Excalibur DBX Manual Remote Digital Line Unit P/N 576051 Rev 1 b Digital Voice Corporation. All rights reserved. 13700 Hutton Drive u Farmers Branch, TX 75234-9005 u 800.777.8329 or 972.888.6300 u FAX 972.888.6380 Contents 1Introduction - - - - - - - - - - - - - - - - - - - - 2Description 1.1 General - - - - - - - - - - - - - - - - - 1 1.2 System Application - - - - - - - - 1 1 - - - - - - - - - - - - - - - - - - - - - 1 2.1 Remote Digital Line Cell - - - - - 1 2.2 Remote Digital Line Unit - - - - - 2 2.3 RDLC PWBA Functions - - - - - 2 2.4 RDLU PWBA Functions - - - - - 5 2.5 Fiber Optic Cable Advantages 5 3Technical Characteristics - - - - - - - - - - - - - - 6 3.1 Power Requirements - - - - - - - 6 3.2 Functional Characteristics - - - 7 3.3 Transmission Medium - - - - - - 8 3.4 Physical Characteristics - - - - - 8 3.5 Environmental Requirements - 8 4Equipment Installation Considerations 4.1 9 RDLU Location - - - - - - - - - - - 9 5Fiber Optic Cable - - - - - - - - - - - - - - - - - -11 5.1 General - - - - - - - - - - - - - - - - - 11 5.2 Outdoor Cable Requirements - 11 5.3 Environmental Considerations 12 5.4 Splicing - - - - - - - - - - - - - - - - - 12 i Remote Digital Line Unit, P/N 576051 Rev 1 b 5.5 Installation - - - - - - - - - - - - - - - 12 5.6 Testing - - - - - - - - - - - - - - - - - 13 6RDLC Installation and Connections - - - - - - - - - 14 6.1 General - - - - - - - - - - - - - - - - - 14 6.2 RDLC Demarcation Box Installation14 7RDLU Installation and Connections - - - - - - - - - 18 7.1 General - - - - - - - - - - - - - - - - - 18 7.2 Installation - - - - - - - - - - - - - - - 18 8.1 General- - - - - - - - - - - - - - - - - - 26 8.2 Remote Digital Line - - - - - - - - 26 8.3 Apply Power - - - - - - - - - - - - - - 26 8.4 Fiber Optic Cable Test - - - - - - 27 8.5 Optional Testing - - - - - - - - - - - 32 8Testing 26 ii Remote Digital Line Unit, P/N 576051 Rev 1 b Figures FIGURE 1. RDLU Equipment Block Diagram - - - - - - -3 FIGURE 2. RDLU Equipment Configuration - - - - - - - -4 FIGURE 3. Single/Double RDLU Floor Plan - - - - - - - -10 FIGURE 4. RDLC PWBA Arrangement - - - - - - - - - - -16 FIGURE 5. RDLC Backplane Cable Connections - - - - -17 FIGURE 6. Fiber Optic Cable Connections - - - - - - - - -21 FIGURE 7. Single RDLU Rack Interconnecting Wiring -24 FIGURE 8. Double RDLU Rack Interconnecting Wiring 25 FIGURE 9. RDLU PWBA Arrangement - - - - - - - - - - -29 FIGURE 10. RDLU Backplane Cable Connections - - - - -30 FIGURE 11. RDLC Loopback - - - - - - - - - - - - - - - - - - -31 FIGURE 12. RDLU PWBA Arrangement - - - - - - - - - - -31 FIGURE 13. RTX and RLC PWBA Component Locations34 iii Remote Digital Line Unit, P/N 576051 Rev 1 b Tables TABLE 1. RDLU Distribution Panel Controls - - - - - - -22 TABLE 2. RDLC and RDLU PWBA Controls and Indicators - - - - - - - - - - - - - - - - - - - - -35 TABLE 3. RDLU Operational Checklist - - - - - - - - - - -37 iv Remote Digital Line Unit, P/N 576051 Rev 1 b SECTION 1 1 Introduction Introduction 1.1 General The RDLU is a self-contained digital/analog line cell that can be located up to 6.2 miles from the controlling telephone system. Longer distances beyond 10 Km are available as special order items. (Contact customer service with specific requirements for evaluation.) The RDLU comes equipped with its own batteries and battery charger which protects service in case of power failure. An RDLU can be equipped to service up to 384 ports. An industry standard fiber optic cable is used to connect the RDLU to the controlling DBX. Two fiber optic conductors are required for every 96 ports on an RDLU. 1.2 System Application 2 The primary purpose of an RDLU is to extend the distance that digital/analog voice telephones and/or data stations can be located from a DBX. Without an RDLU, the maximum wire length distance a digital voice telephone and/or data interface station can be located from a DBX is 3900 feet (0.74 miles). Description 2.1 Remote Digital Line Cell The Remote Digital Line Cell (RDLC) is a one-half cell wide backplane and interfaces to an RDLU. The RDLU is a onequarter cell wide backplane. Each RDLC can be equipped to service up to 96 ports. A second RDLC can be installed in a DBX cabinet when more ports are required. The RDLC power supplies can be mounted on either the left or right side of the cell and near the outside edge of the DBX cabinet. RDLC transceiver printed wiring board assemblies are selected for fiber optic cable lengths of five or ten Km. 1 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 2 Description 2.2 Remote Digital Line Unit An RDLU is available in two configurations. A single RDLU cabinet can be equipped to service up to 192 ports and a double RDLU cabinet can be equipped to service up to 384 ports. A double RDLU occupies the same amount of space as a single RDLU. A double RDLU is equipped with a second RDLU enclosure, a second set of batteries, and larger capacity battery charger. The RDLU is equipped with maintenance-free, rechargeable, sealed batteries that can be charged and discharged in a small room. Variable speed fans are used to control heat inside the cabinet. A ring generator is provided for analog line cards, if equipped. 