6.0 INFRASTRUCTURE Huldra Silver Inc. is constructing a mining

advertisement
6.0 INFRASTRUCTURE
Huldra Silver Inc. is constructing a mining camp on previously logged and developed property
identified as District Lot 1213……. The property was previously part of an eco-adventure camp
referred to as The Gak. The property was purchased by Huldra Silver Inc. from The Gak holdings
on February 24, 2011. The entire surface area of the property has been previously cleared of all
trees and only brush remains. There are a sufficient number of roads and cleared area that there
will be no additional disturbance in construction of the mining camp. This will comply with the
Ministry of Environment Order-WHA #8-083 to 8-089 for Cascade Forest District regarding
Access and Harvesting. The Gak has constructed 18 yurts of various sizes, one large garage,
one workshop, and three washroom facilities. All the structures with the exception of the
washroom facilities have either been dismantled or are in disrepair. As part of the construction all
of the remaining garbage, broken structures, and parts of buildings will be cleaned up and either
recycled or disposed of by Huldra Silver Inc.
Huldra proposes to construct a camp on the property that will include;
• Fresh Water Supply
• Permanent Camp Facilities
• Sewage Treatment
• Maintenance Complex
• Office, First Aid and Communications Complex
• Power Supply and Electrical Distribution
• Waste Management
6.1 FRESH WATER SUPPLY
A fresh water supply in the form of a drilled well will be used for the camp supply of potable
water. A well will be drilled in the immediate area south of the camp for fresh water consumption
and use. A Government Certified installer has been consulted to design the system required. A
full Water Licence Application has been submitted to the Government of British Columbia Natural
Resource Program, Kamloops office, on January 11, 2011 for this use. The well will be drilled to
proper depth to ensure adequate perk volumes for the 24 man camp.
Water Consumption Estimates
AREA
USE
VOLUME – m3/day
Camp-Dorm units
Toilets, showers, laundry
15.5 m3
Camp-Kitchen/Dinning
Kitchen operations
1.760 m3
Camp-Office/First Aid
Small laundry facility, sink.
0.57 m3
1. CAMP FACILITIES
The proposed camp is located as outlined in fig. XXXXXXX. Camp design has been assisted by a
qualified supplier of this type of facility to ensure compliance of the building code. The camp is
designed for 25 men. The opportunity to have female employees has been taken into
consideration and designed into the camp facilities. The camp will consist of a complete kitchen
and dining facility, sleeper section, attached washroom facilities, recreation rooms and separate
mud room for transition area.
Details of these facilities are as follows:
Code Requirements
Structural, BC Building Code - Part 3 (2006)
Electrical, CSA-Canadian Electrical Code - Part 1 (2006)
Plumbing, BC Building Code – Part 7 (2006)
1. KITCHEN / DINER - 24’ x 60’
Structural
Roof Design Load = 100 PSF Floor Design Load = 100 PSF
Roof
45 mil. EPDM roofing, fully adhered
2x4 upstand to junction wall only
15/32" (11.9 mm) OSB sheathing, stapled
2x10 joists at 16" on centre, tapered to 2x8, kiln dried, SPF #2 and better
R30 fibreglass batt insulation
6 mil. poly vapour barrier
1/2” Vinyl clad gypsum wall board, “Partition Systems” Smooth Castle White, c/w battens &
rosettes at 16”
Floor
3/8" (9.5 mm) OSB undersheathing, stapled
2x10 joists at 16" on centre, kiln dried, SPF #2 and better
Joist hangers throughout
Triple rim joists
R30 fibreglass batt insulation
5/8" (15.5 mm) T&G plywood subfloor, select fir, glued and stapled, tongue glued
5/16" underlayment board, ‘U-lay’ or equal, glued and stapled over subfloor
2.0 mm commercial sheet vinyl, seams welded
Walls – Exterior
8’-0 ¼” wall height
Aluminum termination bar, mill finish, fastened with screws
30-gauge horizontal steel fascia, 18" high, prefinished
30-gauge vertical steel siding, prefinished
30-gauge starter strips, prefinished
3/8" (9.5 mm) OSB sheathing, glued and stapled
2x6 studs at 16" on centre, kiln dried, SPS-3 finger joint
R20 friction fit fibreglass batt insulation
6 mil. poly vapour barrier
1/2” vinyl clad gypsum wallboard, 4x8 sheets c/w matching battens
0.090” fibreglass reinforced panels, prefinished white c/w white plastic trims over 3/8" OSB
backing (Kitchen)
Walls – Interior
8’-0 ¼” wall height
2x4 studs at 16" on centre, kiln dried, SPS-3 finger joint
1/2” vinyl clad gypsum wallboard, 4x8 sheets c/w matching battens
0.090” fibreglass reinforced panels, prefinished white c/w white plastic trims over 3/8" OSB
backing (Kitchen)
Walls – Junction
3/8" (9.5 mm) OSB sheathing, glued and stapled
2x4 studs at 16" on centre, kiln dried, SPS-3 finger joint
½” vinyl clad gypsum wallboard, 4x8 sheets c/w matching battens
0.090” fibreglass reinforced panels, prefinished white c/w white plastic trims over 3/8" OSB
backing (Kitchen)
Doors - Exterior All doors keyed alike & mastered to complex (dorm & first aid)
3’-0” x 6’-8” trailer type door
Aluminum face and insulated core, Prefinished white both sides
Panic hardware (Push bar inside, thumblatch outside) c/w cylinder lock
Chainstop
16” x 28” Fixed single Plain Laminated lite
Doors - Interior
2'-6" x 6'-8" vinyl wrapped solid core wood door with rabetted wood frame, painted 2 coats latex
(HWT /Stor.)
