ATE-100 RVDT/LVDT Manual 2014-02-16 page 1 of 16 Actuation Test Equipment ATE-100 CFM56-3 RVDT Manual Actuation Test Equipment 3393 Eddie Road Winnebago, IL 61088-8736 Ph# 815.335.1143 Email: DudleyDevi@Aol.Com February 18, 2015 Rev 1. Figure 1 ATE-100 19" Rack Mount ATE-100 RVDT/LVDT Manual 2014-02-16 page 2 of 16 TABLE OF CONTENTES Topic Calibration Cycle - 3 Overview of Calibration Procedures -3 Calibration Tools – 4 RVDT Module – 5 Feature Identification -5 Controls and Indicators – 6 Datel Meter - 6 MGain - 6 RVDT VAC Pk Primary Excitation SetPoint - 6 Coil Select Primary/Secondary – 6 Primary Resistance Test Selector Switch – 6 Secondary Resistance Test Selector Switch – 6 Secondary Phase Indicator – 6 PLA RVDT Circuit Board Supply – 7 PLA RVDT Calibration - 7 AC Peak Detector Balance Adjustment – 7 Calibrate Primary Meter Indication – 8 Sweep, Measure and Record Calibration of Secondary Circuit – 8 Figures Cover Picture – ATE-100 19” Rack mount -1 Fig 1 – Signal Breakout block - 4 Fig 2 – ATE-100 RVDT Module Faceplate – 5 Fig 3 – Meter Balance Calibration Test Cable 7 Fig 4 – PC Board Silkscreen Artwork – 9 Fig 5 – Electronic Schematic of RVDT5 PC Board – 10 Table 1 – Parts list from PCB Schematic Capture Tool ATE-100 RVDT/LVDT Manual 2014-02-16 page 3 of 16 Calibration Cycle Each time the test box is calibrated, note and record the change in the electrical performance of the circuits. This data will allow determination of appropriate calibration cycles. Overview of Calibration Procedures Start by measuring and recording Ohms from power cord ground prong to the test kit chassis. Energize the test kit and measure the +25, +15 and +5 volt power supplies on the RVDT/LVDT PC Board. Measure and record AC RMS output excitation to RVDT amplitude adjustment range, total harmonic distortion (optional) and accuracy of metering circuit at three points. Measure and record AC RMS and meter indication for Secondary RVDT signal voltage at 3 points. Verify Secondary Phase LEDs change state at 0 deg PLA. Measure and record Coil Resistance test 1mA current output. Measure and record the 20M Ohm Insulation Resistance test threshold. ATE-100 RVDT/LVDT Manual 2014-02-16 page 4 of 16 Calibration tools Two resistor sets measured at 19.5M and 20M Ohms. Use 1/4W 1% metal film resistors. Connect them from the connector pin to ground as a go/no-go determination of the Insulation Resistance test calibration. Adjust Resistance Threshold trimpot to get Pass LED on at 20M Ohms and Fail LED on at 19.5M Ohms. A Small “tweaker” screwdriver to adjust 25 turn trimmer pots. A multimeter capable of measuring 1mA, 250VDC and 3 to 8VAC. An optional ATEo supplied connector breakout block with BNC connectors for all Input and Output signals. Figure 2ATE-100 Signal Breakout ATE-100 Test Block for input/output signal access for troubleshooting and calibration. ATE-100 RVDT/LVDT Manual 2014-02-16 page 5 of 16 RVDT Module Datel Meter Meter Calibration Trimmer VAC Pk SetPoint Pot Meter Input Selector switch Primary Resistance Test Selector Switch Secondary Resistance Test Selector Switch Secondary Phase Indicator Figure 3 ATE-100 RVDT Module Faceplate RVDT Module Controls and Indicators ATE-100 RVDT/LVDT Manual 2014-02-16 page 6 of 16 Controls and Indicators Datel Meter Datel DMS-40PC-1-RS panel meters are used in the ATE-CFM56 test box. The red LED display has been selected for the final configuration to improve visibility. The red LED display has increased viewing angle and can be seen from a greater distance. MGain - Meter Gain Calibration Trimmer A 20 turn trimmer pot located on the circuit board and accessible through the front panel is used to calibrate the mA meter indication. RVDT VAC Pk Primary Excitation Setpoint A 10 turn Potentiometer sets the 3kHz LVDT Primary excitation voltage. Excitation output range is from 6.5 to 7.5 VAC across 10 turns of this pot. Coil Select Primary/Secondary This switch selects either the Primary or Secondary AC signal