Data Acquisition Unit DA100, Main unit, Sub units DS400/DS600

advertisement
<<Contents>> <<Index>>
General
Specifications
GS 04M01B01-11E
Data Acquisition Unit DA100
Main unit —stand-alone type (style number:S10)
—expandable type (style number:S10)
Sub units —DS400/DS600 (style number:S10)
The following product was discontinued as of March, 2013.
Refer to the following cautionary notes
before you configure your system.
Discontinued products: DA100-2 Data Acquisition Unit (Expandable Model)
DARWIN is a system comprising a number of dataacquisition equipment components.
In the course of system growth, new models, software,
various input/output modules and optional features are
added to the family to enhance the systems expandability
and flexibility.You can check the versions of your
equipment and software by referring to the style
number:Sn* shown on the nameplate of the main unit.
When configuring a system, you must confirm that the
style number of each component unit and software
meets the following requirements:
* release number in the case of software:Rn
5.27
5.27
5.29
5.29
5.33
5.46
5.33
5.46
4.98
4.98
5.21
5.21
5.46
5.46
5.15
5.14
5.15
5.14
5.38
5.38
5.00
5.00
5.25
5.25
5.07
5.07
STATUS
DATA ACQUISITION UNIT
stand-alone type
(1) The style number of each input/output module must
be the same as or lower than that of the main unit or
sub-unit to which the module is connected.
(2) The release number of a dedicated software package
must be the same as or higher than the style number
of the main unit or sub-unit where the package is
installed and where it performs control.
Any equipment/software not meeting these requirements is incompatible with your system configuration.
For information on how to upgrade to compatible
equipment/software, consult our sales personnel.
5.27
5.29
5.27
5.29
5.33
5.46
4.98
5.21
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.46
5.15
5.14
5.38
5.00
5.25
5.07
5.00
5.25
5.07
STATUS
STATUS
SUB UNIT
DATA ACQUISITION UNIT
expandable type
DA100 Data acquisition unit
Model
DA100 stand-alone type
Integrated type capable of measuring data from up to 40
channels.
Can be carried about easily and is suitable for small scale
data logging.
The number of channels can be increased from 10 to 40
Increasing number of
channels in a module steps, and also the kinds of inputs
input channels,
changing kinds of inputs can be changed.
Kinds of inputs
Universal, DC V/TC/DI, mA, power monitor, strain, Pulse, DI
Input and output modules Input modules, communication module, DI/DO module,
that can be connected to
alarm output modules, retransmission modules
the main unit
Connection of sub units, Not applicable
and remote measurement
distance
Input and output modules Not applicable
that can be connected to
the sub units
Max scanning speed
All channels/0.5 sec
Features
DA100 expandable type
Can be expanded up to 300 channels.
You can perform multi-channel measurement with the
minimum of wiring by connecting sub units to the main
unit with dedicated cable.
The number of channels can be increased from 10 to 300
channels in a module steps, and also the kinds of inputs
can be changed.
Universal, DC V/TC/DI, mA, power monitor, strain, Pulse, DI
(Input modules are connected to the sub units.)
Communications module, DI/DO module,
alarm output modules
Up to 6 units,
500 m max (Full extension)
Input modules, DI/DO module,
alarm output module , retransmission modules
All channels/0.5 sec
GS 04M01B01-11E
© Copyright November 1995 (YK)
13th Edition: Aug. 2013 (KP)
<<Contents>> <<Index>>
Outline of the stand-alone type
Main features
The DA100 data acquisition unit (stand-alone type) measures input
signals from between 10 and 40 channels, and transfers the measured
data in realtime to a personal computer. This highly portable unit is also
suitable for on-site data logging.
(1) Compact:
Occupies only 1/5 of the volume of other Yokogawa units.
(Comparison between a system consisting of the DA100 main unit
+ one sub unit and a system consisting of one DA2500E + one
remote scanner)
(2) High speed:
Can measure data from 300 channels at 0.5-second intervals
maximum.
(3) A wide range of inputs:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage/
thermocouple/contact dedicated inputs, mA, power monitor, strain,
pulse, DI input.
(4) Remote measurement:
The sub unit is designed to be connected to the main unit with
dedicated cable, enabling it to be located up to 500 m away from
the main unit.
DA100 stand-alone type main unit + PC
5.27
5.27
5.29
5.29
5.33
5.46
5.33
5.46
4.98
4.98
5.21
5.21
5.46
5.46
5.15
5.14
5.15
5.14
5.38
5.38
5.00
5.00
5.25
5.25
5.07
5.07
STATUS
DATA ACQUISITION UNIT
Outline of functions
Main features
(1) Compact:
Occupies only 1/5 of the space of Yokogawa’s remote scanner for
the DA2500E.
(2) High speed:
Can measure data from 40 channels in 0.5 second maximum.
(3) A wide range of inputs:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage/
thermocouple/contact dedicated inputs, mA, power monitor, strain,
pulse, DI input.
Outline of functions
(1) Setting and control of connected input/output modules
(2) The measured results obtained using input modules can be
transferred to a personal computer via a GP-IB, RS-232-C, RS-422A/RS-485, Ethernet communications interface.
