COMMUNICATION FACILITIES GUIDELINES FOR EDUCATIONAL AND ADMINISTRATIVE BUILDINGS Rev. 4/18/2008 Miami Dade College SECTION 17 COMMUNICATION FACILITY GUIDLINES FOR EDUCATIONAL AND ADMINISTRATIVE BUILDINGS INTRODUCTION 17.1 GENERAL 1.1 Responsibility 1.2 References 1.3 Structured Cabling System Outside Plant or backbone cabling system Building Entrance/Entrance Facilities (EF) Communication Rooms Main Communications Room (MCR) Main Distribution Facilities (MDF) Intermediate Distribution Facilities (IDF) Vertical and horizontal risers Cable pathways 17.2 OUTSIDE CABLE PLANT 2.1 Outside Conduits 2.2 Maintenance Holes and Handholds 17.3 BUILDING ENTRANCE FACILITY 3.1 Entrance room 3.2 Redundant building entrance 17.4 COMMUNICATIONS ROOMS 4.1 Location and room use 4.1.1 Main Campus Communications Room (MCR) 4.1.2 Main Building Distribution Facility (MDF) 4.1.3 Intermediate Distribution Facility (IDF) 4.2 Common Conditions in all rooms 4.2.1 Room locations 4.2.2 Walls/paint/doors 4.2.3 Ceilings 4.2.4 Electrical 4.2.5 Equipment 4.2.6 Grounding 4.2.7 Lighting 4.2.8 Air Conditioning 4.2.9 Fire Stopping 4.3 Fire Protection 17.5 CABLE PATHWAYS AND CONDUITS 5.1 Ladder rack and cable trays 5.2 Conduits 5.3 Cable Routing 17.6 Communications Building Power Distribution June 2, 2005 1 1 2 2 2 3 4 4 5 5 6 7 7 7 8 9 SECTION 17 MIAMI DADE COLLEGE COMMUNICATION FACILITIES GUIDELINES FOR EDUCATIONAL AND ADMINISTRATIVE BUILDINGS INTRODUCTION MDC Campus communication environments shall be built with ample consideration given to the integrated Internet-Enabled Systems – voice, network, power, security, and energy management systems. Power and redundancy are key issues related to a high-availability “never down” communications system. Building a modern campus network environment also includes operational and safety components that even go beyond the IT department’s responsibilities. This includes areas such as security, energy management, and call centers. Miami Dade College’s Information Technology Department has developed this document in accordance with industry standards. This section is a statement reflecting how the college defines the physical facilities required for the provision of communications systems for new buildings and major renovations to existing buildings. These specifications take into account the size and utilization of communications rooms, size of conduits, cable distance limitations, vertical and horizontal cabling requirements for the area or building, Voice-Over Internet Protocol, classroom attendance readers and the future growth for these areas. The following are guidelines for the physical infrastructure requirements necessary for a modern campus communications network. 1.0 GENERAL 1.1 RESPONSIBILITY- It is the responsibility of the project architect and engineer to include in the design and construction documents, for new and renovation projects, the latest national and local standards for communication facilities. It is critical to the operations of an Internet-enabled communication system that factors such as: connectivity to existing outside conduit bank and cable runs within regulation distances to network-enabled devices be taken into consideration at the beginning of the design phase. Other design criteria that need to be taken into consideration are: avoiding placing water and drain pipes in close proximity to technology rooms; careful creation of staircases and vaulted open foyers that facilitate wire pathways to intended Intermediate Distribution Facility (IDF) rooms; ceilings spaces must be sized to accommodate cable trays, heating and air conditioning ducts, and water pipes. 1.2 REFERENCES- In addition to the specifications included herewith the architect and engineer is encouraged to refer to the following publications for guidance during the design of the communications infrastructure: ADA - Americans with Disabilities Act AIA – American Institute of Architects ANSI – American National Standards Institute BICSI - Building Industry Consulting Service International EIA/TIA - Electronic Industries Association/Telecommunications Industry Association-Telecommunications Wiring Standards. NEC - NFPA National Electric Code OSHA – Occupational Safety and Health Administration State of Florida Building Code - Requirements for Educational Facilities MIAMI DADE COLLEGE -Information Technology DepartmentStructured Cabling Guidelines. 