2'-0" x 6'-8" vinyl wrapped solid core wood door with rabetted wood frame, painted 2 coats latex
(furnace)
Passage set
Weatherstripping, threshold & sweep to HWT & furnace doors only
Door stop to furnace door only
Windows – Exterior
Rebate frame windows, Horizontal slider XO
Prefinished white vinyl frame
Clear double glazed with ½” sealed air space, Softcoat Low-E glazing
Screens, aluminum drip cap over
Mini Blinds, 1” horizontal aluminum
Mouldings
Base - 4” rubber base
Door & window liners - 1x4 light oak vinyl wrapped wood
Door & window casing - Light oak vinyl wrapped wood, 3000 profile
Exterior wall junction -30 gauge prefinished steel
Interior wall junction -1x4 wood, vinyl wrapped to match wall finish/
Ceiling junction -1x4 wood, vinyl wrapped to match ceiling
Door junction -1x5 wood, vinyl wrapped
Floor junction -Aluminum 4" wide
Roof junction -30 ga. galvanized roof cap
Millwork
Plastic laminated post-formed round underwrap counter top, “Arborite”, standard colour line
Prefinished birch plywood base cabinets, natural finish, European style
Satin Nickel wire pulls
1 No. 54” long x 12” deep hat shelf c/w 13 coat hooks under (Dining)
1 No. 96” long x 12” deep hat shelf c/w 23 coat hooks under (Dining)
1 No. 72” long x 12” deep shelf @ 20” B.F.C., open box type (over hot food table)
1 No. 72” long x 12” deep shelf @ 66” F.F.F. mounted on wall brackets(over baker’s table)
1 No. 108” long x 12” deep shelf @ 66” F.F.F. mounted on wall brackets(over Dishwashing)
1 No. 36” long x 12” deep shelf @ 66” F.F.F. mounted on wall brackets (over SS4 counter)
6 No. 36”x90” Dining table, plastic laminate over 5/8” MDF c/w T edge & folding legs (Dining)
Furnishings
Designer series signs
Mirrors, l8" x 24", eased edges
Paper towel dispensers, "Frost" F101
Soap dispensers
4 No. 5lb. ABC fire extinguisher c/w wall bracket (4 exterior doors)
1 No. 10lb. ABC fire extinguisher c/w wall bracket (Kitchen)
36 No. Chair, stacking, no arms
Stainless Steel
1 No. 84”x 42” S.S. Stainless steel canopy c/w stainless steel filters & backwall, 2100 CFM
exhaust.
1 No. 72” x 30” maple top bakers table c/w S.S. backsplash and legs
1 No. 24”x 36”x36” high S.S. counter c/w galv. Undershelf
1 No. 24”x 42”x36” high S.S. counter c/w galv. Undershelf
2 No. 24”x 84”x36” high S.S. counter c/w galv. Undershelf
1 No. 24”x 132”x36” high S.S. counter c/w galv. Undershelf
12 LF 24” S.S. Dishwasher counter c/w legs & 35” x 22” x 18” dp. double pot sink c/w 3 kW/240V
sterilizer & faucet
3 No. 12”x78” S.S. pass thru shelf
1 No. 24”x4” S.S. drip pan c/w top grate & drain
1 No. 24”x 18” S.S. utensil rack
1 No. S.S. Display shelf, 2 tier, 60” wide x 24” high x 12” dp. w/ plexi glass doors & shelf over
Kitchen Equipment
1 No. Vulcan SG4D single deck convection oven, 60,000 BTUH input,115/1/60, 9 Amps
1 No. Vulcan 1GR45M fryer c/w baskets & S.S. tank, millivolt control, 120,000 BTUH input
1 No. Hobart SR24H undercounter diswasher, 7 kW booster, 120/208-240/1/60, 37.6 Amps
1 No. Food warmer, 48” long
1 No. 5 well hot food table, c/w overshelf
1 No. Manitowoc QY-0214A undercounter ice machine c/w bin, 115/1/60, 7.8 Amps
1 No. Cambro tray & cutlery cart
1 No. True GDM-9K double door counter-top cooler, 115/1/60, 6 Amps c/w cord & plug
1 No. Vulcan 60-SS-4B-36G-P, 60” range, 4 burner, 36” griddle & 2 ovens, 230,000 BTUH input
1 No. Jetspray single juice dispenser
1 No. Silver King 5 gallon milk dispenser
1 No. T & S water station
1 No. Bunn coffee urn twin 6 gallon
2 No. Metroseal 24”x60” 3 tier shelving unit (Cooler & Freezer)
2 No. Metroseal 24”x48” 3 tier shelving unit (Cooler & Freezer)
3 No. Metroseal 24”x48” 3 tier shelving unit (Storage)
1 No. Metroseal 18”x48” 3 tier shelving unit (Storage)
1 No. Metroseal 18”x36” 3 tier shelving unit (Storage)
1 No. 11’-0” x 12’-6” approx. Walk in Cooler/Freezer, 3” pre-manufactured wall & roof panels
c/w door, condenser & light
Mechanical
Commissioning and start-up by camp supplier site subcontractor
Forced Air System:
LPG forced air furnace 70 BTUH downflow, AFUE 80%, sealed combustion, auto ignition model
permanent air filter,
Split system AC coil & condenser, 2ton
Heat/cooling wall thermostat, manual change over w/ secured enclosure
8” dia. fresh air intake duct thru wall
In floor, 4-sided metal ducts c/w 4x10 HD floor registers
24”x12” R/A grille wall mounted
Make - Up Air System
MUA LPG, indoor mounted, size 2,100 cfm, 100% outside air serving kitchen equipment hood
exhaust
Overhead, 4-sided metal ducts c/w double deflection supply grilles
Exhaust Air System:
2,100 cfm exhaust fans, kitchen equipment (2ea)
Electric Heat System:
500 watt Baseboard heater (white) w/ wall thermostat MUA room
2000 watt Baseboard heater (white) w/ built-in thermostat
Plumbing
Site services by qualified contractor
Piping insulation and heat trace by camp supplier site subcontractor
All waste & drainage drops stub out at underside of floor