2.3 RDLC PWBA Functions The remote digital/analog line cell uses four types of Printed Wiring Board Assemblies (PWBA). The following describes basic functions of the PWBAs: A. The Digital Port Controller (DPC) PWBA has a microprocessor that serves as an intelligent interface to the DBX CPU. A remote translator PWBA provides real time control for its associated 48 ports. B. Translator (RTL) PWBA performs interface functions between the digital port controller and the DML-24 channels. C. Remote Link Controller (RLC) PWBA initiates and monitors synchronization between the RDLC and RDLU. D. The Remote Transceiver (RTX) PWBA accomplishes the following functions: 1. The RTX receives incoming data from a fiber optic cable and demultiplexes the data. 2. It multiplexes outgoing data and transmits it onto a fiber optic cable. 2 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 2 FIGURE 1. Description RDLU Equipment Block Diagram 3 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION FIGURE 2. 2 Description RDLU Equipment Configuration Ring Generator Ring Generator RDLU # 2 RDLU RDLU # 1 MANUAL OVERRIDE NORMAL TEST NEG. TEST O F F O F F MANUAL OVERRIDE NORMAL TEST LOAD CONNECTED POS. TEST LOW VOLTAGE DISCONNECT ON O F F AC INPUT OFF POWER ON EQUALIZE R.F.A. H.V.A. L.V.A. NEG. TEST EQ FLOAT ADJ ADJ EQ FLOAT O F F - TP1 TP2 CAUTION Single RDLU Installation LOW VOLTAGE DISCONNECT ON AC INPUT OFF + CAUTION LOAD CONNECTED POS. TEST POWER ON EQUALIZE R.F.A. H.V.A. L.V.A. EQ FLOAT ADJ ADJ EQ FLOAT + - TP1 TP2 CAUTION CAUTION Double RDLU Installation 4 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 2 Description 3. The RTX monitors parity on incoming data and inserts parity bits in outgoing data. 4. The RTX prioritizes requests. 5. The RTX also monitors loopback operations. 2.4 RDLU PWBA Functions The remote digital line unit uses four types of Printed Wiring Board Assemblies (PWBA). The following describes basic functions of the PWBA: 2.5 Fiber Optic Cable Advantages A. The Remote Link Controller (RLC) PWBA functions are the same as described for the RDLC in section 2.3 C. B. The Remote Transceiver (RTX) PWBA functions are the same as described in section 2.3 D. C. The Digital Line Card (DLC) PWBA performs interface functions between eight station multiplexers and a DML-24 channel from the remote transceiver PWBA. Each station multiplexer services three digital voice/data stations. D. The analog line card PWBA performs interface functions between 24 analog line circuits and a DML-24 channel from the remote transceiver PWBA. Fiber optic cable was selected as a conductor for the RDLU because of the following advantages it offers over a metallic conductor. A. An RDLU can service 96 digital or analog stations with a single pair of fiber optic conductors. B. A fiber optic cable is nonmetallic and will not pick up or emit radio frequencies and electromagnetic interfaces, thus eliminating interference caused by closely located lightning and high voltage equipment. C. Electrical power surges are not transmitted to fiber optic cables by lightning and accidental contact with power lines. 5 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 3 Technical Characteristics An RDLU and DBX are better protected from damages by these sources. 3 D. Sparks are not generated by broken fiber optic cables. Thus eliminating possible hazards from a fire, explosion, or electrical shock. This feature makes the fiber optic cable a safer alternative. A fiber optic cable is especially suitable for use in hazardous, flammable, and explosive environments such as petrochemical and mining operations. E. Increased security is provided with a fiber optic cable because electromagnetic eavesdropping devices are rendered ineffective. F. There are no electrical grounding or shorting problems when using a fiber optic cable. Ground loops are completely eliminated. G. Fiber optic cables are much lighter than comparable coaxial cables. Reduced weight can make installations in crowded ducts easier to accomplish. H. Fiber optic cables use standard connectors (ST) along with the link transceivers. Technical Characteristics 3.1 Power Requirements The power requirements for an RDLU are as follows: A. AC power circuit: • • • Dedicated, non-switching circuit. 