Outline of expandable type
The main unit of the DA100 data acquisition unit (expandable type) can
be connected to DS400 (4-slot type) or DS600 (6-slot type) sub units
containing various input modules, in order to configure a system that
can acquire data from a maximum of 300 channels. The measured data
is transferred in realtime to a personal computer.
(1) Setting and control of input/output modules on the sub units
connected with dedicated cable (Setting is done using the connected
personal computer and the setting software provided.)
(2) Control of alarm output modules, DI/DO modules, communication
interface modules connected to the DA100 main unit.
(3) Acquisition by the DA100 main unit of the measured results from
the input modules, via the sub units.
(4) Transfer of the measured results acquired by the DA100 main unit
to a personal computer, via a GP-IB, RS-232-C, or RS-422-A/RS485, and Ethernet communication interfaces.
Outline of sub units
The DS400/DS600 sub unit functions as an interface between the
expandable version of the DA100 data acquisition and the various input/
output modules to which it is connected.
A maximum of four input and output modules of various kinds (4 slots)
can be connected to the DS400, and a maximum of six input and output
modules (6 slots) can be connected to the DS600.
A maximum of six sub units can be connected to one main unit. Both
DS400 and DS600 sub units can be connected to the same main unit.
The main unit can be connected to the sub units, or the sub units to each
other, with dedicated cable, enabling them to be separated by up to 500
m.
The sub units have excellent environmental toughness and can be
installed very easily, enabling them to be installed over a wide area
without environmental restrictions.
Outline of functions
DA100 expandable type main unit + sub unit + PC
5.27
5.29
5.33
5.46
4.98
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
5.00
5.25
5.07
(1) Setting and control of the connected input/output modules (by
means of commands from the DA100 main unit.)
(2) Measured values output to the DA100 main unit .
STATUS
STATUS
SUB UNIT
DATA ACQUISITION UNIT
2
GS 04M01B01-11E
<<Contents>> <<Index>>
■ Configuration
DA100 expandable type:
Expandable type main unit + sub units (DS400 or DS600)
+ various input/output modules + communication interface + data
acquisition software
Component units
Available module groups
b
-/B -/A
CH1
b
-/B -/A
CH1
CH2
b
CH2
CH3
CH4
CH3
CH5
CH4
CH6
CH5
CH7
CH6
CH8
CH7
CH3
STATUS
CH4
CH5
CH6
CH7
CH9
CH10
DATA
ACQUISI
TION
CH8
CH9
-/B -/A
CH1
CH2
UNIT
CH8
CH10
CH9
POWER
CH10
100-240V
AC 50/6
0Hz
70VA
MAX
DA100 main unit stand-alone type
NO C
ALM1
NO C
ALM2
ALM1
ALM3
ALM2
ALM4
ALM3
ALM5
ALM4
ALM6
ALM5
The DA100 data acquisition unit can be freely configured for different
functions by selecting modules from the following module groups and
connecting them to the main or sub units.
Input modules:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage/
thermocouple/contact dedicated input modules, mA, power monitor,
strain, pulse, DI input.
Alarm modules:
4 point out put (transfer contact) or 10 point out put (make contact)
(The number of alarm channels can be increased in module units.)
Communications modules:
Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet.
DI/DO modules:
Alarm 2-point output (transfer contact), fail output, command DO,
remote control signal input.
Retransmission modules:
Re-output of measured values and computed results.
STATUS
ALM7
NOTE
ALM6
ALM8
ALM7
ALM9
DATA
ACQUISI
TION
ALM8
ALM10
Refer to “Standard connection modules” in GS 04M01E01-11E, or
GS 04M01E01-50E for detailed specifications of the above
modules.
UNIT
ALM9
ALM10
POWER
100-240V
AC 50/6
0Hz
70VA
MAX
DA100 main unit expandable type
Package software
• DARWIN DAQ 32 (Standard Package)
• DARWIN DAQ 32 Plus (Optional Package)
General
b
DAQ 32 and DAQ 32 Plus are software packages developed by
YOKOGAWA specially for the DARWIN series.
These packages run on a personal computer, achieving highly
dependable data acquisition using DARWIN series units (DA100,
DC100, DR130, DR230, and DR240) and superb operability.
The main differences between the two packages are in the
monitoring functions. The DAQ 32 only offers two display
formats - waveform trend and digital; has 2 groups of 10 channels/
window; and does not support alarm display. If simultaneous
multi point monitoring or more flexible display forms of data such
as level meter, analog meter, and thermometer faceplates, and
alarm indications are required, use the optional DAQ 32 Plus.
-/B -/A
CH1
b
-/B -/A
CH1
CH2
b
CH2
CH3
-/B -/A
CH1
b
CH4
CH3
CH5
CH4
CH6
CH5
CH7
CH6
CH8
CH7
STATUS
CH3
CH4
CH4
CH5
CH5
CH6
SUB
CH10
UNIT
CH6
CH7
CH9
CH10
CH2
CH3
CH8
CH9
-/B -/A
CH1
CH2
CH8
CH7
CH9
CH8
CH9
CH10
POWER
CH10
100-240V
AC 50/6
0Hz
70VA
MAX
DS400 sub unit
b
-/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b
-/B -/A
CH1
b
CH2
-/B -/A
CH1
b
CH3
CH2
-/B -/A
CH1
b
CH4
CH3
CH5
CH4
CH6
CH5
CH7
CH6
CH8
CH7
CH9
CH10
CH8
CH9
CH10
CH2
CH3
-/B -/A
CH1
CH2
STATUS
CH4
CH5
CH6
CH7
CH3
CH4
CH5
SUB
CH7
CH9
CH8
CH10
UNIT
CH6
CH8
CH9
POWER
CH10
100-240V
AC 50/6
0Hz
70VA
MAX
DS600 sub unit
Unit configuration
The DA100 comes in the following two types, each of which is intended
to be set and controlled by a personal computer via a general purpose
communications interface.