for input to the AC RMS Pk detector circuit. Primary Resistance Test Selector Switch This switch selects either the Insulation Resistance test or the Coil Resistance test of the primary RVDT coil. Secondary Resistance Test Selector Switch This switch selects either the Insulation Resistance test or the Coil Resistance test of the secondary RVDT coil. Secondary Phase Indicator These Red and Green LEDs indicate the phase relationship between the primary and secondary coils of the RVDT or LVDT. ATE-100 RVDT/LVDT Manual 2014-02-16 page 7 of 16 PLA RVDT Circuit Board Supply The circuit board has its own independent 110/220 VAC power supply. On-board regulators provide the +15 volt and +5 volt power required for the circuits on this PC board. PLA RVDT Calibration AC Peak Detector Balance Adjustment Connect a DC voltage source with an inline polarity switch across pins 12 and 3 of the M83723/86W1212N PLA RVDT Electrical Speed Trim connector. Figure 4 Meter Balance Calibration Test Cable One way to calibrate the AC Precision Rectifier Circuit is to construct a test cable as shown and execute the following procedure. The DPDT switch is used to swap the polarity of the DC input signal without affecting the DC voltage level supplied. Set the DC voltage for 10 Volts DC +.25 Volts. (It’s not important what level is actually used, but it is important that the positive and negative Datel meter values are equal in magnitude for equal but opposite DC voltage inputs.) Flip the polarity back and forth and observe the meter indication. If no change in meter indication is seen when the input polarity is switched, no adjustment is necessary. ATE-100 RVDT/LVDT Manual 2014-02-16 page 8 of 16 The Meter Balance Adjustment trimpot is located on the PLA RVDT circuit board. Figure 5 RVDT PC Board Component Side showing AC Balance Trimpot. Rock the Meter AC Balance trimmer pot. If there is no change in the meter indication, you are on the non-adjustable polarity side of the meter polarity. Record the meter indication. Flip the polarity of the input voltage. Adjust the Meter Balance trimpot to get the same meter reading as in the previous step. Flip the polarity of the input voltage and observe that the meter indication does not change. Repeat the adjustment and check procedure until no further improvement can be made. ATE-100 RVDT/LVDT Manual 2014-02-16 page 9 of 16 Alternate Method using Calibration Breakout Tool Connect a DC voltage source with an inline polarity switch into the Secondary BNC jack on the ATE-100 Calibration Breakout Tool. Figure 6 RVDT Connections on Signal Breakout Set the meter input to Secondary. Flip the DC voltage polarity back and forth and observe the meter indication. If no change in meter indication is seen when the input polarity is switched, no adjustment is necessary. The Meter Balance Adjustment trimpot is located on the PLA RVDT circuit board (Fig 5). Rock the Meter Balance trimmer pot. If there is no change in the meter indication, you are on the non-adjustable polarity side of the meter polarity. Record the meter indication. ATE-100 RVDT/LVDT Manual 2014-02-16 page 10 of 16 Flip the polarity of the input voltage. Adjust the Meter Balance trimpot to get the same meter reading as in the previous step. Flip the polarity of the input voltage and observe that the meter indication does not change. Repeat the adjustment and check procedure until no further improvement can be made. Calibrate the Primary Meter Indication Remove the signal source and connect an RVDT to the end of the cable set as a dummy load for the oscillator output. A calibration tool can easily be constructed using a spare RVDT mounted in a protractor assembly as shown: Figure 7 Protractor for spare PLA RVDT. RVDT Mounting method. Connect the reference DMM to the RVDT Primary BNC connector on the ATE-100 Calibration Breakout. ATE-100 RVDT/LVDT Manual 2014-02-16 page 11 of 16 Adjust the Primary Voltage setpoint pot to get 7.07 Volts RMS as measured across the primary, (pins 3 and 12) at the control end of the test cables or at the Primary Exe Test BNC Jack on the Signal Breakout. Flip the Meter Pri/Sec switch to Pri to connect the primary excitation signal to the input of the AC RMS detector circuit. Adjust the Pg tweaker pot to get a 7.070 Volts RMS reading on the Datel meter in the PLA RVDT module. Sweep, Measure and Record Calibration of Secondary Circuit 1. Connect an adjustable 3kHz AC signal source to pins 12 and 3 of the M83723/86W1212N (MS24266R12T12SN) PLA RVDT/Electrical Speed Trim connector or use the ATE-100 Signal Breakout. 