device

advertisement
FireClass
Addressable
FC501
Part 2
- Panel Use
FC501 Engineering
FC501 – Summary
•
•
•
•
•
•
•
•
•
•
•
•
•
•
3 in 1 Loops
Up to 400mA current dynamically shared across 3 loop circuits
Two versions available (1.5 A or 2.5 A power supply)
Up to 128 Addresses / 32 Zones (8 with LED Indications)
Easy to program
Auto Addressing
Auto mapping with Intelli-Zone feature
Out of the Box, auto set up for common fire operation
On Screen Help function
USB interface dual role Host/Device
Multi Users / Multi Installers (Up to 2 Installers, 8 Users)
Walk test function
4000 Event Log
Loop break location
2
FC501 Engineering
New Addressable Panel for Conventional Needs
•
An entry level Triple-Loop addressable
system featuring Intelli-Zone mapping
•
An “out of the box” panel that replaces
conventional technology with a more
powerful, cost effective solution
•
A perfect choice for small systems, with up
to 128 devices shared across 1,2 or 3 loops
•
A panel that uses the wide range of loop
devices provided by FireClass
3
FC501 Engineering
New Addressable Panel for Conventional Needs
•
Zonal LEDS present for zones 1 to 8 on the
panel display. Other zones indicated on the
LCD display only.
•
All three loops must be free of wiring faults
for auto-enrolment to operate.
•
You can select (using the software only) the
configuration for the three loops. They can
be selected as a loop (4 wire) or bus (2
wire). This gives great flexibility.
•
Two power supplies fitted dependent on
market. UK – BAQ60T24 (2.5A) giving
400mA of loop power in total. Rest of the
World –BAQ35T24 (1.5A) giving 200mA of
loop power in total.
4
FC501 Engineering
New Addressable Panel for Conventional Needs
•
Two programmable installer codes and
eight programmable user codes. Defaults
are 00000 (level 2) for the installer and
11111 (level 1) for the user respectively.
•
Lost installer code reset is possible (link on
the PCB).
•
Two 24V Aux supplies, each rated at
500mA, available at the panel, one of which
(24R) is Resettable and the other (24A) is
Always present.
•
Two conventional sounder circuits present
at the panel, SND1 and SND2. SND2 can
be programmed for other uses. 3K9 EOL
resistor.
5
FC501 Engineering
New Addressable Panel for Conventional Needs
•
Fire and fault relays C/NC/NO (normally deenergised) present at the panel.
•
Two programmable open-collector outputs
(OC1 and OC2) available at the panel.
•
Non- networkable
•
Maximum four repeater panels can be
connected to the panel (RS485 line). 24V
Aux supply also available for repeaters.
•
Space for 7Ah or 12Ah (max) batteries
within housing.
6
FC501 Engineering
New Addressable Panel for Conventional Needs
•
Day/Night Functionality
•
4000 Event, time and date stamped, nonvolatile log
•
Log can be cleared using a menu option
•
USB Interface
•
Loop break location
•
Inbuilt PSTN communicator
•
Optional IP communicator
7
L
R
Loop 3
L
R
Loop 2
L
R
Loop 1
8
FC501 Engineering
PC Link
Line Int’
Line Ext’
Earth
Fire/Fault
Relays
2x
Sounders
Mic/Spk
O/P’s (x2)
Open Collector
Reptr 24V
RS485
Batt’ 24v
24V O/P
PSU I/P
FC501 Engineering
Menu Options
•
To access the menu press the ESC key
•
Three levels of access; level 1 – no code
required, level 2 – user code required, level
3 – installer code required.
•
Current access level is displayed in the top
right hand corner of the display together
with the panel ‘heartbeat’
•
Certain control buttons must be enabled by
entry of a minimum level 2 code
(silence/resound sounders, Reset and
Investigate Delay)
•
‘Controls On’ LED illuminates when a level
2 or level 3 code is entered. One minute
time-out.
9
FC501 Engineering
Main Menu Options
•
Quiescent display (e.g. J. Bloggs Fire, London,
Tel:0208 111 2222) can be programmed using
the configuration software only.
•
Six options available on the main menu;
Grouped into two lists.
•
1=Program, 2=Analyse, 3=View Log, 4=More
•
1=Disable, 2=View Lists, 3=Modify, 4=More
•
Only three options can be displayed on the
LCD at one time. Toggle between the two lists
using the ‘4=More’ option.
10
FC501 Engineering
Main Menu Options: 1=Program
•
Accessed via use of installer code only – level 3.
•
Nine options available on the sub-menu
•
1=Auto, 2=Device, 3=SW Zone, 4=Output,
5=Network, 7=USB, 8=System, 9=Default, 0=L3
PWD.
•
1=Auto is the auto-enrolment feature which autoaddresses the devices found on the loop with
default address 255 and assigns a zone to the
device on the following selectable basis:
• On loop basis
• On device address basis
• No assignment
•
All outputs are set to activate on any alarm from
the panel during auto-enrolment.