DA100 stand-alone type:
Stand-alone type main unit + various input/output modules +
communication interface modules + data acquisiton software
GS 04M01B01-11E
3
4
Alarm output
module
I/O module
Input
DI/DO
module
Module
1-5 V module
DC V
DARWIN
DAQ 32
4-20 mA
module
Retransmission module
Set-up and control
software
DA100 stand-alone type system configuration
TC
Universal
DC V/TC/DI
module
DARWIN
DAQ 32 Plus
package software
DI
module
RTD
DAQLOGGER
CH4
CH3
CH2
CH1
CH6
CH5
b
-/B -/A
Power
module
CH10
CH9
CH8
CH7
No alarm module or DI/DO module
can beconnected to theright
side of this input module.
CH1
CH2
CH10
CH9
CH8
CH7
CH6
CH5
CH4
CH3
b
-/B -/A
Contact Status
Input module
Pulse
module
Install
CH1
CH2
CH10
CH9
CH8
CH7
CH6
CH5
CH4
CH3
b
-/B -/A
ACQUIS
ITION
UNIT
100-240V
AC 50/60Hz
POWER
Strain
module
DATA
STATUS
70VA
AC
~
MAX
Communication
interface cable
mA(current)
module
current
A
GP-IB
module
DA100 main unit
Personal computer
PULSE
RS-232-C
module
RS-422-A/485
module
Communication interface module
STRAIN
Ethernet
module
<<Contents>> <<Index>>
GS 04M01B01-11E
GS 04M01B01-11E
Alarm output
module
DI/DO
module
Input
I/O module
Module
DARWIN
DAQ 32
DCV
1-5 V module
4-20 mA
module
Retransmission module
Sub unit
Set-up and control
software
TC
Extension
module
Remote
measurement
DARWIN
DAQ 32 Plus
package software
RTD
Universal
DC V/TC/DI
module
DAQLOGGER
Install
DI
module
NO C
ALM1
ALM2
NO C
ALM10
ALM9
ALM8
ALM7
ALM6
ALM5
ALM4
ALM3
DATA
Contact Status
VAC
UNIT
50/60Hz
ITION
MAX
AC
~
Pulse input
module
current
A
Strain
module
DA100 main unit
Personal computer
Dedicated cable (up to 500 m)
70VA
mA(current)
module
100-240
POWER
ACQUIS
STATUS
Communication
interface cable
Input module
Power
module
ALM10
ALM9
ALM8
ALM7
ALM6
ALM5
ALM4
ALM3
ALM2
ALM1
No alarm module or DI/DO module
can beconnected to theright
side of this input module.
DA100 expandable type system configuration
PULSE
GP-IB
module
RS-232-C
module
STRAIN
RS-422-A/485
module
Communication interface module
Sub unit
Ethernet
module
<<Contents>> <<Index>>
5
<<Contents>> <<Index>>
■ Connecting modules
Connecting modules to the stand-alone type
Modules that can be connected
Input modules:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage/
thermocouple/contact dedicated, mA, power monitor, strain, pluse,
DI input modules
Alarm modules:
4 channels (transfer contact) or 10 channels (make contact) (The
number of alarm channels can be increased in module units.)
Communications modules:
Select one type from GP-IB, RS-232-C, RS-422-A/RS-485,
Ethernet
DI/DO modules:
Alarm 2-point output (transfer contact), fail output, command DO,
remote control signal input
Retransmission modules:
Re-output of measured values and computed results
Extension module:
For remote measurment
Definition of number of connections
•
•
•
•
•
•
•
•
•
A maximum of six modules can be connected to the main unit.
One of these must always be a communications module.
The number of DI/DO modules must be no greater than one.
The alarm output module, DI/DO module, and retrandmission
module must be connected on the left side of the input modules.
Number of input modules ≤ 4
Number of input modules + number of alarm modules + DI/DO
module + communications module ≤ 6
One extension module can be connect to the main unit
Number of retransmission modules ≤ 4
The standard operating temperature and humidity are different for
each module type.
Therefore,always make sure to verify this when connecting the
module.
Connecting modules to the expandable type
Modules that can be connected
Main unit
Alarm modules:
4-point output (transfer contact) or 10-point output (make contact)
(The number of alarm channels can be increased in module units.)
Communications modules:
Select one type from GP-IB, RS-232-C, RS-422-A/RS-485,
Ethernet
DI/DO modules:
Alarm 2-point output (transfer contact), fail output, command DO,
remote control signal input.
Sub unit DS400/DS600
Input modules:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage,
thermocouple, contact dedicated input modules, pulse
Alarm modules:
4-point output (transfer contact) or 10-point output (make contact)
(The number of alarm channels can be increased in module units.)
