Desktop Instruction – Method to Adjust IST Data to the EDG Frequency Administrative Limit to Verify that the Result Remains Within Surveillance Acceptance Criteria PURPOSE This method considers the effects of variations in EDG frequency on the operation of safeguards pumps that can be loaded on the EDGs. It provides a check to verify the safeguards pumps remain operable considering the administrative limit on the EDG frequency range from 59.5 Hz to 60.5 Hz. The evaluation adjusts IST data using pump affinity laws and compares the results to surveillance procedure acceptance criteria. This evaluation provides reasonable assurance that the components affected by EDG frequency variation can fulfill their functional requirements. BACKGROUND Technical Specification 3.8 (specifically SRs 3.8.1.6 and 3.8.1.9) require EDG frequency to be within a range of 58.8 to 61.2 Hz. This range in frequency is +/- 2% of 60Hz. The effects of this frequency variation were not previously considered in analyses for system performance. This method will consider the affects of a frequency range from 59.5 Hz to 60.5 Hz on the performance of safeguards pumps. The frequency effects on motor and centrifugal pump operation are: Motor speed is proportional to frequency. n2/n1 = Hz2/Hz1 Centrifugal pump flow rate is proportional to motor speed. (n2/n1) = (Q2/Q1) Thus, if the EDG frequency is at 59.5 Hz/60 Hz or 0.9917, then the pump flow rate could be reduced by approximately 1%. Centrifugal pump discharge pressure is proportional to motor speed squared. (n2/n1)2 = P2/P1 Thus, if the EDG frequency is at 60.5 Hz/60 Hz or 1.0083, then the discharge pressure could be increased by approximately 1.0167%. Page 1 of 2 D:\533561246.doc Desktop Instruction – Method to Adjust IST Data to the EDG Frequency Administrative Limit to Verify that the Result Remains Within Surveillance Acceptance Criteria METHOD 1.0 2.0 3.0 4.0 Obtain the completed SP and its IST data. Determine if the SP acceptance criteria is: 2.1 A defined range of numerical values for TDH, or 2.2 A graphical solution that uses a plotted point of flow and TDH. If it is 2.1, then go to step 4.0; otherwise, verify it is 2.2 and go to step 5.0. Adjust the TDH value to check that it remains within the lower and upper acceptance criteria. 4.1 For the lower limit, multiply the TDH data by 0.9834. This value defines the 59.5 Hz lower performance point. 4.2 For the upper limit, multiply the TDH data by 1.0167. This value defines the 60.5 Hz upper performance point. 4.3 Compare these values to the SP acceptance criteria. 4.4 If they remain within the acceptance criteria, then document the acceptable result in the comments section of the SP. If either one is outside of the acceptance criteria declare the pump inoperable and initiate a CAP. Head Correction Value 5.0 Lower 0.9834 Upper 1.0167 Adjust the head and flow values that are plotted to obtain a graphical solution to check that the point remains within the lower and upper acceptance criteria. 5.1 For the lower limit, multiply the TDH data by 0.9834, and the flow data by 0.9917. These values define the 59.5 Hz lower performance point. 5.2 For the upper limit, multiply the TDH data by 1.0167, and the flow data by 1.0083. These values define the 60.5 Hz or upper performance point. 5.3 Plot these points on the figures for the SP acceptance criteria. 5.4 If they remain within the acceptance criteria, then document the acceptable result in the comments section of the SP. If either one is outside of the acceptance criteria declare the pump inoperable and initiate a CAP. TDH Correction Value Flow Correction Value Lower 0.9834 0.9917 Page 2 of 2 D:\533561246.doc Upper 1.0167 1.0083