11
FC501 Engineering
Main Menu Options: 2=Analyse
•
No code required (view only) – Level 1.
•
Ten options available on the sub-menu
•
1=Loop, 2=Device, 3=SW Zone, 4=Output,
5=Network, 6= Communication, 7=Options,
8=Log, 9=FW Version, 0=Panel.
•
2=Device allows you to view the condition of a
device in ‘real-time’. In particular, you can view
the temperature, CO level and smoke level for
any detector:
• Choose loop [L1] L2 L3
• Choose device or module on the loop
[d001] d002 m003 etc
• View real time data
•
8=Log gives direct access to the log.
12
FC501 Engineering
Main Menu Options: 3=View Log
•
No code required (view only) – Level 1.
•
Gives direct access to the log.
•
4000 event, time and date stamped, nonvolatile log.
•
Number of events in the log is displayed on the
top left hand side of the display
• Total – No of events in log
• Index – the number of the current
event
• You can use the up/down scroll
buttons to move through the log.
13
FC501 Engineering
Main Menu Options: 1=Disable
•
Accessed via use of user code – level 2.
•
Six options available on the sub-menu
•
1=Disabled List, 2=Device, 3=SW Zone,
4=Output, 5=Network, 6= Telecom
•
1=Disabled List, displays three listing options;
1= Dis.Zone, 2=Dis. Dev and 3=Dis. Part. If
any list has an active disablement the
respective numeral will flash.
•
2=Device allows you to disable a device
• Choose loop [L1] L2 L3
• Choose device or module on the loop
[d001] d002 m003 etc
• Confirm disablement / re-enablement
14
FC501 Engineering
Main Menu Options: 2=View Lists
•
No code required (view only) – Level 1.
•
Seven options available on the sub-menu
•
1=Dis. Zones, 2=Dis.Device, 3=Dis.Part,
4=Walk Test, 5=Faults, 6= Warnings, 7=Dev. In
Test.
•
If any list has an active member the respective
numeral will flash e.g. if a fault is present the ‘5’
will be flashing.
•
Selecting one of the flashing lists will display
the identity, address, loop etc of the device
concerned.
15
FC501 Engineering
Main Menu Options: 3=Modify
•
Accessed via use of user code – level 2.
•
Six options available on the sub-menu
•
1=Init MSG, 2=L2-user Password,
3=Day/Night, 4=Time & Date, 5=Clear LOG, 6=
Zone Walk Test.
•
6=zone walk test, can be used by the
technician or user to place zones in walk test
mode e.g. for routine inspection/testing.
•
Each zone must be placed in walk test
individually
•
Walk test mode is non-volatile.
16
FC501 Engineering
Walk Test Mode Operation
•
Accessed via 3=Modify on the Main menu
•
Test Lamp will illuminate on the front cover
•
No sounders, buzzers or any audible indication
on the panel
•
The First and Last device tested is displayed in
real time on the panel display (as long as the
panel is quiescent)
•
Full details of the walk test are stored in the
event log for audit purposes.
•
Maximum five LEDs lit at any one time
•
Before exiting walk test mode you can reset the
panel as many times as you wish to ensure that
no devices are still in alarm condition.
17
FC501 Engineering
Loop devices – Things to Remember
•
There are 128 addresses available on the loop
•
Multi I/O devices do NOT take multiple
addresses. Instead each input and output on a
multi I/O device is considered to be a separate
channel of the multi I/O device at the single
address of the device.
•
For example an MIO410 addressed as 003 on
the loop is referenced as m003 (m for module)
with seven input/output channels named as i1,
i2, i3, o1, o2, o3, o4. Each of these is
individually programmable.
•
As a result the limit of 128 addresses on the
loop can actually be considered to be a limit of
128 devices whether they are multi I/O devices
or not.
18
FC501 Engineering
Loop devices – Things to Remember
•
There is no fault message on the FC501
equivalent to ‘unconfigured device’.
•
A device which is pre-programmed in the range
1 to 255 and present on the loop but not known
to the panel will not be seen or reported as an
‘unconfigured device’.
•
Auto-enrolment will inform the panel of any preprogrammed device it finds on the loop in the
range 1 -128 and will also inform and auto
address any device it finds on the loop with
address 255.
19
FC501 Engineering
Day / Night Setting
•
Day /night setting enables two facilities:
•
•
Delayed alarm activation (with suitable pre-alarm delay set in software)
The ability to change the mode of detectors via the software
•
Transition from day to night can be set up in the software to change
automatically based on the specified times. Alternatively it can be left to be
changed manually as required from the panel menu.
