City of Atchison Animal Control Building Addition 10/20/2015

advertisement
City of Atchison
Animal Control Building Addition
10/20/2015
Contractors,
The City of Atchison is looking for proposals on building an addition to the Animal Control facility,
located at 1801 Main Street, Atchison, KS 66002.
This new addition will project to the north of the existing building and will house a new clothes washer
& dryer, a central HVAC unit and 3 additional dog pens. Due to space restrictions, the existing animal
control facility will remain operational during construction.
Bid submittals must be in a sealed envelope and delivered to the City of Atchison, Public Works Office
located at 1801 Main Street, Atchison, Kansas 66002. Envelope must be labeled 'Animal Control
Addition'. All bids must be received no later than 2:00PM on November 9, 2015. A public bid opening
will occur at 2:00PM on November 9, 2015 at the Public Works Office. A NOA will be issued on
November 17, 2015 pending approval from the City Commission. Substantial completion date is March
17, 2016 with the final completion date of April 7, 2016.
General NotesWater supply lines and electrical conduit may be surface mounted, but concealed in the new addition
ceiling as much as possible. All surface mounted conduit shall be restricted to the interior of the
building. Conduits penetrating the ceiling shall be sealed to prevent any air intrusion. Sealant shall
match surrounding finish. Any water piping that is not in a conditioned space must be insulated.
Dog Pen Fence RequirementsAll dog pens shall have a minimum 72" high gate for access from the interior and the exterior. Exterior
pens shall have fencing fabric Specs are below







Frame shall be minimum 1 ⅞" welded with middle brace
Fabric shall be 6 gauge with 2" mesh
Tension bars used to stretch fabric with tension bands every 12"
Tie wire used at top & bottom of fabric shall be 6 gauge
Terminal posts min size 2 ⅞ O.D. to terminate within 6" of finished ceiling
(2) Fork latches mounted at 24" & 48" from bottom of gate frame
All materials are to be commercial grade and galvanized unless otherwise approved
Footings for terminal posts shall be 10" diameter x 36" depth
Wall & floor finishAll interior & exterior wall surfaces of the new addition (including 1 exterior wall surface that is now an
interior wall) shall be finished with 580 & 590 multi-purpose epoxy followed by Carboguard 890 with a
Carbothane clear coat. The interior floor surface of the new addition shall be finished with Carboguard
890 and a Carbothane clear coat. The spec sheets for these products are attached. The City of Atchison
City of Atchison
Animal Control Building Addition
10/20/2015
will specify color of finishes and chips to be added to the coatings. Contractor responsible for providing a
color chart. For additional details on these products, installing techniques or ordering, please contact
Gilbert Carlon with Spectra Industrial at 913-269-6786.
All material, workmanship and installation shall be in accordance with the 2012 plumbing code, 2012
electrical code, 2012 mechanical code and 2012 building code. This project is tax exempt. All dimensions
are estimates and it is the contractors responsibility to field verify all items prior to bidding.
Thanks,
Andrew Dilts
Public Works - Project Manager
Andrewd@cityofatchison.com
City of Atchison
1801 Main Street
Atchison, KS 66002
913.367.5561
ADDENDUM - 1
This addendum dated October 30, 2015 applies to:
Animal Control Building Addition
Notice to All Potential Bidders:
This addendum has been issued to clarify HVAC specifications for the building addition project.
Description:







3-Ton 13 Seer Heat Pump Unit – 15 kW Electric
Compressor Sound Blanket
Filter Drier System
Additional 4-5" Media Air Filter
Insulated Duct in Attic with a Single Vent for each Kennel Stall
Common Air Return
Carrier Brand or Equivalent
Location: Per Drawing – Northeast Corner of Addition
Contact:
Andrew Dilts or Clinton McNemee
913-367-5561
andrewd@cityofatchison.com, clintonm@cityofatchison.com
ADDENDUM - 2
This addendum dated November 4, 2015 applies to:
Animal Control Building Addition
Notice to All Potential Bidders:
This addendum has been issued to clarify HVAC specifications for the building addition project.
HVAC modification:
•
•
•
3-Ton 14 Seer Heat Pump Unit - 15 kW Electric - As of January 1, 2015, the Department of Energy has required
that all heat pumps manufactured have to be rated at a minimum 14 seer and 8.0 HSPF. For more information
on this, please see on page 2.
Insulated Duct in Attic with a Single Vent for each Kennel Stall, adequate venting in office/restroom area with an
adjustable damper accessible from the finished space, and extra vents as required in new building addition
Thermostat shall be located in office
Contact:
Andrew Dilts or Clinton McNemee
913-367-5561
andrewd@cityofatchison.com, clintonm@cityofatchison.com
1
eAPB1410
May 5, 2014
o
2015 Federal Regional Standards for
Heating and Cooling Products
On April 24, 2014, the Department of Energy and the American Public Gas Association (APGA)
reached a settlement agreement on the implementation of the Federal Regional Standards.
Conditions under the terms of the agreement are outlined below.






Important Notes:
Additional notifications will
be sent throughout the
rest of the year to clarify
the impact of these
Federal Regional
Standards.
The Federal Regional Furnace Efficiency Standards, which were originally scheduled for
implementation in May of 2013, will be removed. A new rulemaking process will begin to
evaluate future changes to furnace efficiency standards.
Federal Regional Standards for cooling equipment will go into effect as planned on January
1, 2015. All air conditioners (A/C) and heat pumps (H/P) (split system and packaged)
manufactured after December 31, 2014 must comply with these Federal Regional
Standards.
The Federal Regional Standards for air conditioners sold in the south and the southwest is
based on the date of installation; however, the industry will have an 18 month sell-through or
grace period (starting on 1-1-2015). Original equipment manufacturers, distributors and
dealers will be allowed to buy, sell, ship and/or install non-compliant products (13 SEER)
during this period as long as they are manufactured prior to January 1, 2015.
Split system and packaged heat pumps are not subject to the 18 month sell-through or
grace period, as the standard applied is based on the date of manufacture. Split system and
packaged heat pumps manufactured before January 1, 2015 can be sold after January 1,
2015 for as long as inventory exists.
The Department of Energy (DOE) will issue, and publish on its appliance and equipment
standards website, an enforcement policy statement clarifying the agency’s policy for
enforcing the Federal Regional Standards for split system air conditioners. The industry will
work with the DOE to develop these enforcement standards.
Federal regional efficiency requirements are summarized in the illustration below.
Packaged Units
A/C: 14 SEER
H/P: 14 SEER, 8.0 HSPF
Split Systems
A/C: 13 SEER
H/P: 14 SEER, 8.2 HSPF
We will also be
providing information
regarding new products
that are being
developed to comply with
these Federal Regional
Standards.
Packaged Units
A/C: 14 SEER, 11 EER
H/P: 14 SEER, 8.0 HSPF
Split Systems
A/C: 14 SEER, 12.2 EER ≤ 3.5 tons, 11.7 EER ≥ 4 tons
H/P: 14 SEER, 8.2 HSPF
Packaged Units
A/C: 14 SEER
H/P: 14 SEER, 8.0 HSPF
Split Systems
A/C: 14 SEER
H/P: 14 SEER, 8.2 HSPF
Download