1.3 STRUCTURED CABLING SYSTEM – The Structured Cabling System used by MDC is composed of five subsystems: Outside plant or backbone cabling system Building entrance/Entrance facilities (EF) Communication Rooms Main Communications Room (MCR) Main Distribution Facilities (MDF) Intermediate Distribution Facilities (IDF) Vertical and horizontal risers Cable pathways 2.0 OUTSIDE CABLE PLANT The relationship of the outside cable plant, its location and capacity must be taken in to account when developing the site plan for new buildings. In renovations, its current location must be addressed from the standpoint of current and future capacity and ability to provide adequate service to the new educational spaces. 2.1 OUTSIDE CONDUITS 2.1.1 New buildings shall have two conduit paths entering the building at two separate and distinct locations. Please consult the Information Technology Department to discuss these entrance pathways. 2.1.2 Number of conduits - 4-8 conduits connecting existing campus buildings. 2.1.3 The minimum number of conduits connecting the building MDF to the campus MCR shall be at least four four-inch (4-4”) conduits. Note: More entrance conduits might be needed depending on the size and utilization of the building. It is essential for the future growth of the campus and growth within the new buildings that the number of the conduits brought to the new building reflects the potential growth to the area as well as redundant entrances. 2.1.4 Types of cables that are transported in the conduits - copper and fiber. 2.1.5 Specifics for the conduit bank A. The top of the conduit bank must be buried below the ground surface at a depth specified by local code. B. The fiber and copper cable communications conduit banks must be separated from other services as required by EIA/TIA and local code. C. Conduits shall be encased in concrete when: Minimum conduit depth cannot be attained Conduits pass under roads, driveways, or railroad tracks Bend points might be subject to movement D. Underground conduits shall be installed in such a way that a slope exists leading away from the building to allow drainage and prevent the accumulation of water within the conduits. E. A detectable warning tape (containing metallic tracings) shall be placed 18 inches above all duct banks. 2.2 MAINTENANCE HOLES - A maintenance hole is required at specific distances in order to pull and splice cables in an underground, concealed manner. 2.2.1 Maintenance holes are required when: A. The conduit section length exceeds 500 ft. B. Wherever a cable splice will be required as Indicated by NTS. C. When bends exceed a total of 180 degrees or two Bends of 90º. 2.2.2 Maintenance holes must be sized according to the College’s specifications for each project. It is the responsibility of the Information Technology Department to provide this information. 2.2.3 Concrete used for maintenance holes shall be of at least 3500 sq lb/in strength. All maintenance holes will be properly grounded as required by EIA/TIA and NEC. 2.2.4 Equipment: A. Corrosion resistant pulling irons, cable racks, and maintenance hole ladders shall be included in the installation of the maintenance hole. B. All maintenance holes shall be equipped with a round ring and cover, clearly labeled "TELECOM", "TELEPHONE" or COMMUNICATIONS only. 2.2.5 Conduits entering a maintenance hole will do so only through the maintenance hole walls designed for conduit penetration. Under no circumstances shall the structural integrity of the maintenance hole be compromised. 2.2.6 Conduits being added are to start at the bottom and be added in ascending order so to accommodate future expansion of duct-banks and guarantee maximum utilization of the maintenance hole. 2.2.7 Maintenance holes and hand holes will be installed such that no additional bends are added to the conduit path in order to enter the maintenance hole or hand holes. 2.2.8 Maintenance holes and hand holes shall be installed flush with the ground/floor. 2.2.9 Where distances between maintenance holes exceeds 200 feet or there are more than two 90 degree bends in the conduit run, a 4' x 4' x 4' pull box must be used. 2.2.10 The number of conduits going in and out of the pull box shall maximum not exceed eight. 2.2.11 HAND HOLES are not an acceptable alternative to maintenance holes described in this section. Hand holes can only be used in place of maintenance holes after consultation with, and written approval from the Information Technology Department. 3.0 BUILDING ENTRANCE FACILITY A building entrance is the point at which the outside backbone cables enter the building. 