introduction to the 12v190f monobloc - Accu

F R O N T
The PowerSafe® V Front Terminal range of valve regulated lead acid batteries
has been designed specifically for use in applications that demand the highest
levels of security and reliability. With proven compliance to the most rigorous
T E R M I N A L
INTRODUCTION TO
THE 12V190F
MONOBLOC
international standards, PowerSafe V batteries are recognised worldwide as a
premium solution for Telecom applications. The reputation of PowerSafe V
batteries for long service life, together with excellent high rate performance,
also makes it ideal for high integrity, high specification UPS systems.
PowerSafe V batteries deliver superior performance while occupying less
space than conventional standby power batteries. A range of compact
designs, suitable for 19", 23" and ETSI racking, provides users with the benefit
of increased energy density. With all electrical connections at the front,
installation and inspection are both quicker and easier.
The 12V190F front terminal monobloc is the latest addition to the hugely
successful EnerSys® PowerSafe V battery range. Its large capacity and
compact design enable EnerSys to satisfy customers' ever increasing
demand for superior energy density products.
Features & Benefits
12V, 190Ah monobloc (C10/1.80Vpc/20°C)
Compact design & superior energy density:
more back-up power in same space
Front terminal connections for fast and
easy installation and maintenance
Ideal for use in industry-standard power
cabinets
UL94 V-0 flame retardant case and lid
Long design life
RESERVE
POWER
Publication No: EN-VFT-190F-002 - February 2009
Construction
• Positive plates designed to prolong
•
service life and enhance corrosion
resistance
•
•
•
•
•
Separators in low resistance
microporous glass fibre. The electrolyte
is absorbed within this material,
preventing acid spills in case of
accidental damage
Flame arrestors built into each bloc for
increased operational safety
Rope handles fitted as standard for ease
of handling
Installation & Operation
• Monoblocs are designed for installation
in cabinets or on stands, close to the
point of use. A separate battery room is
not necessary
Case and lid in flame retardant ABS
material, highly resistant to shocks and
vibrations
•
Terminal with brass insert for maximum
conductivity and with high compression
grommet for long life
It is recommended that PowerSafe®
12V190F batteries are installed on their
base
•
Recommended float charge voltage:
2.280Vpc at 20°C (68°F)
2.265Vpc at 25°C (77°F)
•
•
Six months shelf life at 20°C
Self-regulating pressure relief valve
prevents ingress of atmospheric oxygen
Standards
• Tested according to international
standard IEC 60896-21 and compliant to
defined requirements of IEC 60896-22
•
Classified as “Long Life” according to
the Eurobat Guide 1999
•
Designed to meet Telcordia SR-4228
requirements
•
•
Recognised by UL (UL Standard 1989)
•
Manufactured in EnerSys® ISO 9001:2000
and ISO 14001:2004 certified production
facilities
Approved to be shipped as nonhazardous cargo in accordance with the
requirements of IMDG (International
Maritime code for Dangerous Goods)
and OICA (Organisation of International
Civil Aviation)
Reduced maintenance:
no water addition required
General Specifications
Nominal Capacity (Ah)
10 hr rate
Nominal to 1.80Vpc
Voltage (V)
@ 20°C
Number
of Cells
12V190F
6
12
190
Nominal Dimensions
8 hr rate
to 1.75Vpc
@ 77°F
Length
mm
in
190
561
Overall
Height
mm
in
Width
mm
in
22.1
125
4.9
316
12.4
kg
Typical
Weight
lbs
57.3 126.3
Short Circuit
Current (A)
Internal
Resistance
(mΩ)
Terminals
3625
3.50
M6 M
Discharge Currents (Amperes) at 20°C
Standby Time (Minutes)
Standby Time (Hours)
Voltage (V)
30
35
40
45
1
2
3
4
5
6
7
8
9
10
1.85
1.80
1.75
1.71
1.67
1.65
1.63
1.60
196.3
208.5
217.9
224.3
229.6
231.6
233.3
235.0
179.1
188.7
196.2
201.4
205.4
207.2
208.6
210.0
163.3
172.6
178.9
183.3
186.7
188.0
189.2
190.1
150.8
159.1
164.7
168.5
171.5
172.6
173.5
174.2
123.0
129.5
133.5
136.0
138.0
138.8
139.4
140.0
73.2
76.0
77.6
78.6
79.3
79.6
79.8
79.9
52.6
54.3
55.3
55.9
56.3
56.5
56.6
56.6
41.1
42.5
43.2
43.6
44.0
44.1
44.2
44.2
33.9
35.0
35.6
35.9
36.2
36.3
36.3
36.3
28.9
29.8
30.3
30.6
30.8
30.9
31.0
31.0
25.3
26.1
26.5
26.8
26.9
27.0
27.0
27.0
22.4
23.2
23.5
23.8
23.9
24.0
24.0
24.0
20.2
20.8
21.2
21.4
21.6
21.6
21.6
21.6
18.4
19.0
19.3
19.5
19.6
19.6
19.7
19.7
Standby Time (Minutes)
Standby Time (Hours)
Voltage (V)
30
35
40
45
1
2
3
4
5
6
7
8
9
10
1.85
1.80
1.75
1.71
1.67
1.65
1.63
1.60
402.6
363.9
332.8
311.7
255.7
151.2
108.3
84.7
69.7
59.9
52.3
45.7
41.9
37.3
420.8
436.3
457.2
378.8
390.0
412.7
347.4
356.5
376.6
323.0
332.4
346.8
263.6
270.2
281.4
154.6
157.4
163.7
110.5
112.2
116.8
86.3
87.6
91.2
71.0
72.0
75.1
61.4
62.1
63.9
53.7
54.3
55.7
46.6
47.3
49.4
43.0
43.5
44.4
38.0
38.6
40.4
454.6
457.8
460.5
402.8
402.8
402.8
366.4
366.4
366.4
343.3
345.1
346.5
277.6
278.8
279.8
160.4
160.9
161.2
114.1
114.3
114.5
88.9
89.1
89.3
73.1
73.2
73.4
62.6
62.7
62.8
54.7
54.8
54.9
48.0
48.1
48.2
43.8
43.9
43.9
39.2
39.3
39.4
463.3
402.8
366.4
348.0
280.7
161.4
114.7
89.4
73.4
62.8
54.9
48.2
44.0
39.4
Contact:
EnerSys
P.O. Box 14145
Reading, PA 19612-4145
USA
Tel: +1-610-208-1991
+1-800-538-3627
Fax: +1-610-372-8613
www.enersys-emea.com
EnerSys Europe
Zurich, Switzerland
EnerSys Asia
Guangdong, China
Tel: +86-755-2689 3639
EnerSys Ltd.
Rake Lane,
Clifton Junction,
Swinton, Manchester
M27 8LR, UK
Tel: +44 (0)161 794 4611
Fax: +44 (0)161 727 3809
© 2009 EnerSys. All rights reserved.
Trademarks and logos are the property of
EnerSys and its affiliates unless otherwise noted.
Publication No. EN-VFT-190F-002 - February 2009 - Subject to revisions without prior notice. E.&O.E.
Constant Power Discharge (Watts per cell) at 20°C