Saint Paul
Sustainable Building Policy
Training Module Six
Indoor environmental quality
requirements
SAINT PAUL SUSTAINABLE BUILDING POLICY
Indoor environmental quality
• Background
– Ventilation
– Construction indoor air quality
– Low emitting materials
– Thermal comfort
• General reporting requirements
• Requirements for specific rating systems
SAINT PAUL SUSTAINABLE BUILDING POLICY
BACKGROUND
SAINT PAUL SUSTAINABLE BUILDING POLICY
Background
• Indoor environmental quality (IEQ) is an essential
part of providing a healthy and comfortable
environment for residents and employees.
• The Saint Paul Overlay has four indoor
environmental quality sections:
– Ventilation requirements
– Construction Indoor Air Quality (IAQ)
management plan
– Selection of low-emitting materials
– Thermal comfort
SAINT PAUL SUSTAINABLE BUILDING POLICY
Ventilation requirements
• Exhaust pollutants
• Mitigate negative health effects
• Manage moisture
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management
• Manage dust and pollutants created during
the construction process.
• Minimize exposure to construction hazards
both to the occupants of the building and
workers during construction.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Low-emitting materials
• Limit the amount of pollutants entering the
indoor environment.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Thermal comfort
• Thermal comfort requirements set limits on
radiant temperature, air temperature, and
humidity, based on building type and a variety
of other factors.
• Intended to provide a comfortable indoor
environment for most occupants.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Specific requirements: Indoor
environmental quality
• ASHRAE standards 62.1 and 62.2
– Define appropriate rates of ventilation
– Commonly incorporated into sustainable building
standards
SAINT PAUL SUSTAINABLE BUILDING POLICY
Specific requirements: Construction
IAQ Management
• During-construction:
– Establish a plan of construction IAQ management
– For buildings occupied while under construction,
follow the SMACNA IAQ guidelines
– Includes specific requirements if not outlined in
guideline or rating system
• Post-construction IAQ management: requires
a pre-occupancy “Building Flush Out” period
SAINT PAUL SUSTAINABLE BUILDING POLICY
Specific requirements: Low-emitting
materials
• Limit the amount of Volatile Organic
Compounds (VOCs) including formaldehyde
present in building materials.
– Primarily achieved through product selection,
typically of paints, adhesives, wood products,
carpet and other interior finishes.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Specific requirements: Thermal
Comfort
• ASHRAE Standard 55
– Defines the range of indoor thermal
environmental conditions acceptable to a majority
of occupants.
SAINT PAUL SUSTAINABLE BUILDING POLICY
GENERAL REPORTING
REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
General reporting requirements:
Ventilation
• Use the Indoor Environment Quality
Worksheet found at:
– www.sustainablebuildingpolicy.umn.edu/saintpaul
• Include a list of spaces found in the project,
their required ventilation rates per ASHRAE 62
and the ventilation rate as designed.
• Submit the completed Worksheet to DSI and
PED
SAINT PAUL SUSTAINABLE BUILDING POLICY
General reporting requirements:
Construction IAQ management Plan
• Submit the required IAQ construction
management plan.
– Indicate in bid and construction documents that
compliance with the Construction Indoor Air
Quality Management Plan is required.
– The Template for construction IAQ management
plan is available at
www.sustainablebuildingpolicy.umn.edu/saintpaul
– Submit completed plan to DSI and PED
SAINT PAUL SUSTAINABLE BUILDING POLICY
General reporting requirements:
Low-emitting materials requirements
• List the products which have been specified for the
the project, along with product type and and method
of verification of compliance ( please list the
database of compliant materials in which the product
appears, or the certification that the product has
recieved).
– Template for Materials Selection Log available at
www.sustainablebuildingpolicy.umn.edu/saintpaul
– Required for products listed under each rating system, specific
requirements vary.
– Submit completed log to DSI and PED
SAINT PAUL SUSTAINABLE BUILDING POLICY
General reporting requirements:
Thermal comfort
• List all spaces in the building, their designed high and low
temperature set points during occupancy, air speed and
relative humidity, verifying that they are within the required
comfort zone for compliance with ASHRAE 55. For spaces
where mean radiant temperature or other indoor comfort
factor may be an issue, list strategies to maintain indoor
surface temperatures within 20 degrees Fahrenheit and
mitigate other comfort factors.
– Template available at
www.sustainablebuildingpolicy.umn.edu/saintpaul - note that this is a
shared template with the ventilation requirement.
SAINT PAUL SUSTAINABLE BUILDING POLICY
REQUIREMENTS FOR SPECIFIC
RATING SYSTEMS
SAINT PAUL SUSTAINABLE BUILDING POLICY
LEED N.C. 2009
LEED N.C. 2009
IEQ REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
Ventilation requirements
LEED N.C. 2009
• Achieve IEQ Prerequisite 1: Minimum indoor
air quality performance.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan
requirements
LEED N.C. 2009
• Achieve IEQ Credit 3.1 and 3.2: Construction
IAQ Management Plans, both During
Construction and Before Occupancy for 2
points total.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Low-emitting materials requirements
LEED N.C. 2009
• Achieve IEQ Credits 4.1, 4.2, 4.3, 4.4: LowEmitting Materials for 4 points total.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Thermal comfort requirements
LEED N.C. 2009
• Achieve IEQ Credit 7.1: Thermal Comfort for 1
point.
