 59 .9 1 59 .9 2 59 .9 3 59 .9 4 59 .9 5 59 .9 6 59 .9 7 59 .9 8 59 .9 9 0 2009 2008 Image Source: Sydney Niemeyer, NRG, 2/9/10 presentation to Texas Regional Entity (part of ERCOT) 7 Gas Turbines • • A gas turbine (usually using natural gas) has a compressor, a combustion chamber and then a turbine The below figure gives an overview of the modeling HRSG is the heat recovery steam generator (if it is a combined cycle unit) Image from IEEE PES, "Dynamic Models for Turbine-Governors in Power System Studies," Jan 2013 8 GAST Model • Quite detailed gas turbine models exist; we'll just consider the simplest, which is still used some It is somewhat similar to the TGOV1. T1 is for the fuel valve, T2 is for the turbine, and T3 is for the load limit response based on the ambient temperature (At); T3 is the delay in measuring the exhaust temperature 9 Play-in (Playback) Models • • • Often time in system simulations there is a desire to test the response of units (or larger parts of the simulation) to particular changes in voltage or frequency – These values may come from an actual system event "Play-in" or playback models can be used to vary an infinite bus voltage magnitude and frequency, with data specified in a file PowerWorld allows both the use of files (for say recorded data) or auto-generated data – Machine type GENCLS_PLAYBACK can play back a file – Machine type InfiniteBusSignalGen can auto-generate a signal 10 PowerWorld Infinite Bus Signal Generation • Below dialog shows some options for auto-generation of voltage magnitude and frequency variations Start Time tells when to start; values are then defined for up to five separate time periods Volt Delta is the magnitude of the pu voltage deviation; Volt Freq is the frequency of the voltage deviation in Hz (zero for dc) Speed Delta is the magnitude of the frequency deviation in Hz; Speed Freq is the frequency of the frequency deviation Duration is the time in seconds for the time period 11 Example: Step Change Voltage Response • Below graph shows the voltage response for the four bus system for a change in the infinite bus voltage 1.125 1.12 1.115 1.11 1.105 1.1 1.095 1.09 1.085 1.08 1.075 1.07 1.065 1.06 1.055 1.05 1.045 1.04 1.035 1.03 1.025 1.02 1.015 1.01 1.005 1 0 1 2 3 b c d e f g 4 5 V (pu)_Bus Bus 2 g b c d e f 6 7 8 9 10 V (pu)_Bus Bus 4 Case name: B4_SignalGen_IEEEG2 12 Simple Diesel Model: DEGOV • • Sometimes models implement time delays (DEGOV) – Often delay values are set to zero Delays can be implemented either by saving the input value or by using a Pade approximation, with a 2nd order given below; a 4th is common e sTD 1 k1 s k2 s TD , k1 , k2 2 1 k1 s k2 s 2 12 2 TD2 13 DEGOV Delay Approximation With TD set to 0.5 seconds (which is longer than normal in order to illustrate the delay) Transient Stability Tim e Step Results Variables 1.2 1.19 1.18 1.17 1.16 1.15 1.14 1.13 1.12 Values • 1.11 1.1 1.09 1.08 1.07 1.06 1.05 1.04 1.03 1.02 1.01 1 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5 Time Gen Bus 4 #1 States of Governor\Actuator 3 Gen Bus 4 #1 Other Fields of Governor\Engine 14 Hydro Units • Hydro units tend to respond slower than steam and gas units; since early transient stability studies focused on just a few seconds (first or second swing instability), detailed hydro units were not used – The original IEEEG2 and IEEEG3 models just gave the linear • response; now considered obsolete Below is the IEEEG2; left side is the governor, right side is the turbine and water column For sudden changes there is actually an inverse change in the output power 15 Four Bus with an IEEEG2 • Graph below shows the mechanical power output of gen 2 for a unit step decrease in the infinite bus frequency; note the power initially goes down! 175 60 170 59.95 165 160 155 150 145 59.8 59.75 140 59.7 135 59.65 130 59.6 125 59.55 120 59.5 115 59.45 110 105 100 95 90 Physically this is caused by a transient decrease in the water pressure when the valve is opened to increase the water flow 59.9 59.85 59.4 59.35 59.3 59.25 85 59.2 80 59.15 75 59.1 70 59.05 65 59 0 1 2 b c d e f g 3 4 Speed_Gen Bus 2 #1 5 b c d e f g 6 7 8 9 10 Mech Input_Gen Bus 4 #1 Case name: B4_SignalGen_IEEEG2 16 IEEEG3 • • This model has a more detailed governor model, but the same linearized turbine/water column model Because of the initial inverse power change, for fast deviations the droop value is transiently set to a larger value (resulting in less of a power change) WECC has about 10% of their governors modeled with IEEEG3s 17 Washout Filters • A washout filter is a high pass filter that removes the steady-state response (i.e., it "washes it out") while passing the high frequency response sTw 1 sTw • • They are commonly