DI/DO modules:
Alarm 2-point output (transfer contact), fail output, command DO
modules and remote control signal input
Extension module:
For remote measurment
Retransmission modules:
Re-output of measured values and computed results
6
Definition of number of connections for the expandable
type
DA100 main unit:
• The number of input modules and retransmission modules is 0.
Also, 1 communications module must always be connected.
• Number of alarm modules + DI/DO module ≤ 3
Sub unit DS400:
• The maximum number of modules per slot that can be connected
is 4.
• Number of input modules + DI/DO module + alarm modules +
retransmission modules ≤ 4
Sub unit DS600:
• The maximum number of modules per slot that can be connected
is 6.
• Number of input modules + DI/DO module + alarm modules +
retransmission modules ≤ 6
Common to all:
• One DI/DO module can be connected to one expandable type
system
• The alarm output module and DI/DO module must be connected
on the left side of the input modules.
• One extension module can be connected to one sub unit.
• The retransmission module can be connected to the sub unit only.
Up to 30 modules.
• The standard operating temperature and humidity are different for
each module type.
Therefore, always make sure to verify this when connecting the
module.
Method of connecting modules
The standared operating temperature and humidity are different for each
module type.
Therefore, always make sure to verify these when connecting the
module.
Stand-alone type:
Connect directly to the main unit.
The alarm output modlues and DI/DO module must be connected
on the left side of the input modules.
Expandable type:
Connect the input modules, retransmission modules, or extension
module directly to the sub unit. (You cannot connect these modules
directly to the main unit.)
Connect the alarm modules, communications module and DI/DO
module directly to the main unit.
The alarm output modlues and DI/DO module must be connected
on the left side of the input modules.
Connecting sub units
Kinds of sub units (type name):
DS400 sub unit: For 4 slots
DS600 sub unit: For 6 slots
Number of sub units to be connected:
Stand-alone type:Cannot be connected.
Expandable type: A maximum of six sub units can be connected.
(This also applies when 4-slot sub units and 6-slot
sub units are connected to the same main unit.)
Method of connecting sub units:
A sub unit can be connected to either the main unit or another sub
unit with dedicated cable. Maximum total extension length is 500
m.
GS 04M01B01-11E
<<Contents>> <<Index>>
■ Standard specifications
General specifications
Construction
Installation method:
Floor mounting: Use the stand at the bottom of each unit.
Direct panel mounting: Screw the unit directly to the panel at the
specified points.
Rack mounting: Use the dedicated mounting brackets.
(Regardless of which mounting method you use,
be sure to install the units in an upright position.)
Materials:
Steel plate, aluminum castings, plastic moldings
Paint color:
Base unit:
Modules:
Lamp black (equivalent to Munsell 0.8Y2.5/0.4)
Slate gray light (equivalent to Munsell 0.1PB4.6/
0.2)
Slate gray light (equivalent to Munsell 0.1PB4.6/
0.2)
External dimensions:
Stand-alone type main unit:
Approx. 422 (W) × 176 (H) × 100 (D) mm
Expandable type main unit:
Approx. 336 (W) × 165 (H) × 100 (D) mm
DS400 sub unit: Approx. 336 (W) × 165 (H) × 100 (D) mm
DS600 sub unit: Approx. 422 (W) × 176 (H) × 100 (D) mm
Weight:
Stand-alone type main unit:
Approx. 3.5 kg (with 4 input modules + 1 alarm
output module + 1 communications module
installed)
Approx. 1.1 kg*
Expandable type main unit:
Approx. 2.5 kg (with 4 input/output modules
installed)
Approx. 0.9 kg*
DS400 sub unit: Approx. 2.5 kg (with 4 input/output modules
installed) Approx. 0.9 kg*
DS600 sub unit: Approx. 3.5 kg (with 6 input/output modules
installed) Approx. 1.1 kg*
*: is the weight of each unit without modules installed.
Input
Measurement range:
NOTE
Refer to “Standard connection modules” in GS 04M01E01-11E for
detailed specifications of the measurement range.
Measurement interval:
Selectable from 0.5, 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 sec
depending on the minimum measurement interval (when modules
with different minimum intervals are installed together, the
measurement interval is determined by whichever module has the
maximum interval).
Stand-alone type:
Max 40 channels/500 ms (when the software
provided is used)
Expandable type:
Max 300 channels/500 ms (when the software
provided is used)
GS 04M01B01-11E
A/D integration period (dependent on the module):
Selectable from 20 ms (50 Hz), 16.7 ms (60 Hz), 100 ms (10 Hz),
and auto switching (unavailable for a DC power supply model).
Alarm
Number of settings:
Up to four settings can be made for each channel.
Kinds of alarms:
Selection from higher limit, lower limit, difference higher limit,
difference lower limit, higher limit of rate of change, lower limit
of rate of change.
Rate of change alarm time interval:
Can be set to measurement interval × 1 to 15 (common to both
rising and falling limits)
Output mode:
Excitation/non-excitation selection, AND/OR mode selection, and
output hold/non-hold specification can be made. (common to all
channels)
Six reflash alarm output contacts can be specified.
Number of alarm output points:
Stand-alone type:
2 points (DI/DO module) to 40 points max
Expandable type:
Up to 30 points can be connected to the DA100
main unit (the number of alarm points can be
increased in module units)
By connecting sub units, (the number of alarm
points can be increased in module units).