Waste manifolding supplied & site installed by qualified contractor
Water supply manifolding supplied and site installed by camp supplier site subcontractor
PRV, if required to be supplied and site installed by qualified contractor
Water supply lines to be ‘PEX’, concealed
Flexible, reinforced inter-module water connectors
Drain, waste and vent lines to be ABS, exposed
Galvanized metal condensation pan under hot water tank
Wall hung basin
Faucet, 4" lever handle, metal stopper drain
LPG water heater, 40 US Gallon, 35,000 BTUH, LPG /w thermal expansion relief valve
Floor drain 3” dia., as required, trap & primer by camp supplier site subcontractor
DWV & water connections to kitchen equipment
Electrical
Power Distribution
From the diesel generator supplied power source, a supplied main distribution station to supply
120/208v
3ph power to 3 distribution panels; 1 to dorm wing, 1 to the Kitchen/Diner complex, 1 to the First
aid
Should transformers be required to reduce the distribution amperage to each of the locations
noted above, the transformers shall be exterior pad mounted type supplied and installed by a
qualified contractor
Sub feeders from Main Distribution to the KD, Rec, Entry Mudroom and each of the Dorms to be
supplied & installed by qualified Electrical Contractor
120 / 208 Volt triple-phase service
120 / 208 Volt main panel, 200 Amp “Square-D” or equal, Nipple thru wall
Push-in centre enclosures and circuit breakers
Hard wire intermodule connections Lumex wiring
Surface mounted, 2-tube fluorescent fixtures c/w warm-white T-8 lamps
& electronic ballast
Vapor proof lights under kitchen canopy, rough in only, lights by hood supplier
Exterior wallpack light, 70 Watt High pressure sodium with photocell
Standard switches and duplex receptacles, white
3 way switches, white
GFI receptacles beside sinks
Underfloor heat trace receptacles
Heat trace to refrigeration equipment condensate drains
Weatherproof exterior receptacles
Exhaust fans 90CFM
Electrical supply & low voltage wiring to HVAC systems
Electric heat
Kitchen equipment connections
Range hood / fan/make-up air / fresh air damper connections
Illuminated exit signs & Emergency lighting c/w battery pack
2. 25 PERSON DORMITORY ( up to 8 trailer units)
Structural
Roof Design load = 4.2 kPa (100 PSF) Floor Design load = 2.4 kPa (50 PSF)
Roof
45 mil. EPDM roofing, fully adhered
(2) 2x4 Upstand to Corridor side of module only
2x6 Raised roof curb area for A/C Condenser, EPDM over c/w galv. Metal cap
15/32” (11.9 mm) OSB roof sheathing, stapled
2x10 joists at 16" on centre, tapered to 2x8, kiln dried, SPF #2 and better
Provide blocking for interior partitions to joists (2x on flat w/ blocking between @ 32” o.c.)
Single rim joists (Avoid joint laps at Corridor locations)
R-28 fibreglass batt insulation
6 mil. poly vapour barrier
½” type-x vinyl clad gyproc, 4’ x 12’ sheets, screwed c/w “snap-caps” at 16” on center both ways,
20 FSR (U.N.O.)
5/8” type-x vinyl clad gyproc, 4’ x 12’ sheets, screwed c/w “snap-caps” at 16” on center both
ways, 20 FSR (Furnace, Service & Laundry)
Floor
3/8” spruce plywood undersheathing, stapled, painted 1 coat exterior paint
2x10 joists at 16" on centre kiln dried, SPF #2 and better /w tie-down to skids and reinforced to
both sides at heat notch with 3x6 nail plates
Double rim joists at ends, clamped to outside skids
Triple rim joists at sides
Simpson hangers, throughout
R-28 fibreglass batt insulation
2x6 at 16" o.c. on 2x4 on flat at 16” oc raised floor framing (Washrooms only)
5/8" (15.5 mm) T&G plywood subfloor, standard fir, glued and stapled, tongue glued
5/16” plywood underlayment board, glued and stapled over sub floor
2.0 mm sheet vinyl, seams welded
Walls – Exterior - Wall height 8'-0 1/4"
Termination metal bar, screwed (no vinyl insert)
Standard profile siding 30 gauge prefinished steel, stock colors, c/w 18” Fascia, Starter Strip, full
height siding, bottom trim, corner trims
3/8” OSB sheathing, glued and stapled
2x6 studs at 16" on centre, kiln dried, SPF stud grade, solids, prenotched w/ 2 notches evenly
spaced for let in horizontal ribbon, 2 rows 1x3 for gluing VC Gypsum field
Single top plates
R-20 friction fit fibreglass batt insulation
6 mil. poly vapour barrier
½” type-x vinyl clad gypsum wallboard, 20 FSR (U.N.O.)
5/8” type-x vinyl clad gypsum, 20 FSR (Service & Laundry)
5/8” type-x vinyl clad GWB w/ metal inside corners, 20 FSR (Furnace)
0.090” fiberglass reinforced panels over ½” plain gypsum wallboard, white (Washcar) (to walls
behind public bathroom sinks, urinals, above showers & 48” high around mop sink & from floor to
bottom of coat hook board in mudroom)
Walls – Junction walls
3/8” OSB sheathing, glued and stapled
2x4 studs at 16" on centre, kiln dried, SPF stud grade, solids
Single top plates
R-12 friction fit fibreglass batt insulation
½” type-x vinyl clad gypsum wallboard, 20 FSR (U.N.O.)