3.1 Entrance Room 3.1.1. Location –In accordance with NEC Article 800 Section 800-50 exception No.3 the entrance or outside building cables shall be terminated and protected on a listed primary protector within 50 ft. of entering the building. This room shall meet NEC Article Section 800-50 exception No. 3 for an Entrance room. It is from this room that feeder cables will be run to the Main Communication Room. A second option exists in that the outside plant cables can be transported through the building, in a straight run, encased in a conduit. It is our preference that these outside cables terminate within our main communication room 3.1.2 Size – This room should be sized to reflect the amount of outside cabling that will be terminated within these walls. The architect will seek this information from the MDC District IT Department. The cables will be terminated on protectors mounted on one wall. Service from these protectors to the Main Communication Room will be provided via conduits or cable trays. 3.1.3 Grounding- Access shall be made available to the main or independent telecommunications grounding system specified by ANSI/TIA/EIA-607. 3.1.4 Lighting – Shall be a minimum of 50-foot candles measured 3 ft. above the finished floor. 3.1.5 Air conditioning – The entrance facility room requires building air if it serves as a Main Distribution Room. 3.1.6 Electrical - A minimum of two dedicated 15A, 110V AC duplex electrical outlets. 3.2 Redundant Building Entrances – New building projects may require redundant building entrance pathways for the fiber cables. This redundant path must be totally separate from existing pathways and use a conduit bank coming from a different direction. Information regarding redundant pathway options may be gotten from the District Information Technology Department. 4.0 COMMUNICATIONS ROOMS (CR) MDC has three different classifications for a communications room, each is designed to meet a specific campus requirement. One of the elements that all of these rooms have in common is that they only house equipment directly related to the network and telecommunications systems and its environmental support systems. 4.1 Location, room use and size 4.1.1 Main Campus Communications Room (MCR)-This room is the demarcation point for all outside services coming into the campus. It will contain PBX equipment, rectifiers, routers, hubs etc. (See Section 4.2 for room details). There is one Main Campus Communications Room on each campus. This room is established on all MDC campuses. Room size is a minimum of 900 square feet but can be larger depending on the equipment that will be housed here. 4.1.2 Main Building Distribution Facility (MDF) - Each building has a main communications/distribution room in which all of the network and telecommunications equipment that services the occupants of the building is located. This room will contain voice (backboards, riser cables) and network-enabled systems (routers, hubs, and switches), fiber, coaxial connections and UPS’s. (See Section 4.2 for room details). The MDF serving the interior dimension of the building must be at least 150 -175 feet. 4.1.3 Intermediate Distribution Facility (IDF) – Each IDF contains voice and network equipment used to distribute the backbone’s capacity to individual station jacks. IDF rooms can not be further than 90 meters (295ft.) in actual cable length from the farthest wall jack on each floor to the IDF patch panel. The minimum IDF room size is a 100 square feet using a 10ft X 10ft footprint. In special-use buildings (as defined by IT), the equipment room floor space shall be based on the known number of work stations (not on usable floor area). This standard can be found in EIA/TIA-569 table 8.2-2. 4.2 Condition’s common to all three types of communications rooms. When selecting the equipment room site it is desirable to locate the equipment rooms close to the main backbone pathway. Avoid locations that are restricted by building components that limit expansion such as elevators: utility chases, outside walls, stairwells or other fixed building walls. Special attention for distance separation between rooms shall be given to electrical power supply, transformers, motors and generators, x-ray equipment, radio, or radar transmitters, and induction sealing devices. Water and chiller lines cannot be run through the communications rooms. 4.2.1 Location of rooms - IDF rooms MUST stack one on top of the other. Avoidance of 90º turns is critical in the conduit path. 4.2.2 Walls/paint/doors A) Floors, walls and ceiling shall be treated to eliminate dust. Finishes shall be light in color. B) A minimum of one wall should be covered with rigidly fixed (3/4 trade size) A-C plywood void free, 8 ft. high, capable of supporting attached equipment. C) Plywood should be fire rated and covered with two coats of medium gray paint. D) The access door shall be a minimum of 36 in. wide and 80 in. high and shall be fitted with a lock and current security access panel. 