Number of alarm output modules that can be connected:
Stand-alone type:
The number of alarm points can be increased in
module units.
Expandable type:
Up to 3 modules can be connected to the DA100
main unit, up to 6 modules can be connected to
one sub unit, and up to 4 modules can be
connected to one subunit.
Standard computation functions
Computation functions:
Difference between arbitrary channels, linear scaling, moving
average
Scaling:
Ranges for which scaling can be done:
DC voltage, thermocouple, RTD, contact, strain,
mA,
Scaling range: –30000 to +30000
Decimal point: Can be set freely.
Measurement accuracy for scaling:
Measurement accuracy for scaling (digits) =
Measurement accuracy (digits) × Scaling span
(digits)/Measurement span (digits) + 2 digits
(Numbers below the decimal point are rounded
up.)
Moving average:
The moving average results for between 2 to 64 scans are computed.
Communications functions
Communication modules:
GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet communications
interface modules
7
<<Contents>> <<Index>>
Output functions
DI/DO module:
Internal alarm output 2 points, fail output function, command Do.
Retransmission modules:
Re-output of measured values and computed results.
10 voltage and 2 current channels.
AC power supply section
Rated supply voltage:
100 to 240 VAC (free supply voltage selection)
Usable supply voltage range:
90 to 250 VAC
Rated supply frequency:
50/60 Hz
Power consumption:
Stand-alone type main unit
(when 6 connectable modules are installed)
max approx. 55 VA (when 100 VAC is input)
max approx. 70 VA (when 240 VAC is input)
Expandable type main unit
(when 4 connectable modules are installed)
max approx. 45 VA (when 100 VAC is input)
max approx. 55 VA (when 240 VAC is input)
DS400 sub unit
(when 4 connectable input/output modules are installed)
max approx. 45VA (when 100 VAC is input)
max approx. 55 VA (when 240 VAC is input)
DS600 sub unit
(When 6 connectable input/output modules are installed)
max approx. 55 VA (when 100 VAC is input)
max approx. 70 VA (when 240 VAC is input)
DC power Supply section
(DC power supply only, Specify when ordering)
Rated supply voltage:
12 to 28 VDC
Usable supply voltage range:
10 to 32 VDC
Power consumption:
Approx. 25 VA max.
Terminal:
Dedicated connector
Other:
Automatic selection of A/D integral period does
not function.
AC Adapter
(for DC power supply model only, optional accessary)
Rated supply voltage:
100 to 240 VAC
Usable supply voltage range:
90 to 250 VAC
Rated supply frequency:
50/60 Hz
Power consumption:
max. 90 VA
Others
Clock:
With calendar function (Western calendar).
Clock accuracy: ±100 ppm
System alarm: Contact output (when DI/DO module is
connected)
Set value backup:
Lithium battery backup (approx. 10 years),
excluding clock function
Insulation resistance:
At least 20 MΩ between each terminal and
ground (measured with 500 VDC)
8
Withstand voltage:
Between AC power supply terminal and case of
DA100 main unit:1500 VAC (50/60 Hz) for one
minute
Between DC power supply terminal and case of
DA100 main unit:1000 VAC (50/60 Hz) for one
minute
Between input terminal and case of DA100 main
unit:1500 VAC (50/60 Hz) for one minute
Between output terminal and case of DA100
main unit:2300 VAC (50/60 Hz) for one minute
Normal operation conditions
Supply voltage: 90 to 250 VAC, 10 to 32 VDC
Supply frequency:50 Hz ± 2%, 60 Hz ± 2%
Ambient temperature:
Stand-alone type main unit
Expandable type main unit
When floor-mounted and Desk top : 0 to 50˚C
When panel-mounted : 0 to 50˚C
When Rack-mounted : 0 to 50˚C
DS400/DS600 sub unit
When floor-mounted and Desk top : -10 to 50˚C
When panel-mounted : -10 to 60˚C
When Rack-mounted : -10 to 50˚C
When DC power operation : 0 to 50˚C
Ambient humidity:
Temperature
Humidity
–10 to 40°C
20 to 80% RH
40 to 50°C
10 to 50% RH
50 to 60°C
5 to 30% RH
* no ice formation
10 to 60 Hz 0.2 m/s2
Not allowed
400 A/m max (50/60 Hz)
Mount the unit left-right horizontally or
vertically, as a general rule.
Installation location:
Room
Installation height:
Altitude up to 2,000 m
Installation category:
II (according to CSA22.2 No.1010.1)
Measurement category:
II (according to IEC61010-1)
Degree of pollution: 2
Warm-up time: At least 30 minutes after power switch-on
Vibration:
Shock:
Magnetic field:
Position:
Standard performance
Measurement accuracy:
Reference operation state:
23 ± 2°C, 55 ± 10% RH, supply voltage: 90 to
250 VAC, supply frequency: 50/60 Hz ± 1%,
Warmup: At least 30 minutes; When operating,
the system must not adversely affect the operation
of other measuring instruments by generating
vibration, for example. enerating vibration, for
example.
NOTE
Refer to “Standard connection modules” in GS 04M01E01-11E for
detailed specifications of the measurement accuracy.