5/8” type-x vinyl clad gypsum wallboard, 20 FSR (Service & Laundry)
0.090” fiberglass reinforced panels over ½” plain gypsum wallboard, white (Washcar) (to walls
behind public bathroom sinks, urinals, above showers & 48” high around mop sink) & from floor to
bottom of coat hook board in mudroom)
Walls – Corridor
Standard profile siding 30 gauge prefinished steel, stock colors, c/w Upper starter strip, full height
siding, bottom trim & corner trims
½” type-x gypsum wallboard, fire taped
2x6 studs at 16" on centre, kiln dried, SPF stud grade, solids, Single top plates
R-20 friction fit fibreglass batt insulation
½” type-x vinyl clad gypsum wallboard, 20 FSR (U.N.O.)
5/8” type-x vinyl clad gypsum wallboard, 20 FSR (Service & Laundry)
5/8” type-x vinyl clad GWB w/ metal inside corners, 20 FSR (Furnace)
0.090” fiberglass reinforced panels over ½” plain gypsum wallboard, white (Washcar) (to walls
behind public bathroom sinks, urinals, above showers & 48” high around mop sink & from floor to
bottom of coat hook board in mudroom)
Continuous 2”x3”x3/16” thick ledger at bottom of module for corridor floor panel 2x2x8’, 1/4” steel
angle lag screwed to walls for attachment of corridor wall panels
Walls – Interior
½” type-x vinyl clad gypsum wallboard ,4x8 sheets, 20 FSR (U.N.O.)
5/8” type-x vinyl clad gypsum wallboard, 4x8 sheets, 20 FSR (Service, Laundry, Module 3
Hallways)
5/8” type-x vinyl clad gypsum wallboard c/w metal inside corners, 4x8 sheets, 20 FSR (Furnace)
0.090” fiberglass reinforced panels over ½” plain gypsum wallboard, white (Washcar) (to walls
behind public bathroom sinks, urinals, above showers & 48” high around mop sink)
7/16” sound board to bedroom partitions, 4x8 sheets, one side only
2x4 studs at 16" on centre, kiln dried, SPS-3 finger joint, Single top plates (U.N.O.)
R-12 friction fit fibreglass batt insulation (Bedrooms)
Corridor Panels - To suit 48” wide corridor
Roof Panels
45 mil. EPDM roofing, 7’-0” wide (Loose laid at site over panels)
Termination Bar (no insert) c/w screws provided. Loose for site installation.
3/8” pressure treated plywood sheathing, glued and stapled
2x4 Cross joists at 16" on centre, SPF #2 and better, pressure treated
2x6 Rim joists, SPF #2 and better, pressure treated
R-12 (2”) polyisocyanurate insulation
3/8” OSB sheathing
30 gauge steel ceiling, prefinished c/w colour match screws
Floor Panels
3/8” pressure treated plywood undersheathing, glued and stapled
2x4 Cross joists at 16" on centre, SPF #2 and better, pressure treated
2x4 Rim joists, SPF #2 and better, pressure treated
R-12 (2”) polyisocyanurate insulation
5/8" (15.5 mm) plywood subfloor, standard fir, glued and stapled
Underlay 4’-0” wide (Loose laid at site over panels)
Rubber runner 4’-0” wide (Loose laid at site over panels)
End Wall Panels
One at each end of dorm complex
30 gauge steel siding, prefinished, (Interior side of wall)
3/8” spruce plywood sheathing, glued and stapled
2x4 studs at 16" on centre, kiln dried, SPF stud grade, solids
Single top plates
R-12 (2”) polyisocyanurate insulation
3/8” spruce plywood sheathing, glued and stapled
30 gauge steel fascia, prefinished x 18” high at high point, (Ext. Side of wall)
Upper starter strip, prefinished
30 gauge steel siding (no split siding), prefinished
Exterior door
Smoke Wall Panels
One required
30 gauge steel siding (no fascia or split siding), prefinished
½” type-x gypsum wall board, fire taped
3/8” spruce plywood sheathing, glued and stapled
2x4 studs at 16" on centre, kiln dried, SPF stud grade, solids
Single top plates
3/8” spruce plywood sheathing, glued and stapled
½” type-x gypsum wall board, fire taped
30 gauge steel siding (no fascia), prefinished
Smoke Door
Doors - Exterior
Exterior doors prefinished (except Smoke Door painted to match interior doors)
1 No. 3'-0" x 6' -8" trailer type door (Washcar Exit)
Aluminum face, solid core, Weatherstripping, Mill finish aluminum frame
Heavy duty chainstop, vinyl wrapped
Exit Only Panic hardware (push bar inside)
Inside “D” handle door pull
16” x 28” vertical slider window c/w screens
Aluminum eyebrow over
2 No. 3'-0" x 6' -8" trailer type door (Main Entries – in Corridor End Wall Panel)
Aluminum face, solid core, Weatherstripping, Mill finish aluminum frame 16” x 28” vertical slider
window c/w screens
Exit/Entry Panic hardware (thumblatch outside, push bar inside)
Inside “D” handle door pull, Closer, Aluminum eyebrows
1 No. 3’-0” x 6'-8" Hollow non-insulated commercial metal door, 20 min fire rated (Smoke Door –
Corridor Wall Panel)
Knock-down, expandable steel frame, painted to match door, passage set, fire rated, closer
Weatherstripping
Electro-magnetic hold open device tied to fire alarm
Doors - Interior
36 No. 2'-8" x 6'-8" Residential insulated metal door (Bedrooms)
20 min. rated c/w ULC label
Door bottom/sweep white, Weatherstripping, threshold c/w bumper stop, 1 ½ pair hinges
Door stop & Door hold open, Nameplate holder
Knock-down, expandable steel frame, painted to match door, screws to be exposed, lockset
Closer, Aluminum eyebrow over
8 No. 2'-0" x 6'-8" Residential insulated metal door (Furnaces)
45 min. rated c/w ULC label
Door bottom/sweep white, threshold c/w bumper stop