20
FC501 Engineering
Day / Night Setting
•
Delayed Alarm in Day Mode - The initial
investigate period is set on the FC501 by
use of the pre-alarm delay. On initial
activation of a detector there is a buzzer
and a ‘Time to Alarm’ counter on the LCD
display. If the ‘Investigate Delay’ button is
not pressed to extend the time then the
panel enters full alarm. As usual the
delay only applies if a pre-alarm time has
been set, the panel is in day mode and
the activated device is a detector. Delay
does not apply to Callpoints or Evacuate
buttons
•
Detector Mode Settings – Different modes
of operation can be selected for detectors
based on whether the FC501 is currently
in Day or Night mode.
21
FC501 Engineering
Auto-Enrolment
•
There is no fault message on the FC501
equivalent to ‘unconfigured device’.
•
A device which is pre-programmed in the range
1 to 255 and present on the loop but not known
to the panel will not be seen or reported as an
‘unconfigured device’.
•
Auto-enrolment will inform the panel of any preprogrammed device it finds on the loop in the
range 1 -128 and will also inform and auto
address any device it finds on the loop with
address 255.
22
FC501 Engineering
Device Mapping Option
•
Can be used to program loop devices during
commissioning by activating devices on the
loop(s) in sequence.
•
Option is available only if non-addressed
devices (address 255) are found during
enrolment and auto-addressing is invoked.
•
Two situations to consider;
i.
Multiple devices of the same type on the loop.
ii.
Only one device of a particular type on the
loop.
•
In order for the panel to address multiple
devices of the same type you must activate
them on the loop in sequence. The devices will
then be displayed on the LCD display in the
chronological sequence they were activated.
•
Devices which are unique on the loop (i.e. only
one of them) are included automatically.
23
FC501 Engineering
Device Mapping Procedure
•
At the end of the auto-addressing procedure
you will be invited to enter device mapping.
•
On entering device mapping you will see a
message stating ‘Device Mapping RUNNING’
The display will also have the following
columns present; evt, time, type, add
•
The display will normally be empty at this
stage. It will only fill with events once you begin
to activate multiple devices of the same type on
the loop.
•
Activate your detectors, call points etc in
sequence. That sequence will be displayed on
the device mapping screen as event 001,
event 002 etc. with the time, type of device
and current address and loop number of the
device displayed.
24
FC501 Engineering
25
Device Mapping Procedure
•
Devices which are unique on the loop (i.e.
there are only one of them present) will be
added automatically to the list by the panel with
the title ‘unique’ in the time column.
•
The zone mapping function will automatically
allocate devices it finds on the loop(s) to the
zones shown in the table on the right. These
can be edited later if required.
•
To begin editing the device map press the zero
(0) key on the display.
•
The current (temporary) address of the device
will be displayed. To accept it simply press
enter or alternatively change the address and
press enter.
•
You can then use the scroll keys to either move
to the next device in the list or continue to the
programming options for the current device.
Device Address
1 - 16
17 – 32
33 – 48
49 – 64
65 – 80
81 -96
97 – 112
113 - 128
Allocated Zone
0001
0002
0003
0004
0005
0006
0007
0008
FC501 Engineering
Device Mapping Procedure
•
What about output devices?
•
As you cannot ‘activate’ output devices
(sounders, sounder bases etc) as you would a
detector during the device mapping process
they are displayed on the device list
automatically.
•
To enable accurate discrimination between
multiple output devices of the same type, for
identification and addressing purposes,
selecting an output device on the device map
list activates it.
•
The output device (e.g. sounder base) will be
‘active’ whilst it is selected allowing it to be
identified if necessary. You can also press the
silence/resound button to silence the selected
output device if you wish.
26
FC501 Engineering
Device Mapping Procedure
•
When you have completed all the required
addressing (and programming, if required) you
can exit device mapping by pressing the ESC
key.
•
You will see a message on the display saying
‘Are you sure you want to leave device
mapping’. Press enter to confirm that you do.
•
You may see a further message which states
‘Assignment of the final addresses RUNNING
Wait Please’
27
FC501 Engineering
Cause & Effect Programming
•
It is the specific output where the cause
and effect is configured
•
Can trigger from any of up to four zones.
•
Can trigger from any of up to three
individual devices (or channels of devices)
•
Can specify under which conditions the
specific zone(s) or specific trigger points
activate the output (Alarm, Pre-Alarm etc)
•
Alternatively you can specify that an
output operates for a number of global
conditions (Alarm, Pre-Alarm etc) present
on the panel.
During auto-enrolment all outputs are
marked as alarm from panel.
•
•
Can specify a delay for an output on an
alarm activation.
28
FC501 Engineering
Lost Installer (Level 3) Password Procedure
•
If you have lost the installer password (default:
00000) you will receive a ‘wrong password’
message on entering the installer password.
•
•
•
•
Remove link J5 on the PCB.
Press the ESC key to enter the main menu.
Select 1=Program.
You will be prompted to enter the Installer
password.
Enter the password of your choice starting with
a zero and then a further four digits (0****) and
press the enter key.
The panel will reset automatically followed by
the message ‘SYS INIT’ on the LCD display for
a brief period.
The new Installer Password is now
programmed in the panel.
Replace link J5 on the PCB.
•
•
•
•
29