4.2.3 Ceilings –The minimum ceiling height is 9 feet above the finished floor. There should be no false ceilings. Exception –Rooms that are plenum rated. This type of room requires a dropped ceiling and that dropped ceiling will be no lower then 9 feet. 4.2.4 Electrical A) A minimum of four dedicated 15A, 110V AC duplex electrical outlets, each on separate circuits, from the dedicated building communications panel shall be provided for equipment power. The final number of duplex circuits will be determined by the number of equipment racks in each room. B) Convenience duplex outlets shall be placed at 6 ft. intervals around the parameter walls, at a height of 6 in. above the floor. C) If generator power is available; consideration shall be given to automatic switchover of power. If an emergency power source is available in the building, it is desirable that at least one of the duplex outlets be so supplied. D) Building UPS in a separate room shall be required in new buildings 4.2.5 Equipment - The communication rooms are centralized spaces for the telecommunications and the district wide area network equipment that serves occupants of the building. These rooms house only equipment and services for the telecommunications and network equipment A) PBX (this is located only in the main communications room) B) Network switches, router, and hubs C) Air exchange equipment or stand alone air conditioning units D) Rectifier E) Main backbone distribution equipment from outside sources such as: BellSouth, ATT etc. F) Racks and wire managers. 4.2.6 Grounding and bonding. Racks and equipment shall have a grounding source according to EIA/TIA -569. 4.2.7 Lighting A) Lighting shall be a minimum of 50-foot candles measured 3 ft. above the finished floor. B) Coordinate closely with the front of rack placements. C) Locate light fixtures a minimum of 2.6 m (8.5ft) above the finished floor. Exception - Light fixtures may have to be higher in some cases when ladder racks span the room. D) Emergency lighting is required. Place emergency lighting to ensure that the loss of power to normal lights will not hamper an emergency exit from the CR. E) Power for lighting should not come from the power panel inside the CM. 4.2.8 Air Conditioning - All of these rooms require continuous and dedicated air conditioning 24 hours a day, seven days a week. The HVAC system shall maintain temperature 64-75, (18 C to 24C) degrees Fahrenheit with 30% - 55% relative humidity. Heat dissipation shall be based on 750 – 5000 Btu per hour per cabinet. 4.2.9 Fire Stopping - Section 10 of EIA/TIA-569 contains fire stopping, miscellaneous pathways, and telecommunications recommendations of separation from less than 480V power lines. Further information of entrance rooms can be found in EIA/TIA-569 and the BICSI Telecommunications Distribution Methods Manuals. 4.2.10 The following list of equipment shall not be in this room: Batteries needed to support the Main Communication Room equipment Electrical power Transformers Motors and generators. Small UPS- UPS’s over 30KVA MUST be housed in a separate room 4.3 4.4 Fire Protection 4.3.1 If sprinklers heads are provided, install wire cages to prevent accidental operation. Confer with NTS on the requirements for this item. 4.3.2 “Dry pipe” sprinkler systems are allowed. Additional information regarding MDC required specifications can be found in the MDC STRUCTURED CABLING - Engineering Guidelines. This can be procured from the District IT department. 5.0 CABLE PATHWAYS AND CONDUITS Specific requirements that establish the cable pathways and cabling conduits for each project shall be coordinated with the MDC Information Technology Project Manager at the onset of the design phase for major renovations and new construction projects. The architect and engineer for these is cautioned that the Education Specification’s Program for the project should include communication requirements, but may not be all-inclusive regarding communication facilities. Therefore, the architect and engineer should work closely with the building occupant and the MDC Information Technology Project Manager to minimize the need for revisions and changes after the completion of the design phase. 5.1 Ladder racks and cable trays – Cable trays and ladder racks shall be installed in order to transport all cables through out the building. Cable tray specifications can be found in the MDC STRUCTURED CABLING - Engineering Guidelines, available through District IT. 5.1.1 The IT Project Manager, prior to installation of the cabling, shall approve all cable routes. 