Knock-down, expandable steel frame, painted to match door, screws to be exposed, lockset
Closer, Aluminum eyebrow over, Sign, “Furnace”
1 No. 2'-6" x 6'-8"residential insulated metal door (Public washroom)
20 min rated c/w ULC label
Door bottom/sweep white, threshold c/w bumper stop, Weatherstripping, Door stop
Knock-down, expandable steel frame, painted to match door, screws to be exposed deadbolt, fire
rated
Door pull, both sides, closer, Aluminum Eyebrow
Aluminum kickplate to one side of door
9 No. 2’-0” x 6'-8" solid core wood paint grade door (Private washrooms)
20 min rated c/w ULC label
Knock-down, expandable steel frame, painted to match door, screws to be exposed privacy set,
fire rated
Closer, Aluminum kickplate to one side of door, Door stop
2 No. 2'-8" x 6'-8" Residential insulated metal door (Service & HWT)
45 min. rated c/w ULC label
Door bottom/sweep white, Weatherstripping, aluminum threshold c/w bumper stop
Knock-down, expandable steel frame, painted to match door, screws to be exposed lockset, fire
rated
Closer, Aluminum eyebrow, Sign, “Service”
1 No. 3'-0" x 6'-8" Residential insulated metal door (Laundry)
45 min. rated c/w ULC label
Door bottom/sweep white, Weatherstripping, aluminum threshold c/w bumper stop
Knock-down, expandable steel frame, painted to match door, screws to be exposed lockset, fire
rated
Closer, Aluminum eyebrow, Sign, “Laundry”
1 No. 2'-0" x 6'-8" Residential insulated metal door (Storage)
45 min. rated c/w ULC label
Door bottom/sweep white, Weatherstripping, threshold c/w bumper stop
Knock-down, expandable steel frame, painted to match door, screws to be exposed lockset, fire
rated
Closer, Aluminum eyebrow, Sign, “Storage”
4 No. 3'-0" x 6'-8" Residential insulated metal door (Mudroom, Rec, Games)
20 min. rated c/w ULC label
Door bottom/sweep white, Weatherstripping, threshold c/w bumper stop, 1 ½ pair hinges
Door stop & Door hold open,
Knock-down, expandable steel frame, painted to match door, screws to be exposed lockset
Closer, Aluminum eyebrow over
Windows (Top of Windows at 82” From Finished Floor uno)
Rebate frame windows, Horizontal slider XO
Prefinished white or beige vinyl frame
Clear double glazed with ½” sealed air space Softcoat Low-E glazing
Aluminum drip cap over Screens
Mini Blinds, 1” horizontal aluminum
Mouldings
Base - 4” Rubber base
Casing - Vinyl wrapped
Window Liner - Primed white wood, integral with window
Top wall trim - Batten
Battens - Vinyl wrapped wood to match wall finish, 1 ½”
Millwork
Plastic laminated top, round underwrap post form on particle board,
24” deep (no backsplash) to desks, 22 ½” deep (Vanity tops)
3/4”, birch plywood base cabinets, European style construction, stained “natural” finish
Satin Nickel wire pulls
90European hinges
Bedrooms –per bedroom
39” x 80” single captains bed with two drawers under each with hasp for lock
36” x 24” single desk with alarm clock shelf
36” x 24” x 72” double closet, c/w shelves, coat rod and 1 lockable drawer c/w 2 No. Keys, doors
30”x5” birch plywood mounting surface for towel bar, toothbrush/tumbler holder
Heavy duty coat hooks mounted on 3/4” birch plywood
Washcar
4-tier plywood shelves in storage
2 No. open box shelf, bottom at 66” F.F.F. (over L/T & Mop)
1 No. Open under vanity 84” long x 32" high (Public W/R)
1 No. 4” wide shaving shelf x 78” long (Public W/R)
9 No. Open under vanity 28” long x 32" high
9 No. 4” wide shaving shelf x 28” long
9 No. 3 Heavy duty coat hooks mounted on 3/4” birch plywood
Mudroom
90 LF Prefinished birch coat hook board, hooks at 24” o.c., c/w hat shelf over
36 LF. Bench, clear S4S Fir, w/ metal legs, bolted to floor
Furnishings
Rec Room & Games Room
Furnishings to include TV, computer and card table
3 No. Recessed Fire Extinguisher Cabinet, 9”x24”x6” (Mount at 48” F.F.F. to top)
Non-adjustable front w/ flat trim, Full glass door, 6mm Georgian wired glass c/w
10lbs ‘ABC’ type fire extinguisher, Painted red
3 No. Fire Alarm Pull Station Sign, “In Case of Fire Phone _______ ”
Bedrooms-Per bedroom
39” x 80” single bed mattress
Fabric padded stacking chair less arms
Towel bar, 18”
Toothbrush / tumbler holder
Soap dish
Non slip throw rug, min. 24”x36”
Metal waste basket
Mirrored medicine cabinet, with top at 74” F.F.F.
Public Washroom
1 No. Paper towel dispenser, top at 54” f.f.f.
2 No. Soap dispenser
1 No. Toilet paper holder
3 No. Mirror, 18" x 24" erassed edges (bottom @ 50” F.F.F.)
1 No. Prefinished metal toilet partitions
2 No. Prefinished 24” urinal toilet partitions
Private Washrooms-Per washroom
Paper towel dispenser, top at 54” f.f.f.
Soap dispenser
Toilet paper holder
Mirror, 18" x 24" erassed edges (Bottom @ 50” F.F.F.)
Plastic shower curtain c/w metal rod, minimum 60” long
Rubber multi-nib shower mat, 24”x32”,black
Laundry
3 No. 3.1 cuft front loader washer & 5.7 cuft dryer, c/w stacking kit
2 No. commercial Washer
2 No. commercial Dryer
Plumbing
Pressurized domestic water to be provided to each water connection point @ 75 PSI (Max)
“Pex” polyethylene water lines, exposed in w/r & laundry only (Lines 1 1/4” & over in dia. to be
copper)
Copper main water line drop thru wall (to one drop per module)
Drain, waste & vent lines to be ABS, semi-exposed.