15 amps for a single RDLU 20 amps for a double RDLU B. AC power Connector: C. A standard 3-prong AC power connector and receptacle is provided. D. AC voltage: 6 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 3 Technical Characteristics • E. AC current: • • 3.2 Functional Characteristics 8 amps maximum and 2 amps nominal for a single RDLU 14 amps maximum and 4 amps nominal for a double RDLU The functional characteristics of an RDLU are as follows: • • • A. B. -54.0 to 54.5 VDC Low voltage disconnect for batteries: • H. -48 VDC Battery charger output voltage: • G. 4 hours Battery voltage: • F. Less than 1 in 100,000,000 (100 million) Minimum hours of operation on battery back-up: • E. 64k bits per second Bit error rate: • D. 96 per fiber optic cable pair (or loop) Data rate per channel: • C. Number of Ports: up to 192 for a single RDLU up to 384 for a double RDLU Number of channels: • -46 VDC Maximum -48 VDC current: • • • • • 3.3 Transmission Medium 120 VAC +/- 10 percent 8 amps for a single RDLU 16 amps for a double RDLU Nominal -48 VDC Power: 60 watts for a single RDLU 120 watts for a double RDLU The transmission mediums for an RDLU are as follows: A. Fiber Optic Cable: 7 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION • • • • 3 Technical Characteristics 62.5/125 or 50/125 micron multimode Five Km (3.1 miles) is the maximum distance with a 1300 nm transmitter. Two conductors are required for each 96 ports nm transmitter. Two Km (1.2 miles) max distance with an 820 nm transmitter. See Sections 5.3 and 5.4 for additional information. Note: The actual distance transmitted will depend on the signal loss (budget). Signal loss is determined by the fiber loss and connector transmission losses. Distances greater than 5 Km are possible. Contact DVC for special cases. 3.4 Physical Characteristics The physical characteristics of an RDLU are as follows: 3.5 Environmental Requirements The environmental requirements for an RDLU are as follows: • • • • • • A. Operating ambient temperature range: • • B. 1500 BTU per hour Operating relative humidity range: • E. 750 BTU per hour Heat generated by a double RDLU: • D. +32°F to +90°F O°C to +32°C) Heat generated by a single RDLU: • C. Width: 21 inches (54 cm) Depth: 24inches (61 cm) Height: 6 feet (1.83 m) Packaging: 19 inch Rack Mountable Components Rack Capacity: 1 or 2 RDLU Weight: single RDLU approximately 220 pounds (100 kg); double RDLU approximately 390 pounds (177 kg) 20 percent to 90 percent non-condensing Storage temperature range: 8 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 4 Equipment Installation Considerations • • F. Storage relative humidity range: • 4 O°F to +140°F -18°C to +60°C) 20 percent to 95 percent non-condensing Equipment Installation Considerations 4.1 RDLU Location. A double RDLU occupies the same amount of space as a single RDLU. Both RDLUs use the same size racks. However, a double RDLU rack contains additional equipment. Figure 3 illustrates the floor plan requirements for a single and double RDLU. The dimensions shown in this diagram are minimum values which can be exceeded, but not decreased. When installing RDLUs in very small rooms, an air vent in the bottom and top of the door is recommended to maintain a desirable operating temperature. 9 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION FIGURE 3. 4 Equipment Installation Considerations Single/Double RDLU Floor Plan Note: 1. The area around an RDLU in this diagram must be kept free of obstructions. 2. Either side of an RDLU can be mounted against a wall. 3. Rotate this diagram 180° to view an RDLU installation on a left wall. 4. The customer shall provide a standard AC power receptacle within nine cable feet from the RDLU power supply. (See Section 3.1). 10 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 5 5 Fiber Optic Cable Fiber Optic Cable 5.1 General This section describes the fiber optic cable specifications to perform properly with an RDLU. This document does not, however, provide a step-by-step installation procedure for the fiber optic cable. (Installation is dependent on the type of cable installed and the equipment available to the installer.) Always consult the fiber optic cable manufacturer for specific handling and installation information. Plan to install an extra pair of fiber optic cables if there is a possibility of upgrading a single RDLU to a double RDLU. The installer usually furnishes the demarcation box for splicing outdoor to indoor cable. Specialized equipment, knowledge, and skills are required to install a fiber optic cable. It may be necessary and/or advantageous to subcontract the fiber optic cable installation to an installer who is equipped to handle this work. 5.2 Outdoor Cable Requirements The RDLU requires an industry standard fiber optic cable. A. The fiber optic cable uses 62.5/125 or 50/125 micron glass fibers. B. The fiber optic cable has loose buffer glass fibers that are tightly secured and break easily when the cable is bent. C. The fiber optic cable uses Kevlar for strength members. (Metal strength members are not recommended because they are more susceptible to damage from lighting.) A multiconductor cable should have two conductors to service each 96 RDLU ports and have extra conductors to allow for breakage and growth. 