The part no of this guide is 39214-074/Issue 3 LED Indicators Two LEDs are fitted to the PCB to indicate functions as follows: ! SOUNDERS ON ! FAULT Illuminated red when sounder relay is energised Illuminated yellow under any fault condition (except group address conflict) Functional Test Data OUTPUT BIT FUNCTION INPUT BIT FUNCTION 2 GROUP MODE* 2 GROUP MODE 1 PULSED MODE 1 PULSED MODE CONFIRMED CONTINUOUS MODE 0 0 1 = OFF 0 = ON 1 = ON 0 = OFF 1 = ON 0 = OFF 1 = GROUP 0 = INDIVIDUAL 1 = ON 0 = OFF CONTINUOUS MODE CONFIRMED 1 = ON 0 = OFF *Note: group mode is disabled if the group address DIL switch is set to ‘0000’, irrespective of the protocol message Troubleshooting Before investigating individual units for faults, it is very important to check that the system wiring is fault free. Earth faults on a data loop or any ancillary zone wiring may cause communication errors. Many fault conditions are the result of simple wiring errors. Check all connections to the unit and make sure the correct value resistors are fitted where necessary. Fault Finding Problem No response or missing Fault condition reported Sounders do not operate Sounders operate continuously Analogue value unstable FIRE DETECTORS LIMITED Possible Cause Incorrect individual address setting Incorrect loop wiring Incorrect group or individual address setting Incorrect wiring of sounder zone or fault input Faulty sounder Local supply faulty or polarity incorrect Fuse blown on sounder PCB Incorrect wiring Incorrect group address setting Fuse blown on sounder PCB Incorrect cause and effect programming Faulty sounder Panel fault Incorrect sounder zone wiring Dual address Loop data fault, data corruption For a full technical specification of the Sounder Control Unit, please refer to the XP95 Sounder Control Unit PIN Sheet, PP2019. XP95 Sounder Control Unit Installation Guide General The XP95 Sounder Control Unit, part no 55000-823, is supplied with a backbox for surface mounting. It is also available without a backbox for flush fitting — part no 55000-824. For flush fitting the installer will need to provide a suitable metal box with fixing centres of 120.6mm (UK standard 2-gang accessory box). Note: The XP95 Sounder Control Unit is not designed for outdoor use unless it is mounted in a suitable weatherproof enclosure. Surface Mounting 1. Mount the back box as required and install all cables for termination. Ensure that earth continuity is maintained. 2. Remove the cover plate (if secured) from the Sounder Control Unit assembly by inserting the blade of a terminal screwdriver into each of the four securing clips in turn, gently prising the outer edge of the cover plate over the clips underneath. DO NOT USE EXCESSIVE FORCE. 3. Terminate all cables. 4. Gently push the completed assembly towards the back box until the mounting holes are aligned and secure with the two mounting screws provided. DO NOT OVERTIGHTEN. 5. Set the address of the unit as shown on page 3. 6. Finally, when commissioning is complete, fit the cover plate by placing it in position, observing the correct orientation (LEDs on the PCB must be aligned with viewing holes). Apply pressure to the cover plate until all four clips are holding it in position. Flush Mounting 1. Secure a suitable metal back box (30mm minimum depth) in position and install all cables for termination. Ensure that earth continuity is maintained. 2. Follow steps 2 to 6 as above. Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754 Email: techsales@apollo-fire.co.uk Website: www.apollo-fire.co.uk 4 1 addr Wiring Details All wiring terminals accept solid or stranded cables up to 2.5mm². LOCAL POWER SUPPLY L2 (+ve)* SOUNDER – L1 (–ve)* SOUNDER + Vex – Vex + { { NORMALLY CLOSED FAULT CONTACT FUSE N/C COM N/O FAULT INPUT FAULT INPUT NOT USED (WIRE LINK MUST BE FITTED) NORMALLY OPEN FAULT CONTACT { { SOUNDERS WITH POLARISING DIODES XP95 LOOP 10KΩ EOL DIL switch setting 1234567 Address Setting The Sounder Control Unit is designed to be polled by the control panel in two ways, individually or as part of a group. Two DIL switches are provided for setting the addresses. DIL switch setting 1234567 addr DIL switch setting 1234567 addr DIL switch setting 1234567 11 12 13 14 15 16 17 18 19 20 1101000 0011000 1011000 0111000 1111000 0000100 1000100 0100100 1100100 0010100 21 22 23 24 25 26 27 28 29 30 1010100 0110100 1110100 0001100 1001100 0101100 1101100 0011100 1011100 0111100 31 32 33 34 35 36 37 38 39 40 1111100 0000010 1000010 0100010 1100010 0010010 1010010 0110010 1110010 0001010 41 42 43 44 45 46 47 48 49 50 1001010 0101010 1101010 0011010 1011010 0111010 1111010 0000110 1000110 0100110 51 52 53 54 55 56 57 58 59 60 1100110 0010110 1010110 0110110 1110110 0001110 1001110 0101110 1101110 0011110 61 62 63 64 65 66 67 68 69 70 1011110 0111110 1111110 0000001 1000001 0100001 1100001 0010001 1010001 0110001 71 72 73 74 75 76 77 78 79 80 1110001 0001001 1001001 0101001 1101001 0011001 1011001 0111001 1111001 0000101 81 82 83 84 85 86 87 88 89 90 1000101 0100101 1100101 0010101 1010101 0110101 1110101 0001101 1001101 0101101 91 92 93 94 95 96 97 98 99 100 1101101 0011101 1011101 0111101 1111101 0000011 1000011 0100011 1100011 0010011 101 102 103 104 105 1010011 0110011 1110011 0001011 1001011 106 107 108 109 110 0101011 1101011 0011011 1011011 0111011 111 112 113 114 115 1111011 0000111 1000111 0100111 1100111 116 117 118 119 120 0010111 1010111 0110111 1110111 0001111 121 122 123 124 125 126 1001111 0101111 1101111 0011111 1011111 0111111 Group Address Setting In Group mode the Sounder Control Unit responds to an additional address referred to as the “group address”, which is used to activate groups of Sounder Control Units simultaneously. (The unit continues to respond to its own individual address and report its status from that address in the normal way.) The group address is selected by the four-segment DIL switch which is factory-set to 0000. A group address may be any spare address within – and only within – the range 112 to 126 inclusive. The required group address is set by moving one or more of the segments on the switch to “1”. The following table shows the settings for the group address switch. Fuse: 1.25A, anti-surge Local supply: 24V (9V min, 32V max) Sounder zone end-of-line resistor: 10KΩ, ¹/3Watt 2.6mA 1.9mA 1.7mA 3.6mA addr 1000000 0100000 1100000 0010000 1010000 0110000 1110000 0001000 1001000 0101000 addr switch-on surge, max 100 mS quiescent sounders operated fault DIL switch setting 1234567 1 2 3 4 5 6 7 8 9 10 * L1 and L2 are polarity insensitive, but, for the sake of consistency, it is recommended that L1 be kept negative Maximum current consumption at 24V addr 112 113 114 115 116 117 118 119 120 DIL switch setting 1248 1111 0111 1011 0011 1101 0101 1001 0001 1110 addr 121 122 123 124 125 126 DIL switch setting 1248 0110 1010 0010 1100 0100 1000 Note: one switch is sealed with a sticky label. This label should not be removed unless the unit is to be controlled as part of a group. Commissioning It is important that the Sounder Control Unit be fully tested after installation. An XP95 Test Set, part no 55000-870, may be used to carry out functional testing of individual units. It can also be used to perform data integrity tests of an entire system. Individual Address Setting The individual address of the Sounder Control Unit is set using the seven-segment DIL switch. Each segment of the switch must be set to “0” or “1”, using a small screwdriver or similar tool. A complete list of address settings is shown opposite. The cause and effect programming (the control panel software responsible for switching sounders and outputs etc. in alarm condition) should be fully checked, along with all equipment connected to the Sounder Control Unit. 2 3