Waste to terminate to 3 No. Drops with FIP connector
All waterlines to have low point drains
All plumbing to be graded for drain
Galvanized metal condensation pan under hot water tank
Washer Rough-Ins
Floor drain in furnace room for furnace condensate, to be connected on site by purchaser
1 No. Fire hose cabinet, Single valve, 30” x 30” x 6” deep, 100’-0” + 50’-0” hoses coupled
together, glass door, 1 ½” inlet
10 No. Water Closet
Elongated 1.6 gpf bowl
Elongated open front seat
With 1.6 gpf tank
2 No. Urinal, metering valve with vacuum breaker
12 No. Lavatory basin
Faucet, 4" lever handle, 1.5 GPM aerator
Drain, metal stopper drain
9 No. Fibreglass shower 32" x 32"
Faucet, valve
Tub cove molding
2 No. Single fibreglass laundry tub c/w stand, faucet, 4” centers
2 No. Mop sink, mop sink faucet
3 No. Propane (LPG) Hot water tank,71 gallons U.S
120,000 BTU LPG, 116 gal/hr recovery rate at 100 deg. Fahrenheit temp. rise,
120 VAC for Motorized flue damper (0.7 FLA lamp)
QC Mechanical
Commissioning and start-up by building supplier Site subcontractor
Electrical supply to HVAC unit by building supplier electrical subcontractor
Electrical connections to furnace by building supplier electrical subcontractor
Electrical connections to roof mounted A/C Condenser by purchaser
Low voltage wiring for thermostat by building supplier electrical subcontractor
Low voltage connections to thermostat by building supplier electrical subcontractor
LPG to run on roof c/w Hose (type 1 connections) (Sleepers)
Propane (LPG) lines to run on roof c/w hose (type 1) connections & Gas Reg. (Washcar)
1 No. LPG forced air furnace 90 BTUH downflow, AFUE 80%, sealed combustion, auto ignition
model permanent air filter (Washcar)
7 No. LPG forced air furnace 70 BTUH downflow, AFUE 80%, sealed combustion, auto ignition
model permanent air filter, (Sleepers)
7 No. split system air conditioning, 2 Ton (24,000 BTU/Hr.) with roof mounted condenser,
Heat / cool, automatic change over wall thermostat
5”Fresh air intake c/w birdscreen, thru floor at furnace alcove (Furnace – Typ. u.n.o.)
7”Combustion air pot w/insulated duct to wall cap (HWT – Typ. u.n.o.)
Four sided metal supply air duct in floor, c/w 10x4 floor registers
Four sided metal return air duct in floor, c/w 10x4 floor registers u.n.o.
Four sided metal supply air duct in floor thru wall c/w wall grille for supply air to Corridor
Return air floor openings in furnace alcoves w/ 6”x14”x 1/8” exp. Metal mesh covers painted black
Fresh Air thru floor of furnace alcove
Forced air to raised floor cavities (Washrooms)
500W Baseboard heaters
Electrical
120/208 Volt triple phase service
Main Power supply to Module 3 by qualified Electrical Contractor
Grounding system by qualified Electrical Contractor
Power supply from Module 3 to sleepers by building supplier
Push-in centre enclosures, push-in circuit breakers
Lumex wiring
Module 3 (Washcar)
(1) 6”Dia. ABS nipple thru wall only, 208 Volt main power feed cord n.i.c. (Service Room)
120/208 Volt main distribution panel, “F.P.E.”, 200 amp, 42 ccts.
sub-feeders to Sleepers, hardwire both ends, run sleepers on ground under corridor
200 Amp main breaker
Meter base by qualified Electrical Contractor
Sleepers
Under floor power connection
7 No. 120/208 Volt, 40 A. single phase subpanels “F.P.E.”
Cabtire sub-feeders from Washcar, S.O. type, c/w hardwire connection at both ends to be
loose laid under corridor to each module (Site installed)
Exterior incandescent Cooper 1B-P-100 (Side Exit)
Exterior HPS Cooper HPFZ158 Lumark Zpac, 150Watt c/w photocell (Corridor entrances)
Fluorescents 2 tube, T-8 3500K lamps, electronic ballast (Typ. U.N.O.)
(Lights in hallway to be on at all times with Corridor lights)
Corridor light fixture surface mounted marine light c/w (2) PL13 incandescent lamps
Ceiling mounted incandescent fixtures c/w 60w lamp (Washrooms)
Bunk type light over each bed
Bathlight, 3 lamp incandescent c/w 40w lamp white (Mounted @ 78” F.F.F. above vanity)
Illuminated exit sign, wall mounted
Emergency lighting c/w 36 Watt battery pack
Emergency remote double head
Toggle switches, white
Furnace switches, white
Duplex receptacles, white
Separate Circuit receptacles, white for stacking washer/dryer @ 36” F.F.F.
220 volt receptacles for stacking washer/dryer @ 36” F.F.F.
Waterproof receptacles for heat trace, beside sewage outlet
GFI duplex receptacles
Connection for hot water tank flue damper (See Plumbing)
Exhaust fans 70 CFM (Wall mounted – Public Washroom)
Exhaust fans 50 CFM (Ceiling mounted & wall mounted)
Exhaust fans 50 CFM (Mudroom)(wall mounted)
500 watt Baseboard heater
1000 watt Baseboard heater (Mechanical Room)
Built in thermostat (BB heater) (Mechanical Room)
Built-in thermorstats (BB heater) (Mudroom)
Line thermostats (BB heater)
1500 watt Wall insert fan heater, with built-in thermostat c/w hinged cover for transport
BGI S2H-8 splitters (In furnace enclosure, opposite side of gas pipe)
TV outlet c/w standard coaxial cable, mudring, single gang faceplate & male coaxial cable
connector both ends, provide 3’ loose cable in each bedroom and connect opposite end to splitter
in each furnace enclosure
Internet outlet c/w standard Cat5E cable, mudring, single gang faceplate & male Cat5E cable
connector both ends, provide 3’ loose cable in each bedroom and 3’ loose in furnace enclosure
3/4” Dia. Conduit from furnace room thru wall to exterior complex wall (for TV main signal)
3/4” Dia. Conduit from furnace room thru wall to exterior complex wall (Internet main signal)
Fire Alarm
Smoke detector, wall mount (Corridors)
Heat detector, (Laundry)
Heat detector, (furnaces)
Carbon Monoxide Detector, (furnace)
Smoke Detector (furnace)
