Liquid Ring Water Sealed Partial Recirculating Continuous On Demand Vacuum System (See page 3 for information to fill in the blanks) Ohio Medical Healthcair® Series Model ______ "Continuous On Demand" packaged system. The ___________, partial recirculating, medical vacuum system shall consist of ____ electric motor driven positive displacement non-pulsating liquid ring vacuum pumps, _______ ASME receiver and an Underwriters Laboratories listed ______ electrical control system mounted in a NEMA 12 enclosure. The components shall be assembled on a ____ to accommodate most existing doorways. The system shall include interconnecting piping and wiring to provide a functional operating package with applicable electrical and plumbing connections at the installation site. Each liquid ring vacuum pump shall have a cast iron body, bronze impeller, and mechanical seals. The packaged unit shall be factory tested prior to shipment and warranted for 24 months from date of shipment. The capacity of each pump shall be _____ SCFM @ 19” Hg, when direct driven by a ____ HP, TEFC motor, operating on ___ Volts-60 Hz. Each pump will require _____ GPM of 59oF cooling water. Pump suction accessories shall include an inlet check valve, isolation valve and inlet flexible connector. Pump discharge accessories shall include a discharge air/water separator constructed of high density polyethylene that also serves as the partial recirculation reservoir (Models LP30 and 40 utilize a steel water/air separator). The recirculation reservoir shall have a two station combination level sensor/ sight glass to maintain proper liquid level. Recirculation liquid control will be interactive through a temperature sensor, with a range of 75F to 90F. Each recirculation liquid line shall include a strainer and isolation/flow regulation valve. The make-up water lines shall include a strainer, regulating valve, solenoid valve with manual priming valve and flexible connector. The pump suction ports shall be manifolded to a _______, ______ gallon, ASME receiver rated for full vacuum. The receiver is equipped with a source isolation valve, sight glass, vacuum gauge, manual drain, valved by-pass and source flexible connector. The pump discharge separator vents shall be manifolded, and a flexible connector shall be provided for job site installation to facilitate connection of vent piping to the exterior of the building. The Underwriters Laboratories Listed ______________ electrical motor control system shall be of a fuseless design in a NEMA 12 (dustproof) enclosure. The "Continuous On Demand" feature shall stop the operation of the motors during periods of low or no demand. The controls include individual self protected combination motor controls with short circuit, single phase and thermal overload protection, individual 120 volt control circuit transformers with fuseless primary and secondary protection, pressure transmitters, and an electronic controller to automatically switch the operating sequence of the vacuum pumps. The cabinet door shall have an HMI (Human Machine Interface) system status display to include system pressure, pump operation, accumulated time, maintenance interval, fault conditions and silence button; lighted Hand-Off-Automatic selector switches and safety disconnect operating handles. All required local alarm functions shall be integrated into the packaged system. The circuitry shall be designed so the audib le signal can be silenced and the visual indicator will remain until the fault has been cleared and the reset button actuated. Local alarm functions shall be provided for reserve pump in use (lag alarm). Dry contacts are furnished for remote (master) alarm signals. Factory start-up supervision will be provided by a qualified technical representative. Accessories included for job site installation are inlet and discharge flexible connectors, source isolation valve, vibration mounting pads and touch-up paint. COMMENTS: 1. 2. 3. 4. 5. 6. 7. 8. Ohio Medical Corporation’s proposal is based on our interpretation of the plans and specifications. Any modification to the proposal may result in a price adjustment. For motor protection, the equipment should not be operated in an ambient temperature above 104 oF. Equipment conforms to the National Electrical Code. The system shall meet NFPA 99 2005 requirements. For installations above sea level, consult Ohio Medical Corporation. Actual make up water required may be less than shown based upon operating conditions. The SCFM capacity is calculated at 19" Hg. and based upon a service water temperature of 59°F. As the water temperature rises, the SCFM capacity will decrease. If the fluid temperature is higher than 59 oF, consult Ohio Medical for the actual pump performance. Customer Connection: vacuum inlet, reservoir vent, reservoir overflow, make up water inlet and electrical connections. Overall Length (Inches) Overall Width (Inches) Overall Height (Inches) Weight 1370 21.6 5 1.1 120 21.6 92 46 70 1600 33.7 7.5 1.6 200 33.7 92 46 76 2050 LP10B-T2 47.5 10 2.0 200 47.5 92 56 76 2340 LP15B-T2 75.5 15 2.9 200 75.5 92 56 76 2630 100.7 20 3.3 240 100.7 114 64 86 3300 137.4 30 4.9 240 137.4 130 70 100 4300 199.6 40 6.2 240 199.6 130 70 100 4600 100.7 20 3.3 240 201.4 150 64 86 4600 137.4 30 4.9 240 274.8 176 70 100 6260 199.6 40 6.2 240 399.2 176 70 100 6700 33.7 7.5 1.6 120 33.7 70 54 92 2045 47.5 10 2.0 120 47.5 70 64 94 2380 75.5 15 2.9 120 75.5 70 64 94 2670 47.5 10 2.0 240 95 114 64 94 3940 75.5 15 2.9 240 151 114 64 94 4370 33.7 7.5 1.6 240 101.1 114 64 92 4200 47.5 10 2.0 240 142.5 114 64 92 4900 75.5 15 2.9 240 226.5 114 64 94 5500 Model Receiver Size (Gallons) 66 Average makeup water required @ 19” Hg (GPM) 40 HP Per Pump 88 SCFM @ 19" Hg Each 11.7 Base Configuration 120 Panel Configuration 0.7 Receiver Style 3 Qty of Motors 11.7 System Configuration Design Capacity SCFM @ 19" Hg LIQUID RING WATER SEALED PARTIAL RECIRCULATING VACUUM SYSTEMS LP3B-T2 LP5B-T2 LP75B-T2 Tank Mounted Duplex Two Horizontal Duplex Receiver LP20B-B2 LP30B-B2 Base Mounted Duplex Two Vertical Duplex Heavy Duty Modular Skid Base LP40B-B2 LP20B-B3 LP30B-B3 Base Mounted Three Vertical Triplex Triplex Heavy Duty Modular Skid Base LP40B-B3 LP75B-ST2 Stack LP10B-ST2 Mounted Duplex LP15B-ST2 Two Vertical Duplex LP10B-ST3 Stack Mounted Three Vertical LP15B-ST3 Triplex LP75B-ST4 Stack LP10B-ST4 Mounted Four Quaruplex LP15B-ST4 Triplex Heavy Duty Modular Stacked Base Heavy Duty Modular Stacked Base Heavy Duty Modular Vertical Quadruplex Stacked Base COMMENTS 1. 2. 3. 4. 5. 6. 7. Design capacity values should correspond with "Calculated Peak Demand". This will allow for the reserve pump as is required per NFPA for Level 1 installations. For motor protection, the equipment should not be operated in an ambient temperature above 104 oF. For installations above sea level, consult Ohio Medical Corporation System weight is approximate and without crate. Actual make up water required may be less than shown based upon operating conditions. The SCFM capacity is calculated at 19” Hg, based upon a service water temperature of 59 oF. As the water temperature increases, the SCFM capacity will decrease. If the fluid temperature is higher than 59 oF, consult Ohio medical for actual pump performance. Customer Connections: vacuum inlet, reservoir vent, reservoir overflow, make up water inlet and electrical connections.