5.3 Environmental Considerations Environmental considerations determine the type of fiber optic cable to install. The following are examples of factors to consider: 11 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 5.4 Splicing 5 Fiber Optic Cable A. Direct burial installations require a heavy-duty covering. B. Aerial installations require a greater amount of tensile strength. C. Rodent infested areas require an armor type of protection. D. Areas prone to chemical exposure require chemical resistant material. If a fiber optic cable length exceeds two kilometers, a splice is usually necessary as two kilometers is currently the maximum reel length for most industry standard cable. For permanent burial applications, a secure fusion splice is recommended. This method is comparatively expensive. Therefore, a high quality, inexpensive permanent splice may be used. This type of technology is rapidly improving, thus the latest splicing techniques should be investigated before a method is selected. If the cable splice can be located in an accessible area, a disconnectable splice and enclosure can be used. 5.5 Installation. Caution: Special equipment, knowledge, and skills are required to properly install a fiber optic cable. This installation should only be performed by a qualified installer. A. The following precautions apply to fiber optic cable installation. 1. Have the DVC installation representative approve the outdoor fiber optic cable before purchasing the cable. 2. Do not exceed the fiber optic cable loss budget supplied by the DVC installation representative. 3. Install the fiber optic cable in a utility duct or an interduct for added protection. 4. Bury the cable sufficiently if an area is subjected to digging. 12 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 5 Fiber Optic Cable 5. Observe the restraints for bending, twisting, and pulling the cable during installation. 6. Exercise care to avoid damaging existing utilities when digging in easement areas. 7. Perform an attenuation test on a reel of fiber optic cable before it is installed to ensure that it was not damaged during the shipping and handling process. 8. Perform an attenuation test after the fiber optic cable is installed. If damage occurs, a record of the individual fiber conductors’ loss must be presented to the DVC installation representative. B. Dress and number the ends of the fiber optic cable with a breakout kit. Belden Breakout kit number 601343-033, or another equivalent kit, may be used for two to twelve conductor pairs. 5.6 Testing C. Place the ends of the fiber optic cable in a demarcation box where the outdoor cable is connected to the indoor cable. A demarcation box is supplied by the cable installer. D. Underwriter Laboratory (UL) requirements recommend and sometimes require plenum indoor cable. Warning: Avoid direct viewing of a fiber optic cable connected to a light source transmitter. These transmitters produce invisible light waves that can cause permanent damage to the eye. Test the one to two kilometer cable with an 820 nanometer light source and test the five to ten kilometer cable with a 1300 nanometer light source. The maximum amount of attenuation from one demarcation box to the other must be within the loss budget and within acceptance cable and splice specifications. A record of the attenuation level for each fiber conductor should be presented to the DVC installation representative. 13 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 6 6 RDLC INSTALLATION AND CONNECTIONS RDLC INSTALLATION AND CONNECTIONS 6.1 General. If a Remote Digital Line Cell (RDLC) is ordered with a DBX, the DBX will normally arrive with the RDLC preinstalled. If an RDLU is ordered after the applicable DBX is shipped, the RDLC must be installed at the site. Instructions for an RDLC installation are provided in section 576029, System Expansion and Feature Implementation. Printed Wiring Board Assembly (PWBA) locations for the RDLC are displayed in Figure 4 and cable connections to the RDLC backplane are displayed in Figure 5. These illustrations show an RDLC for a double RDLU. If a single RDLU is used, the PWBA will usually be located in cell positions 1 through 50, in order to minimize the length of the power bus connections. 6.2 RDLC Demarcation Box Installation Warning: Avoid direct viewing of a fiber optic cable connected to a light source transmitter. These transmitters produce invisible light waves that can cause permanent damage to the eye. A. A demarcation box is used to connect the outdoor fiber optic cable to the indoor fiber optic cable (Figure 6). An indoor fiber optic cable is provided to connect the RDLC to its demarcation box. Install a demarcation box on a switch room wall that is convenient to the location where the outdoor fiber optic cable will enter the switch room. Warning: The indoor fiber optic cable is sensitive to mechanical stresses such as compressing, stretching, and bending. Install with care and do not crush or secure tightly with wire ties. Do not lay other heavy cables on top of a fiber optic cable. B. Route the indoor fiber optic cable from the RDLC backplane fiber optic connectors to the demarcation box (See Figure 6). 14 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 6 RDLC INSTALLATION AND CONNECTIONS Coil any excess cable in the cable tray, ceiling, or if space permits, in the demarcation box. C. Ensure the DBX is operating properly and all remote digital/ analog line cell PWBA are installed correctly. 15 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION FIGURE 4. 