110 Volt smoke alarm, (Bedrooms, U.N.O.)
Smoke alarm/Carbon Monoxide Detector (Bedrooms beside furnace)
Manual pull station
Fire alarm horn/strobe
Fire alarm door hold open device for Corridor smoke door
Fire alarm panel w/ relay & 24v coil for smoke door hold open device and provision for furnace
shut down
Wiring & low voltage wiring to HVAC systems
Furnace thermostat
Electric HWT
Fire alarm interconnecting cords c/w quick connect plugs
2. SEWAGE TREATMENT
A self-contained sewage treatment processing system will be constructed on site. This system
has been designed by a local registered onsite Wastewater Practioner, licensed and insured
(NAME). The flow rates used for design and system schematics are attached (Please refer to
figure XXXXXXXX) The system will be underground and include grease interceptor, course
aeration, mixing tank, secondary treatment and then pressured effluent dispersed into a
disbursement field. Final dispersal field is assumed to be 800 lineal feet of trench however final
design is dependent on actual soil tests on site this spring. All work will be in conjunction with
Ministry of Health regulations required for this type of sewage treatment.
3. MAINTENANCE COMPLEX
A central maintenance complex would be constructed to provide shops for maintenance and
repairing of surface and underground equipment, light vehicle repair and tire repair facilities. This
structure will be engineered to facilitate the extreme shift of weather from season to season in this
area. Included in this complex would be storage space for spare parts and consumables. Power
for this building would be pulled overhead from the camp generator located in close proximity,
across the road.
Details of this facility are as follows:
Code Requirements
Structural, BC Building Code - Part 3 (2006)
Electrical, CSA-Canadian Electrical Code - Part 1 (2006)
Plumbing, BC Building Code – Part 7 (2006)
Structural
Roof Design Load = 100 PSF Floor Design = Concrete Slab
Roof
Pre-Engineered roof designed by building supplier
Floor
Concrete slab
Walls
Pre-Engineered walls sitting on concrete blocks to support added side load from snow pack
Doors – Exterior
Shop Door:
Pre manufactured 12’ x 14’ overhead door to accommodate large equipment
Man Doors:
3’-0” x 6’-8” exterior type door
Aluminum face and insulated core, Prefinished white both sides
Panic hardware (Push bar inside, thumblatch outside) , c/w cylinder lock
Chainstop
4. OFFICE / FIRST AID / COMMUNICATIONS COMPLEX
A central office complex would be located within the area of the camp. The office would consist of
a 60 foot trailer and include a meeting area and offices. The fully equipped First Aid station would
be located in the office complex with a dividing wall and separate entrance. A communications
network will be established using the most modern technology available. This would utilize
satellite technology and wireless communication for voice, fax, internet and PC network traffic to
ensure 24 hr communications to all points of the mine property and surrounding area. The
communications infrastructure would consist of satellite link, telephone private branch exchange
system, wireless internet, desktop and laptop computers, copper and fibre cable and site VHF
radio system. The site VHF radio system would also be working in conjunction with all Tolko
vehicle traffic in the area to ensure road safety. A backup power source, separate from the camp
power, would ensure 24 hour contact and communications.
Details of this facility are as follows:
Code Requirements
Structural, BC Building Code - Part 3 (2006)
Electrical, CSA-Canadian Electrical Code - Part 1 (2006)
Plumbing, BC Building Code – Part 7 (2006)
Structural
Roof Design Load = 100 PSF Floor Design Load = 100 PSF
Roof
45 mil. EPDM roofing, fully adhered
2x4 upstand to junction wall only
15/32" (11.9 mm) OSB sheathing, stapled
2x10 joists at 16" on centre, tapered to 2x8, kiln dried, SPF #2 and better
R30 fibreglass batt insulation
6 mil. poly vapour barrier
1/2” Vinyl clad gypsum wall board, c/w battens & rosettes at 16”
Floor
3/8" (9.5 mm) OSB undersheathing, stapled
2x10 joists at 16" on centre, kiln dried, SPF #2 and better
Joist hangers throughout
Triple rim joists
R30 fibreglass batt insulation
5/8" (15.5 mm) T&G plywood subfloor, select fir, glued and stapled, tongue glued 12” x 12” x 1/8”
vinyl composite tile
Walls – Exterior - 8’-0 ¼” wall height
Aluminum termination bar, mill finish, fastened with screws
30-gauge horizontal steel fascia, 18" high, prefinished
30-gauge vertical steel siding, prefinished
30-gauge starter strips, prefinished
3/8" (9.5 mm) OSB sheathing, glued and stapled
2x6 studs at 16" on centre, kiln dried, SPS-3 finger joint
R20 friction fit fibreglass batt insulation
1/2” vinyl clad gypsum wallboard, 4x8 sheets c/w matching battens
Walls – Interior
1/2” vinyl clad gypsum wallboard, 4x8 sheets c/w matching battens
2x4 studs at 16" on centre, kiln dried, SPS-3 finger joint
1/2” vinyl clad gypsum wallboard, 4x8 sheets c/w matching battens
Doors - Exterior All doors keyed alike & mastered to complex (dorm & Kitchen)
3’-0” x 6’-8” trailer type door
Aluminum face and insulated core, Prefinished white both sides
Panic hardware (Push bar inside, thumblatch outside) , c/w cylinder lock
Chainstop
16” x 28” Fixed single Plain Laminated lite
Doors - Interior
2'-8" x 6'-8" vinyl wrapped solid core wood door with rabetted wood frame, painted 2 coats latex
(Typ.)