GS 04M01B01-11E
<<Contents>> <<Index>>
Effect of Operation Conditions
Ambient temperature:
Variation for a temperature change of 10°C
within ±(0.1% of rdg + 1 digit)
±(0.2% of span + 1 digit) for Cu 10 Ω
Voltage variation: Within ±1 digit over the range of 90 to 132, or
180 to 250 VAC (frequency 50/60 Hz)
External magnetic field:
Variation with respect to AC (50/60 Hz) and DC
magnetic fields of 400 A/m ... Within ±(0.1% of
rdg + 10 digits)
Radio wave:
Within ±(1% of span) at 1 m from 150 MHz or
460 MHz field
Signal source resistance:
Variation with respect to signal source resistance
+ 1 kΩ change
(1) Voltage 2 V range or below ... Within ±10 µV
6 V range or above ... Within ±0.1% of rdg
(2) Thermocouple
Within ±10 µV; However, it must be within ±100
µ when burnout is specified.
(3) RTD Variation with respect to change of 10 Ω per wire
(when all three wires are the same resistance
value)
Indication ... Within ±(0.1% of rdg + 1 digit)
Variation in indication with respect to a
difference of 40 mΩ in the resistance
between conductors (max difference between
3 wires) ... Approx. 0.1°C
Mounting position:
Variation when the unit is mounted horizontally
on a panel ... Within ±(0.1% of rdg + 1 digit)
excluding RJC error
Vibration:
Variation when sinusoidal vibration of
acceleration 0.2 m/s2 is applied for 2 hours in each
of the 3 axial directions over a frequency range of
10 to 60 Hz ... Within ±(0.1% of rdg + 1 digit)
Transportation and storage conditions
These refer to the environmental conditions existing during transportation and storage from the time of shipment from the factory until
commencement of use, and also during transportation and storage in the
case of a temporary period of non-use.
If the environmental conditions are maintained within the specified
range, the unit will not incur permanent damage, and can be returned to
a normal working condition (re-adjustment may be required in some
cases).
Ambient temperature: –25 to 60°C
Humidity:
5 to 95% RH
Vibration:
10 to 60 Hz 4.9 m/s2 max
Shock:
392 m/s2 max (in packed condition)
Supported standards
Obtained CSA22.2 No.61010-1
Installation category (Overvoltage category): II,
Degree of pollution: 2
Obtained UL No.61010-1 (CSA NRTL/C)
UL
CE marking was removed under the publication of the
CE
3rd edition of IEC Standard.
EN 55011 Class A, Group 1
C-Tick
KC marking Electromagnetic wave interference prevention
standard, electromagnetic wave protection standard
compliance
CSA
GS 04M01B01-11E
/M1: MATH Function
Computation types
Types:
Four arithmetical operations, SQR (square root), ABS (absolute
value), LOG (common logarithm), LN (natural logarithm), EXP
(exponent), statistical computation*, logical computation (AND,
OR, NOT, and XOR), relational computation, exponentiation,
previously-measured value reference, hold**, reset, clear, and
remote RJC.
* Statistical computation
CLOG:
Computation process of simultaneously measured
values within a group (total, maximum,
minimum, average, and maximum - minimum)
TLOG:
Computation process of a specific channel over
time axis (total, maximum, minimum, average,
and maximum - minimum)
Statistical computation interval:
Set by the event/action function (effective when
/M1 option is selected)
**Temporary hold of the computed result
Can be controlled by event/action function (such as remote control
signal, time specified, and alarm status). (effective when /M1 option
is selected)
Number of channels for computing (Number of channels that can
be allocated for computational purposes.):
Stand-alone type: 30ch maximum
Expandable type: 60ch maximum
Computation interval:
Every measurement interval (except when the computation
becomes too difficult to be processed every measured interval, in
which case an alarm is generated)
Significant digits during computation:
±1038
Significant digits of the computed result:
-9999999 to +99999999 (Decimal point can be set to have 1 to 4
digits on the right of the decimal point)
Input from communication interface:
Digital value (ASCII numerical array) input from the communication interface
Computation start/stop:
Can be controlled by communication commands and event/action
function (such as remote control signal, time specified, and alarm
status)
Other functions included in the math function:
Remote RJC
Input type:
Thermocouple (TC)
Accuracy:
(Twice the measurement accuracy of the standard
thermocouple input) + (temperature difference
between the terminal of the remote terminal
section and thermocouple section for measuring
the remote terminal temperature)
Thermocouple burnout: not selectable
/M3: Report Function
Refer to the GS 04M01B01-31E
9
<<Contents>> <<Index>>