6 RDLC INSTALLATION AND CONNECTIONS RDLC PWBA Arrangement Package contains 816414 and 816415 Each package contains boards and interconnecting flat ribbon cable and 6 Db attentuator spacers. - 2 km package assembly P/N 816427-701 RDLC - 5 km package assembly P/N 816427-702 RDLC 16 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 6 FIGURE 5. RDLC INSTALLATION AND CONNECTIONS RDLC Backplane Cable Connections Fiber optic connectors and optional cable 17 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 7 7 RDLU Installation and Connections RDLU Installation and Connections 7.1 General Inspect all equipment for shipping damage, bent connector pins, and other visible damage. Verify that all items listed on the bill of materials were received. Ensure that all items necessary to complete the installation were received. 7.2 Installation Warning: Avoid direct viewing of a fiber optic cable connected to a light source transmitter. These transmitters produce invisible light waves that can cause permanent damage to the eye. A. A customer-supplied standard, single outlet AC power receptacle must be installed within nine cable feet from the RDLU power supply as noted in Figure 3. B. A sturdy floor is required to support the RDLU. Ensure there is adequate space around the RDLU to provide access for servicing. Position the RDLU for installation as shown in Figure 3. C. Place circuit breakers CB1 and CB2 on the distribution panel in the OFF positions (Figure 2). D. Place the power supply AC POWER and DC POWER circuit breakers in the OFF positions (see Table 2). E. Place the low voltage disconnect panel toggle switch in its NORMAL position (see Table 1). Warning: Use extreme care when installing batteries in an RDLU. Short circuits and incorrect wire connections discharge large amounts of current and can cause injury and equipment damage. F. Install the batteries in the RDLU rack as shown in Figures 7 and 8. Refer to Figure 7 for a single RDLU or Figure 8 for a double RDLU. After the batteries are installed, check for a minimum of -48 VDC across their series connection(s). 18 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 7 RDLU Installation and Connections G. Connect the power supply to AC power and connect a voltmeter to its front panel OUTPUT VOLTAGE test points. Turn on the power supply AC POWER and DC POWER circuit breakers. Set its output voltage from -54.0 to -54.5 VDC. The power supply should be charging the RDLU batteries. H. Install the distributing frame(s) on a wall that is convenient to the RDLU and the interconnecting station wiring. I. Install the station multiplexers, digital voice telephones, and data interface instruments (if applicable) in accordance with the instructions provided in section 576015 Digital Voice/ Data Station Instruments Installation and Maintenance. J. A demarcation box is used to connect the outdoor fiber optic cable to the indoor fiber optic cable. An indoor fiber optic cable is provided to connect the RDLU with its demarcation box. Install a demarcation box on a wall that is convenient to the location where the outdoor fiber optic cable enters the room. Warning: The indoor fiber optic cable is sensitive to mechanical stresses such as compressing, stretching, and bending. Install with care and do not crush or secure tightly with wire ties. Do not lay other heavy cables on top of a fiber optic cable. K. Route the indoor fiber optic cable from the RDLU backplane fiber optic connectors to the demarcation box. Coil any excess cable in the cable tray or, if space permits, in the demarcation box. L. Connect the indoor fiber optic cable located in the demarcation box to the outdoor fiber optic cable. (Perform this step if the outdoor fiber optic cable is installed.) M. Ensure circuit breakers CB1 and CB2 on the distribution panel are in the OFF positions (see Table 1). CB1 supplies 19 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 7 RDLU Installation and Connections the power for the boards and CB2 supplies the power for a ring generator, if equipped for analog phones. N. If installing a double RDLU, perform the following steps on the lower RDLU PWBA enclosure (RDLU #1): 1. Remove the screws securing the front cover to the RDLU PWBA enclosure and open the front cover. 2. Unplug all printed wiring board assemblies in the RDLU PWBA enclosure, except the power supply, and pull them out approximately two inches from their inserted positions. Do not remove the PWBA from their RDLU enclosure slots. 3. Check the battery voltage for -54.0 to -54.5 VDC before continuing with this procedure. Check the meter. 4. Place circuit breaker CB1 on the distribution panel in the ON position. 5. Verify that the green lamp on the front of the PWBA enclosure DC power supply illuminates. • Verify illumination of the green LEDs on the back of the RDLU PWBA enclosure backplane for the following voltages: • +5.00 Vdc • -5.00 Vdc • -48 Vdc 6. Place circuit breaker CB1 on the distribution panel in the OFF position. 