SAINT PAUL SUSTAINABLE BUILDING POLICY
GBI - Green Globes
GBI - GREEN GLOBES
IEQ REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
Ventilation requirements
GBI - Green Globes
• Achieve 10 points for credit 12.1.1.1.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan
GBI – Green Globes
• Achieve 4 points for credit 6.2.4.1 and 5 points
for credit 6.2.4.2.
And
• Meet construction air quality requirements of
SMACNA IAQ Guideline for Occupied Buildings
under Construction. Requirements include
elements for IAQ protection during construction.
See the Saint Paul Overlay to the Sustainable
Building Policy for more information.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Low-emitting material requirements
GBI - Green Globes
• Achieve 8 points for credit 12.2.1.1: Volatile
Organic Compounds.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Thermal comfort requirements
GBI - Green Globes
• Achieve 10 points from section 12.5.2.1:
Thermal comfort design.
SAINT PAUL SUSTAINABLE BUILDING POLICY
B3 - Minnesota Sustainable
Building Guidelines
B3-MINNESOTA SUSTAINABLE
BUILDING GUIDELINES
IEQ REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
B3 - Minnesota Sustainable
Building Guidelines
Ventilation requirements
• Achieve required MSBG criteria I.4.
SAINT PAUL SUSTAINABLE BUILDING POLICY
B3 - Minnesota Sustainable
Building Guidelines
Ventilation requirements
SAINT PAUL SUSTAINABLE BUILDING POLICY
B3 - Minnesota Sustainable
Building Guidelines
Construction IAQ management plan
• Achieve required MSBG criteria P.4.
SAINT PAUL SUSTAINABLE BUILDING POLICY
B3 - Minnesota Sustainable
Building Guidelines
Low-emitting material requirements
• Achieve required MSBG criteria I.2.
SAINT PAUL SUSTAINABLE BUILDING POLICY
B3 - Minnesota Sustainable
Building Guidelines
Thermal comfort requirements
• Achieve required MSBG criteria I.5, including
optional section E.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Green Communities
MINNESOTA GREEN COMMUNITIES
IEQ REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
Ventilation requirements
Green Communities
• Achieve mandatory credit 7-6, installing a
ventilation system that supplies fresh air per
ASHRAE 62.1 - 2007.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan
Green Communities
• Minnesota Green Communities does not have
a satisfactory ventilation criterion. Instead
meet Sections 1 and 2 of the following
guidelines, when applicable:
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan –
section 1
Green Communities
• Comply with a pre-occupancy building flushout as described in LEED N.C. Version 2.2.
• Total air volume of 14,000 cu. ft. of outdoor
air per sq. ft. of floor area
• 60 degrees temperature
• 60% maximum relative humidity
• Replace all filtration media prior to occupancy
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan –
section 2
Green Communities
• Meet construction air quality requirements of
SMACNA IAQ Guideline for Occupied Buildings
under Construction.
• Maintain ventilation continuously during
installation.
• Ventilate areas directly to outside.
• During dust-producing activities (e.g., drywall
installation and finishing, and transportation
and delivery), turn ventilation system off.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Low-emitting material requirements
Green Communities
• Achieve required credits 7-1, 7-2, 7-3 and 7-4
SAINT PAUL SUSTAINABLE BUILDING POLICY
Thermal comfort requirements
Green Communities
• Meet the requirements of ASHRAE Standard
55–2004: Thermal Comfort Conditions for
Human Occupancy.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Minnesota GreenStar
MINNESOTA GREEN STAR
IEQ REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
Ventilation requirements
Minnesota GreenStar
• Achieve Section 5A-PR1
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan
Minnesota GreenStar
• Satisfy overall requirement OPR-4
• Achieve 3 points for section 8F-1
SAINT PAUL SUSTAINABLE BUILDING POLICY
Low-emitting material requirements
Minnesota GreenStar
• At a minimum, achieve credits in the following
categories:
8A-3c, 8A-3f, 8A-6d, 8B-5, 8B-9d, 8C-2d, 8C5d, 8D-2d, 8E-2 (for no-added urea
formaldehyde), 8E-3, 8F-2, 8F-3.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Thermal comfort requirements
Minnesota GreenStar
• Meet the requirements of ASHRAE Standard
55–2004: Thermal Comfort Conditions for
Human Occupancy.
SAINT PAUL SUSTAINABLE BUILDING POLICY
LEED for Homes
LEED FOR HOMES
IEQ REQUIREMENTS
SAINT PAUL SUSTAINABLE BUILDING POLICY
Ventilation requirements
LEED for Homes
• Achieve required criteria for Indoor
Environmental Quality (EQ) credit 4.1: Basic
Outdoor Air Ventilation.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Construction IAQ management plan
LEED for Homes
• Achieve at least 1 point each for the following:
– EQ credit 8.1 Indoor contaminant control during
construction
– EQ credit 8.2: Indoor contaminant control
– EQ Credit 8.3: Preoccupancy flush
SAINT PAUL SUSTAINABLE BUILDING POLICY
Low-emitting material requirements
LEED for Homes
• Achieve all possible points in section Materials
and Resources (MR) 2.2 by achieving lowemissions standards for Environmentally
Preferable Products.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Thermal comfort requirements
LEED for Homes
• Achieve at least 1 point for EQ 6: Distribution
of Space Heating and Cooling.
SAINT PAUL SUSTAINABLE BUILDING POLICY
Questions?
SAINT PAUL SUSTAINABLE BUILDING POLICY
End of Module 6