2. Flip the Meter Pri/Sec switch to Sec to connect the secondary inputs to the AC RMS Input. 3. Connect an NIST (NBS) calibration reference meter across the AC input signal. 4. Adjust the signal source for approximately 0 .5 Volts. 5. Measure and record Datel Meter and external AC RMS DMM indications. 6. Increase signal source output amplitude by 0.5VAC. 7. Repeat steps 5, 6 & 7 until input voltage reaches 7.0 VAC RMS. Calibration of Coil Ohms Test The ATE-100 PMC Simulator has an integral coil resistance test circuit that provides a 1mA current supply that is switched through the coils in the RVDT by relays controlled by toggle switches on the front of the RVDT Module. While 1mA is flowing through a coil, the DC voltage across the coil is displayed, calibrated to display Ohms where 1mV @ 1mA = 1 Ohm. To calibrate, connect a DMM set to measure low mA current to the ATE-100 Signal Breakout Secondary BNC connector. Switch the Secondary Coil Resistance test on the Resolver Module and observe and adjust the mA trimmer on the Insulation Resistance module face so that that 1mA flows through the meter. Measure known RVDT coil resistances and record along with the coil resistance measurements from the NIST Calibrated DMM. ATE-100 RVDT/LVDT Manual 2014-02-16 Figure 8 RVDT PC Board Silkscreen Artwork page 12 of 16 ATE-100 RVDT/LVDT Manual 2014-02-16 Figure 9 RVDT Circuit Board Schematic page 13 of 16 ATE-100 RVDT/LVDT Manual Item 2 3 4 5 5.1 6 7 8 9 9.1 10 11 12 13 14 15 16 17 18 19 20 21 22 22.1 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 37.1 Quantity 1 4 4 11 4 2 1 8 1 1 2 1 2 1 2 2 2 2 2 2 8 1 1 1 1 3 7 1 4 2 1 1 2 2 1 9 2014-02-16 Reference BR1 C1,C33,C35,C38 C2,C16,C18,C20 C3,C4,C5,C7,C8,C10a,C10b, C19,C34,C36,C39 C6,C10,C26,C30 C7a,C15 C9 C11,C11b,C12,C13,C14b, C15b,C40,R51 C14 C21 C28,C29 C31 C32,C37 C41 Ch1+,Ch2+ Ch1,PL11 Ch1-,Ch2D3,D4 D5,D6 D7,D8 D9,D10,D11,D12,D13,D14, D15,D16 F1 Freq GND1 HS1 HS2,HS3,HS4 L1,L2,L3,L4,L9,IN,Out IRstR Idle+,Idle-,VSV+,VSVMOV1,MOV2 MU2 OscAmp P1,P3 P4,P6 P9 PL10,POut,PRI,PRet,PShld, SEC,SOut,SRet,SShld Part BRIDGE 10uF 1uF .1uF 33pF .0015uF .047uF tbd 10pF .47uF 0.1uF 330pF 470uF .01uF STrim+ STrim STrim1N914 1N414B 1N4001 1N4005 .5A 5K GND/SHLD HS HS1 LED IdleRst Sold 130V DMSBCD 10K 12LONG DB9F 26LONG RVDT page 14 of 16 ATE-100 RVDT/LVDT Manual 38 39 40 41 42 43 44 45 46 47 48 49 50 51 51.1 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 1 1 2 7 1 1 5 1 1 4 1 2 1 15 2 1 2 1 1 1 1 1 1 1 2 1 1 1 1 4 5 1 1 2 1 1 2 1 1 1 1 1 1 1 2014-02-16 PL12 PL13 Spare1,PL14 Q1,Q2,Q3,Q4,Q7,Q8,Q9 Q5 Q6 R2,R8,R67,R69,R71 R3 R4 R5,R35,R52,R55 R6 R13,R18 R14 R16,R31,R32,R33,R34,R36, R53,R54,R56,R57,R58,R59, R17,R48 R19 R20,R46 R22 R25 R26 R27 R28 R29 R30 R37,R40 R38 R39 R41 R49 R61,R63,R64,R66 RL1,RL2,RL3,RL4,RL5 RY1 RY4 Ry2,Ry5 Ry3 S1 S2,S2A S3 SW1 Shld Spare2 T1 TM1 TP3 Sol DB25F DB25 2N3904 EGC466 LM299 4.7k 15.6k 0 Ohm 100k 0 Ohms 20k 6.65k 10k 4.53k 22k 3.24k 10M 33.2k 30.1k 2k 6.04k 1.1k 1M 32.4k See Table 1 7.5k 1.5k 1 Ohm 1k .27k RYOM2 Run/Test RYOM 1mA/100V SW SPDT PriICR SecICR DPDT Shld DB15 TALEMA SpdTrim ACAmpl page 15 of 16 ATE-100 RVDT/LVDT Manual 82 83 84 85 86 87 88 89 90 91 92 93 2 1 1 1 1 1 5 1 1 1 1 2 End of file. U1,U2 U3 U5 U6 U7 U8 VR1,VR2,VR3,VR4,VR6 VREG1 VREG2 VREG3 VSVR com,hot 2014-02-16 LM301A LM124 OPA541AP LM239 CD4070 LF356 1K LM7805 LM7815 LM7915 VSV Rst ts1 page 16 of 16