7. Insert all printed wiring board assemblies in the RDLU PWBA enclosure backplane (Figure 9). Note: If the backplane connectors do not align with the PWBA connectors, loosen the backplane mounting screws to allow backplane movement. Insert all PWBA in the backplane. Retighten the backplane mounting screws. 8. Close and secure the RDLU enclosure front cover. Ensure that the fans are rotating. 9. Place circuit breaker CB1 on the distribution panel in its ON position. 20 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 7 RDLU Installation and Connections 10. If installing a double RDLU, repeat steps 2 through 11 on the upper RDLU PWBA enclosure (RDLU #2), substituting circuit breaker CB2 on the distribution panel for CB1. 11. After installation is complete, bolt the RDLU cabinet to the floor. FIGURE 6. Fiber Optic Cable Connections 21 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION RDLU Installation and Connections RDLU Distribution Panel Controls TABLE 1. Step 7 Control Type Function 1 CB1 Circuit Breaker Connects RDLU enclosure number 1 (lower position) to battery power. 2 CB2 Circuit Breaker Connects RDLU enclosure number 2 (lower position) to battery power. 3 AC Power Circuit Breaker Supplies 117 VAC input power to the power supply. 4 DC Power Circuit Breaker Supplies DC power to the output connector and terminal blocks. 5 Load Distribution Fuse Holder Not used in the RDLU application. Fuses can be inserted in this holder allowing fused AC power to be distributed from terminal blocks on the back of the power supply. 6 AC Power On Green Light Illuminated while 117 VAC input power is operating the power supply. 7 HV Shutdown Red Light Illuminates when the DC output voltage is automatically turned off, after exceeding -60 VDC. 8 Low Current Red Light Illuminated when the output current is less than 0.06 amps. 9 Output Voltage Test Points + and - test provide access to the DC output voltage with a voltmeter or other test equipment. 10 Output Voltage Adjust Slot Screw Adjusts the maximum value of the DC output voltage. 11 Manual Override Toggle Switch When placed in the MANUAL OVERRIDE position, the RDLUs remain connected to the batteries regardless of battery voltage. 22 Remote Digital Line Unit, P/N 576051 Rev 1b 7 SECTION RDLU Installation and Connections RDLU Distribution Panel Controls (Continued) TABLE 1. Step Control Type Function Normal Toggle Switch In the NORMAL position, the RDLUs are connected to the batteries while the battery voltage is greater than -46 VDC. The RDLUs are automatically disconnected if the battery voltage drops below -46 VDC. Test Toggle Switch In the TEST position, a low battery voltage condition is simulated and the RDLUs should automatically disconnect from the batteries. 12 Load Connected Green Light Illuminates while the RDLUs are connected to the batteries. 13 NEG Test Test Point Provides access to the negative side of the battery voltage with a voltmeter or other test instrument. 14 POS Test Test Point Provides access to the positive side of the battery voltage with a voltmeter or other test instrument. 15 Fuse 3 AG 1 amp Provides over current protection for the panels internal circuitry. The RDLUs are automatically disconnected from the batteries if the panels internal circuitry fails and/or this fuse opens. If the panels circuitry fails, the RDLUs can be manually reconnected to the batteries without low voltage disconnect protection by placing the toggle switch in the MANUAL OVERRIDE position. 23 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION FIGURE 7. 7 RDLU Installation and Connections Single RDLU Rack Interconnecting Wiring Note: 1. The building ground can be connected here if the 120 VAC safety ground is not available at the power receptacle. 2. The power supply is equipped with a nine-foot AC power cord. Connect this cord to a dedicated nonswitching 120 VAC 15 amp circuit. DO NOT CONNECT THE BUILDING GROUND TO THE RDLU. 24 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 7 FIGURE 8. RDLU Installation and Connections Double RDLU Rack Interconnecting Wiring Note: 1. The building ground can be connected here if the 120 VAC safety ground is not available at the power receptacle. 2. The power supply is equipped with a nine-foot AC power cord. Connect this cord to a dedicated nonswitching 120 VAC 15 amp circuit. DO NOT CONNECT THE BUILDING GROUND TO THE RDLU. 25 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 8 Testing Testing 8.1 General The Remote Digital/Analog Line Cell and Remote Digital/ Analog Line Unit uses identical PWBA cell power supplies but different remote transceiver PWBA and remote port controller PWBA. The RDLC uses 816414 (RLC) and 816415 (RTX). The RDLU uses 770079 (RLC) and 770080 (RTX). Table 2 describes the controls and indicators that are common to both the remote digital line cell and the remote digital line unit. 8.2 Remote Digital Line A fiber optic meter is required for reading light levels at the transmitter and receiving ends of both fibers. The meter must be capable of measuring 820 nm or 1300 nm depending upon the short or long transceivers. The Laser Precision AM-3500 power meter with ST style connector interface or a standard voltmeter are recommended. Perform the following test procedure when installing the Remote Digital Line equipment: 1. Apply Power • • RDLC RDLU 2. Check fiber optic cable attenuation light levels. 