Type name and specification code
Data Acquisition Unit DA100
Model
DA100
Type
Suffix Code
Data acquisition unit
Stand-alone type
-1
Expandable type
-2
Software
Power Supply
Description
Optional Code
DARWIN DAQ 32 for IBM PC-AT
3
100 VAC to 240 VAC
12 VDC to 28 VDC (DC power supply only)
-1
-2
(always specify Y for the power cable)
Power Inlet & Power Cable
D
F
3-pin power inlet w/UL, CSA cable
3-pin power inlet w/VDE cable
H
3-pin power inlet w/CCC cable
R
S
3-pin power inlet w/SAA cable
3-pin power inlet w/BS cable
W
3-pin power inlet w/screw terminal
/M1
Dedicated connector for DC power supply w/o power cable
Math function (including RRJC)
/M3
Report function
/FC
DARWIN DAQ 32 is supplied with floppy disks
Optional Code
Description
4 slots subunit for inputs and alarm output
6 slots subunit for inputs and alarm output
Always-00
100 VAC to 240 VAC
12 VDC to 28 VDC (DC power supply only)
(always specify Y for the power cable)
3-pin power inlet w/UL, CSA cable
3-pin power inlet w/VDE cable
3-pin power inlet w/CCC cable
3-pin power inlet w/SAA cable
3-pin power inlet w/BS cable
3-pin power inlet w/screw terminal
Dedicated connector for DC power supply w/o power cable
Y
Optional Features
Subunit DS400/DS600
Model
DS400
DS600
Type
Power Supply
Suffix Code
-00
Power Inlet & Power Cable
10
-1
-2
D
F
H
R
S
W
Y
GS 04M01B01-11E
<<Contents>> <<Index>>
Input module
Model Code
DU100-11
DU100-21
DU100-31
DU100-12
DU100-22
DU100-32
DU200-11
DU200-21
DU200-31
DU200-12
DU200-22
DU200-32
DU300-11
DU300-12
DU400-12
DU400-22
DU500-12
DU500-13
DU500-14
DU600-11
DU700-11
Description
10ch universal input module (DCV/TC/DI & RTD)
20ch universal input module (DCV/TC/DI & RTD)
30ch universal input module (DCV/TC/DI & RTD)
10ch universal input module (DCV/TC/DI & RTD)
20ch universal input module (DCV/TC/DI & RTD)
30ch universal input module (DCV/TC/DI & RTD)
10ch DCV/TC/DI input module
20ch DCV/TC/DI input module
30ch DCV/TC/DI input module
10ch DCV/TC/DI input module
20ch DCV/TC/DI input module
30ch DCV/TC/DI input module
10ch mA input module
10ch mA input module
Power monitor module for single phase
Power monitor module for 3 phase
10ch strain input module (120 Ω)
10ch strain input module (350 Ω)
10ch strain input module (External bridge box)
10ch pulse input module
10ch DI input module
Terminal
Screw
Screw
Screw
Clamp
Clamp
Clamp
Screw
Screw
Screw
Clamp
Clamp
Clamp
Screw
Clamp
Clamp
Clamp
Clamp
Clamp
NDIS
Screw
Screw
Other module
Model Code
DT100-11
DT200-11
DT200-21
DT300-11
DT300-21
DT300-31
DT300-41
DT500-11
DT500-21
GS 04M01B01-11E
Description
2 alarm, 12 remote, fail/chart end
Screw terminal
4 alarm relay output (transfer contacts)
Screw terminal
10 alarm relay output (make contacts)
Screw terminal
GP-IB interface module
RS-232-C interface module
RS-422-A/RS-485 interface module
Ethernet interface module
10 channels, 1-5 V output retransmission module
2 channels, 4-20 mA output retransmission module
11
<<Contents>> <<Index>>
Accessories
Model Code
Description
DV100-011
DV100-012
Extension module
Extension base unit
DV200-000
Extension cable (0.5 m)
DV200-001
DV200-002
Extension cable (1 m)
Extension cable (2 m)
DC200-005
Extension cable (5 m)
DV200-010
Extension cable (10 m)
DV200-020
DV200-050
Extension cable (20 m)
Extension cable (50 m)
DV200-100
Extension cable (100 m)
DV200-200
DV200-300
Extension cable (200 m)
Extension cable (300 m)
DV200-400
Extension cable (400 m)
DV200-500
DV250-001
Extension cable (500 m)
Cable adapter
DV300-011
Shunt resistor 10 Ω for screw input terminal
DV300-012
DV300-101
Shunt resistor 10 Ω for clamped input terminal
Shunt resistor 100 Ω for screw input terminal
DV300-102
Shunt resistor 100 Ω for clamped input terminal
DV300-251
DV300-252
DV400-011
Shunt resistor 250 Ω for screw input terminal
Shunt resistor 250 Ω for clamped input terminal
Rack mount kit (DA100 exp./DS400) for ANSI
DV400-012
DV450-001
DV500-001
Rack mount kit (DA100 stand./DS600) for ANSI
Strain conversion cable
AC adapter W/UL, CSA cable
DV500-002
DV500-003
DV500-004
AC adapter W/VDE cable
AC adapter W/SAA cable
DV500-005
AC adapter W/BS cable
AC adapter W/CCC cable
Package software
12
Model Code
DP120-13
WX102/CD1
Description
DARWIN DAQ 32 software (Windows XP/Vista/7) (comes standard)
DARWIN DAQ 32 Plus software (Windows 2000/XP/Vista/7) (optional)
WX101/CD1
DAQLOGGER for multi-channel data logging software (Windows 2000/XP/Vista/7) (optional)
GS 04M01B01-11E
<<Contents>> <<Index>>
Wiring Input Signal Lines (to Universal and DCV/TC/DI input modules)
Terminals
Screw type terminal
b
Clamp type terminal
-
+
DC voltage • TC •
contact
B
A
RTD*
CH1
CH2
*There are no RTD
input terminals on
the DCV/TC/DI input
module.