“Tell” Lever handle passage set (Typ)
“Tell” Lever handle Privacy set (Washroom only)
“Tell” dead bolt (Office, Storage & First aid rm)
Door stop
Windows – Exterior
Rebate frame windows, Horizontal slider XO
Prefinished white vinyl frame
Clear double glazed with ½” sealed air space, Softcoat Low-E glazing
Screens, aluminum drip cap over Mini Blinds, 1” horizontal aluminum
Mouldings
Base - 4” rubber base
Door & window liners - 1x4 light oak vinyl wrapped wood
Door & window casing - Light oak vinyl wrapped wood, 3000 profile
Exterior wall junction -30 gauge prefinished steel
Interior wall junction -1x4 wood, vinyl wrapped to match wall finish/
Ceiling junction -1x4 wood, vinyl wrapped to match ceiling
Door junction -1x5 wood, vinyl wrapped
Floor junction –Aluminum, 4" wide
Roof junction -30 ga. galvanized roof cap
Millwork
Plastic laminated post-formed round underwrap counter top
Prefinished birch plywood base cabinets, natural finish, European style
Satin Nickel wire pulls
3 No. 24” long coat hook board c/w 3 hooks
1 No. 66” long x 12” deep upper cabinet, open box, no doors
1 No. 66” long Kitchen counter & cabinet, doors & drawers
1 No. Standard First Aid Bed 80”x 38”
Furnishings
Designer series signs
5lb. ABC fire extinguisher c/w wall bracket (@ 2 exterior doors)
Steel A/C Bracket
Paper towel dispensers
Soap dispensers
7’-0” high x 16’-0” canvas Curtain suspended from ceiling
c/w ceiling mounted I-Beam track & hardware
36” x 78” mattress c/w staph check cover
Mechanical
Commissioning and start-up by trailer supplier site subcontractor
Forced Air System:
LPG forced air furnace 70 BTUH downflow, AFUE 80%, sealed combustion, auto ignition model
permanent air filter,
Split system AC coil & condenser, 2ton
Heat/cooling wall thermostat, manual change over w/ secured enclosure
8” dia. fresh air intake duct thru wall
In floor, 4-sided metal ducts c/w 4x10 HD floor registers
24”x12” R/A grille wall mounted
Undercut interior doors
Electric Heat System:
500 watt Baseboard heater w/ built in thermostat (4 Total)
Plumbing
Site services by qualified contractor
Piping insulation and heat trace by trailer supplier site subcontractor
All waste & drainage drops stub out at underside of floor only
Waste manifolding supplied & site installed by qualified contractor
Water supply manifolding supplied and site installed by trailer supplier site subcontractor
PRV, if required to be supplied and site installed by qualified contractor
Water supply lines to be ‘PEX’, concealed
Drain, waste and vent lines to be ABS, exposed
Galvanized metal condensation pan under hot water tank
Stainless steel sink
Single Faucet, single lever, 8" centre
Electric water heater, 6 US Gallon, 1,500 watts electric, 120 Volt, single phase, hard wire type
c/w thermal expansion relief valve
Electrical
Power distribution from the diesel generator supplied power source, a qualified electrical
contractor supplied main distribution station to supply 120/208v
3ph power to 3 distribution panels; 1 to dorm wing, 1 to the Kitchen/Diner complex, 1 to the First
aid
Should transformers be required to reduce the distribution amperage to each of the locations
noted above, the transformers shall be exterior pad mounted type supplied and installed by a
qualified electrical contractor
Sub feeders from Main Distribution to the KD, Rec, Entry Mudroom and each of the Dorms to be
supplied & installed by contractor
120 / 208 Volt triple-phase service
120 / 208 Volt main panel, 40 Amp
Push-in centre enclosures and circuit breakers
Hard wire intermodule connections Lumex wiring
Surface mounted, 2-tube fluorescent fixtures c/w warm-white T-8 lamps & electronic ballast
Exterior wallpack light, 70 Watt High pressure sodium with photocell
Standard switches and duplex receptacles, white
GFI receptacles beside sinks
Underfloor heat trace receptacle
Weatherproof exterior receptacles
Electrical supply & low voltage wiring to HVAC systems
Electric heat
Illuminated exit signs & Emergency lighting c/w battery pack
REGULATIONS
5. POWER SUPPLY AND ELECTRICAL DISTRIBUTION
Electrical power for the Treasure Mountain Mine property will be obtained from two new fuel
efficient diesel generators. The generators will be rated at 250 kW each and be self-contained
including fuel storage and fuel containment. Each generator will also have its own portable
building which will house distribution panels for use in the camp and the mine. The generators will
be located strategically in the camp to minimize noise and at the top of the mountain to service
the mine requirements. Distribution lines and exact location are indicated on figure
XXXXXXXXXXX.
The camp generator will be located near the shop facility to accommodate service to it. The
camp distribution wires will be overhead from the power distribution unit, located near the
generator, to the kitchen/dining building. From there, distribution will continue overhead to the
sleeping dorm including the mud room and recreation facilities. Overhead power will also be
supplied to the mine office, first aid facility. Site lighting will be attached to power poles to
adequately illuminate the camp.
The power requirements for the 30 man camp would include the added demand from site
lighting, air conditioning and heat tracing for the water works, the self-contained generator of 250
kW will be used to ensure adequate power during peak periods. The generator would be fully
contained and come with double walled fuel storage with spill pans to manage risk of the of fuel
or oil leakage. Environmental spill kits will be on hand at the generator stations.
Table insert with consumption details.