3. Optional Testing • • 8.3 Apply Power RDLC Loopback Test RDLU Loopback Test Use the following procedures to test the RDLC (switch side): RDLC (Switch Side) 1. Insert all boards into the RDLC beginning with the power supply. Verify the switches on the remote controller at both ends of the link are set to the following normal positions: 26 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 Testing • Push in the lower portion of both rocker switches S3 and S4. • Place the S2 loopback toggle switch in the UP position. 2. The green lamp on the front of the card edge power supply must illuminate. 3. Using a voltmeter verify the +5 volts is within range +/0.25 volts. Apply probes to capacitor C5 (See Figure 12) on the RLC board (remote link controller). The lower lead is the positive (+) side. If the power is not within tolerance, replace the power supply. Use the following procedures to test the RDLU (Remote End): 1. Turn the CB1 and CB2 and the AC and DC circuit breakers circuit breakers OFF. 2. Turn the AC and DC circuit breakers ON. Check the output voltage for -54.0 to -54.5 VDC across the batteries. Adjust the voltage, if necessary, by the adjustment on the front panel of the power supply. 3. Turn CB1 to ON position. This will send DC power to the RDLU enclosure box. If a second RDLU is equipped, turn CB2 ON. Perform check as in steps 2 and 3 above. 8.4 Test Fiber Optic Cable Attenuation Light Levels Use the following procedures to test the fiber optic cable attenuation light levels. 1. Verify the fiber optic transmitter on each end is transmitting at an acceptable power level. Use a fiber optic meter to connect to the transmitter daughter card of the transceiver PWBA. The transmitter is the lower daughter board. • An acceptable level is greater than -17 dBm for 820 or 1300 nm. 2. Connect the fiber optic meter at the receive end of the cable. • An acceptable level is (820nm)-29.6 to -36.2 dBm. • An acceptable level is (1300nm)-11.3 to -36.8 dBm. 27 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 Testing An attenuator spacer (or in-line attenuator) should be used to reduce the power level if the level exceeds the upper limit. The more negative the dBm, the weaker the signal. Note: The 1300 nm receiver will self-adjust to an extent and should not need an attenuator. Try connecting the link and test for misframes (CR3) and or parity errors (CR2). See Figure 12. If there are no errors, the link is acceptable. 3. If an attenuator is required a 6dBm at 820 nm or 11dBm at 1300 nm spacer is included with the boards. The same spacer has different attenuator levels for different frequencies (820 or 1300 nm). The attenuator spacer always goes at the transmitter end of the cable. Call customer service in the event more attenuation is necessary for either a 10 or 15 dBm in-line attenuator. One in-line attenuator is used for each strand. Two are required for both strands. 4. Connect all fiber cables once proper attenuation levels are achieved. The lamps on the link controller board should indicate the following: • CR3 misframe lamp extinguishes in 3-10 seconds. • CR1 green heartbeat lamp blinks. • CR4 loopback lamp is OFF. • CR10 loss of clock lock lamp should be OFF (n/a at RDLU side). • CR2 parity lamp should be OFF. If the link does not operate properly verify that the attenuation levels are within acceptable limits. A loopback test may isolate the trouble. This concludes the hardware installation test for the link. Proceed to system testing by making phone calls. 28 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 FIGURE 9. Testing RDLU PWBA Arrangement Note: See section 576015 “Digital Voice/Data Station Instruments Installation and Maintenance Practice” for a listing of connections to the multiplexors and associated stations. Note: Each package contains P/N 770079 and P/N 770080 boards and interconnecting flat ribbon cable and 6 Db attenuator spacer. • • 2 Km Package Assembly P/N 770427-703 5 Km Package Assembly P/N 770427-701 29 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION FIGURE 10. 8 Testing RDLU Backplane Cable Connections Note: See Section 576015 “Digital Voice/Data Station Instruments Installation and Maintenance Practice” for a listing of connections to the multiplexors and associated stations. J-3, J-4, J-6, J-8 NOT USED FOR RDLU INSTALLATION 30 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 FIGURE 11. Testing RDLC Loopback Note: Tests the RDLC only, less the fiber transensors. FIGURE 12. RDLU PWBA Arrangement Note: Remote digital line unit loopback test checks the RDLU transmitter and receiver, the two fiber optic conductors, and the RDLC transmitter and receiver. The fiber optic cable must be connected. 31 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8.5 Optional Testing 8 Testing Use the following procedures for optional testing requirements. 