used with hydro governors and (as we shall see) with power system stabilizers With hydro turbines ballpark values for Tw are around one or two seconds 18 IEEEG3 Four Bus Frequency Change • The two graphs compare the case response for the frequency change with different Rtemp values 60 107 106.5 106 105.5 105 104.5 104 103.5 60 59.95 117 59.9 116 59.85 115 114 59.8 113 59.75 112 59.7 59.65 59.95 59.9 59.85 59.8 59.75 111 59.7 110 59.65 103 59.6 109 59.6 102.5 59.55 108 59.55 102 59.5 107 59.5 101.5 59.45 106 59.45 101 59.4 105 59.4 100.5 59.35 104 59.35 100 59.3 103 99.5 59.25 102 59.2 101 99 98.5 98 97.5 97 100 59.15 99 59.1 98 59.05 97 59 59.3 59.25 59.2 59.15 59.1 59.05 59 0 1 2 b c d e f g 3 4 5 Speed_Gen Bus 2 #1 b c d e f g 6 7 8 9 Mech Input_Gen Bus 4 #1 Rtemp = 0.5, Rperm = 0.05 10 0 1 2 b c d e f g 3 4 Speed_Gen Bus 2 #1 5 b c d e f g 6 7 8 9 10 Mech Input_Gen Bus 4 #1 Rtemp = 0.05, Rperm = 0.05 Case name: B4_SignalGen_IEEEG2 19 Basic Nonlinear Hydro Turbine Model • • Basic hydro system is shown below – Hydro turbines work be converting the kinetic energy in the water into mechanical energy – assume the water is incompressible At the gate assume a velocity of U, a cross-sectional penstock area of A; then the volume flow is A*U=Q; Source: 9.2, Kundur, Power System Stability and Control, 1994 20 Basic Nonlinear Hydro Turbine Model • From Newton's law dQ L Fnet A g H H gate H loss dt where is the water density, g is the gravitational constant, H is the static head (at the drop of the reservoir) and H gate is the head at the gate (which will change as the gate position is changed) and H loss is the head loss due to friction in the penstock • As per [a] paper, this equation is normalized to dq dt 1 hgate hloss TW T is called the water time constant, or water starting time [a] "Hydraulic Turbine and Turbine Control Models for System Dynamic Studies," IEEE Trans. Power Syst., Feb, 92 21 Basic Nonlinear Hydro Turbine Model • • • With hbase the static head, qbase the flow when the gate is fully open, an interpretation of Tw is the time (in seconds) taken for the flow to go from stand-still to full flow if the total head is hbase If included the head losses, hloss, vary with the square of the flow The flow is assumed to vary as linearly with the gate position (denoted by c) q q c h or h c 2 22 Basic Nonlinear Hydro Turbine Model • Power developed is proportional to flow rate and head, with a term qnl added to model the fixed turbine (no load) losses – The term At is used to change the per unit scaling to that of the electric generator Pm At h q qnl 23 Model HYGOV • This simple model, combined with a governor, is implemented in HYGOV About 10% of WECC governors use this model Hloss is assumed small and not included The gate position (gv) to gate power (pgv) is sometimes represented with a nonlinear curve 24 Linearized Model Derivation • The previously mentioned linearized model can now be derived as dq 1 h(c) gate dt TW h(c) gate d q q q q c h dt TW c h And for the linearized power Pm Pm Pm h q h q q Pm Pm q sTw h c Pm c q Then q c 1 sTw h 25 Four Bus Case with HYGOV • The below graph plots the gate position and the power output for the bus 2 signal generator decreasing the speed then increasing it Note that just like in the linearized model, opening the gate initially decreases the power output 0.96 0.955 0.95 112 111 110 0.945 109 0.94 108 0.935 0.93 0.925 0.92 0.915 107 106 105 104 103 0.91 102 0.905 101 0.9 100 0.895 99 0.89 98 0.885 97 0 1 2 3 g b c d e f b c d e f g 4 5 6 7 8 9 10 Mech Input_Gen Bus 4 #1 States of Governor\Gate_Gen Bus 4 #1 26 PID Controllers • • Governors and exciters often use proportional-integralderivative (PID) controllers PIDs combine – Proportional gain, which produces an output value that is proportional to the current error – Integral gain, which produces an output value that varies with the integral of the error; this will eventually drive the error to zero – Derivative gain, which acts to predict the system behavior. This can enhance system stability, but it can be quite susceptible to noise 27 PID Example: Position Control • • • • Say we wish to get an object to a position in 1dimensional space by controlling its acceleration (force) – Error is distance from desired position – Control is speed With just proportional control, acceleration will be decreasing, but we'd reach maximum speed at the desired point, overshooting With derivative control, we'll be slowing down, avoiding the overshoot The integral term will make sure we stay at the desired point 28 HYG3 • The HYG3 models either a PID or a double derivative Looks more complicated than it is since depending on cflag only one of the upper paths is used 29