A +
B b
CH2
CH10
CH1
CH4
CH3
CH10
CH9
Wiring Diagram
DC voltage input/DI input (contact)
+
DC input
-
+
+
DC voltage input
-
+
DC current input
-
TC input
-
RTD input
b
B
+
Shunt resistor
Note:For 4 to 20 mA input, shunt
resistance value should
be 250 Ω ± 0.1%
A
A
b
B
Compensation lead
10 Ω* max./leadwire
Three wire resistances
should be approx. equal.
*10 Ω max. for Pt 100 Ω and
Pt 50 Ω, 1 Ω max. for Cu 10 Ω.
Wiring Alarm Output SIgnal Lines (to DI/DO and Alarm output modules)
Terminals
NO
Contact capacity:
250 VDC/0.1 A (with a
resistor load)
250 VAC/2 A (with a
resistor load)
30 VDC/2 A (with a resistor
load)
Fail output:
becomes de-activated when
an error is detected in the
system.
GS 04M01B01-11E
C
DT100-11
NC
Fail output
(transfer
contact)
Remote control
input
Can be used for
event/action
function only
when the /M1
option of DA100
is specified.
1
2
Alarm output
(transfer
contact)
NO
C
DT200-11
NC
1
2
Alarm output
(transfer
contact)
NO
C
DT200-21
1
2
Alarm output
(make
contact)
3
4
Alarm output
(transfer
contact)
10
13
<<Contents>> <<Index>>
Location and Location Number (Channel Number, Alarm Output Number, DI/DO Number)
The location numbers correspond to channel numbers for locations where the input module is connected,
to alarm output numbers for locations where the alarm output module is connected, and to DI/DO
numbers for locations where the DI/DO module is connected.
In case of the DA100 Stand-alone type
The location numbers correspond to the location of each module as shown in the figure below.
Module 5 (Location numbers:051 to 060)
Module 4 (Location numbers:041 to 050)
Module 3 (Location numbers:031 to 040)
Module 2 (Location numbers:021 to 030)
Module 1 (Location numbers:011 to 020)
Module 0 (Location numbers:001 to 010)
In case of the DA100 Expandable type
The unit number (the number of the main unit is fixed at “I”) and location numbers correspond to the
location of each module as shown in the figure below.
Module 3 (Location numbers:131 to 140)
Module 2 (Location numbers:121 to 130)
Module 1 (Location numbers:111 to 120)
Module 0 (Location numbers:101 to 110)
Main unit
Input modules cannot
be connected.
Unit No.:I
Module 5 (Location numbers:051 to 060)
Module 4 (Location numbers:041 to 050)
Module 3 (Location numbers:031 to 040)
Module 2 (Location numbers:021 to 030)
Module 1 (Location numbers:011 to 020)
Module 0 (Location numbers:001 to 010)
Subunit DS600
Unit No.:0
Module 3 (Location numbers:131 to 140)
Module 2 (Location numbers:121 to 130)
Module 1 (Location numbers:111 to 120)
Module 0 (Location numbers:101 to 110)
Subunit DS400
Unit No.:1
14
GS 04M01B01-11E
<<Contents>> <<Index>>
■ Name and Function of Each Part
DA100 Stand-alone type (DA100-1)
Installation
holes
Module
connector
Screw holes for
module installation
Status indicator
Power switch
Function grounding
terminal (below power switch)
Feet
Power connector
(when specifying W,
changed to screw terminal)
(when specifying Y,
changed to dedicated connector)
Holes for fastening
the feet
DA100 Expandable type (DA100-2)
Module connector
Lid covering the extension
cable connector
Status indicator
Screw holes for
module installation
Power switch
Function grounding
terminal (below power switch)
Feet
Installation holes
Power connector
(when specifying W,
changed to screw terminal)
(when specifying Y,
changed to dedicated connector)
Holes for fastening the feet
Subunit DS400
Module connector
Lid covering the extension
cable connector
Switch to set the
unit number
Status indicator
Screw holes for
module installation
Power switch
Function grounding
terminal (below power switch)
Feet
Installation holes
Power connector
(when specifying W,
changed to screw terminal)
(when specifying Y,
changed to dedicated connector)
Holes for fastening the feet
GS 04M01B01-11E
15
<<Contents>> <<Index>>
Subunit DS600
Installation
holes
Module
connector
Lid covering the
extension cable
connector
Screw holes for
module installation
Status indicator
Switch to set
the unit number
Power switch
Function grounding
terminal (below power switch)
Feet
Power connector
(when specifying W,
changed to screw terminal)
(when specifying Y,
changed to dedicated connector)
Holes for fastening
the feet
■ Rack Mount Fitting (ANSI/EIA)
DA100 expandable type/DS400 subunit
6.8
482.6
453.2
37.7
177
101.6
14.7
DA100 stand-alone type/DS600 subunit
6.8
482.6
453.2
37.7
177
101.6
14.7
16
GS 04M01B01-11E
<<Contents>> <<Index>>
■ Dimensional Drawings
20
145
Unit: mm
115
DA100 Stand-alone type/Subunit DS600
369
100
422
156
162
22
20
176
168
55
20
115
145
DA100 Expandable type/Subunit DS400
290
336
320
100
22
40
50
165
50
8
If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3 mm.
GS 04M01B01-11E
Subject to change withut notice.
17