1. RDLC loopback testing. This test loopbacks the digital output before the optical transceivers. It is designed to test the digital signal to and from the daughter fiber cards but does not test the daughter cards. To test the daughter cards requires a loopback fiber cable with acceptable attenuation to not overdrive the receiver. Note: Loopback operation will cause all service channels to be out of service. 2. Place the RTX PWBA in the loopback mode by setting switch S2 in the DOWN position. 3. Observe the lamps: • The CR3 misframe lamp should extinguish in 3 to 10 seconds. • The CR1 green heartbeat lamp should blink. • The CR4 Loopback lamp should illuminate. • Disregard any indications from the CR2 parity lamp. If the test fails, suspect the RTX and/or the RLC board. 4. Go to normal mode by setting S2 in the UP position. End RDLC loopback testing. 1. RDLU loopback testing. Note: Loopback operation will cause all service channels to be out of service. 2. Place the RTX PWBA in the loopback mode (Figure 11) by setting switch S2 in the DOWN position. 3. Observe the lamps: • The CR3 misframe lamp should extinguish in 3 to 10 seconds. • The CR1 green heartbeat lamp should blink. • The CR4 loopback lamp should illuminate. • Disregard any indications from the CR2 parity lamp. 32 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 Testing If the test fails suspect the fiber cable or fiber tranceivers. If this test passes but the RDLU does not work properly out of loopback, suspect the RTX and/or the RLC board(s). End RDLU loopback testing. 33 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION FIGURE 13. 8 Testing RTX and RLC PWBA Component Locations 34 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 TABLE 2. Testing RDLC and RDLU PWBA Controls and Indicators Control or Indicator Type Function System Clock (CR10) Red LED Lights when the RDLC loses phase locking to the DBX system clock. This indicator is inactive when its PWBA is installed in an RDLU. Parity Error (CR2) Red LED Flashes when a frame with an even parity error is received. Heartbeat (CR1) Green LED Flashes when the micro CPU is executing. Misframe (CR3) Red LED Lights when a loss of sync occurs on the transmission link. All ports will be down and purged during this time. Once the cause of failure is removed, three to ten seconds are needed to reestablish link synchronization and restoration of ports. Loopback (CR4) Red LED Lights when the PWBA is in a loopback test mode. Loopback (S2) Toggle Switch 2-position UP is the normal position for this switch, allowing a software command to initiate a loopback test. DOWN position manually places the PWBA in a loopback test mode (see Figure 11). CPU Reset (S1) Push Button 35 Remote Digital Line Unit, P/N 576051 Rev 1b Momentarily pressing this button purges all calls, terminates existing operations, and initiates the cold start sequence. A link reset is also initiated causing the communications link to go down and resynchronize. SECTION TABLE 2. Control or Indicator 8 Testing RDLC and RDLU PWBA Controls and Indicators Type Function Inject Parity Errors (right DIP Switch side of S3) The switch is inactive (normal position) when the lower portion of its rocker is pushed in. The active position injects parity errors in the transmission link to check the parity tester on the receiver circuit for an error indication. It is active when the upper portion of its rocker is pushed in. DIP Switch Loopback Disable (left side of S3) (Software and Hardware) This switch prevents the PWBA from entering the loopback test mode when the upper portion of its rocker is pushed in. It permits loopback testing on the PWBA when the lower portion of its rocker switch is pushed in (normal position). It is now in the upper portion. Expansion (S4) This switch is provided for future expansion.The lower portion of both rockers are pushed in its normal position. DIP Switch 36 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 Testing RDLU Operational Checklist TABLE 3. Date: Performed by: Place an X in the box when the task is complete. Check all RDLU wires and cables for secure connections. Check that the RDLU enclosure fan is circulating air. Measure and record the battery voltage (see section 8.3). -54.0 to -54.5 VDS measured value is: Measure and record the power supply +5VDC output (see section 8.3). +5.00 +/- -0.25 VDC measured value is: Perform a loopback test and check for correct indications (see section 8.5). Check all systems for correct positions (see section 8.3). Check all lamps for correct indications (see section 8.4). Measure and record the transmitter dBm power levels (see section 8.4). -17 dBm minimum from a 1 to 2 km 820 nanometer transmitter measure value is: -17 dBm minimum from a 2 to 5 km 1300 nanometer transmitter measured value is: Measure and record the receiver dBm power level (see section 8.4). Measured value is ____________________ RDLU __________________ RDLC. For 820 nm -29.6 dBm maximum to -36.2 dBm minimum. For 1300 nm -11.3 dBm maximum to -36.8 dBm minimum. 37 Remote Digital Line Unit, P/N 576051 Rev 1b SECTION 8 Testing 38 Remote Digital Line Unit, P/N 576051 Rev 1b