5.1.2 Cable Trays are rigid structures for the containment of communications cables. These trays shall be installed and grounded in accordance with the National Electric Code. 5.1.3 Cable trays shall be installed above false ceilings and run down hallways and corridors providing a pathway for communication cables from the information outlets to the respective communications closets. 5.1.4 Cable tray installation must be coordinated with all of other trades so that they are not obstructed by other equipment, i.e. air conditioning ducts, electrical conduit etc. 5.1.5 5.1.6 5.1.7 Cable trays must be easily accessible for the installation of cables and future changes to the communication systems. A minimum of 3 in. clear vertical space must be available between the top of the ceiling tiles and the bottom of the cable tray. A minimum of 12 in of clear horizontal space on each side of the cable tray shall be available. Also, minimum of 6 in of clearance shall be available between the top of the cable tray and any other utilities. Under no circumstances, shall any other utilities pass within the distances as specified in BISCI or EAI guidelines. 5.2 Conduits 5.2.1 Communication’s rooms contain the vertical cable riser space. Conduits and/or sleeves shall be used to interconnect communications rooms. The open ends of conduits and/or sleeves must be located a maximum of 3 in. from the wall and extend a minimum of 1 in. above the finished floor. 5.2.2 All vertical risers shall rise straight up through the building. 5.2.3 5.2.4 5.2.5 5.2.6 5.2.7 5.2.8 If fixed ceilings are installed and cable trays cannot be used, the conduit from information outlets must be "homerun" to the respective telecommunications room. A pull box shall be installed in sections of conduit longer than 100 ft., containing more than two 90 degree bends or if there is a reverse bend in the run. All conduits must have a fish tape or pull cord installed end-to-end. Wall and room conduits: A 3/4 inch EMT conduit shall be installed from each information outlet electrical box and "stubbed" up above the ceiling level pointing to the nearest respective cable tray. The open ends of all conduits and/or sleeves regardless of size must be equipped with bushings and must be readily accessible and not concealed within walls. The inside radius of a bend in conduit shall be at least 6 times the internal diameter. When the conduit size is greater than 2 in. the inside radius shall be at least 10 times the internal diameter of the conduit. Minimum requirements for installed conduit, such as support, end protection and continuity, are found in the appropriate national and local electrical codes. 5.3 Cable Routing 5.3.1 All horizontal cables, regardless of media type, shall not exceed 90 m (295 ft) from the telecommunications outlets in the work area to the horizontal cross connect. 5.3.2 Horizontal cables shall be routed to each work area unless otherwise specified and as shown on project drawings. 5.3.3 Horizontal pathways shall be installed or selected such that the minimum bend radius of horizontal cables is kept within manufacturer specifications both during and after installation. 5.3.4 Communications pathways, spaces and metallic cables, which run parallel with electric power or lighting, which is less than or equal to 480 Vrms, shall be installed with a minimum clearance of 12 inches. 5.3.5 The installation of telecommunications cabling shall maintain a minimum clearance of 3 m (10 ft) from power cables in excess of 480 Vrms. 5.3.6 Horizontal pathways should avoid being parallel to sources electromagnetic interference when ever possible. Crossing perpendicular is preferred. 5.3.7 For voice or data applications, 4-pair UTP or fiber optic cables shall be run using a star topology from the communications room/closet serving that zone to every individual information outlet. 5.3.8 Continuous conduit runs installed by the General Contractor should not exceed 30.5 m (100 ft) or contain no more than two (2) 90-degree bends without utilizing appropriately sized pull boxes. 5.3.9 All horizontal pathways shall be designed, installed and grounded to meet applicable local and national building and electrical codes. 5.3.10 The number of horizontal cables placed in a cable pathway shall be limited to a number of cables that will not cause a geometric shape change of the cables and not exceed 60% fill ratio. 5.3.12 Minimum pathway capacity shall not exceed a 60% fill. 5.3.13 The maximum cable bend radii shall not exceed manufacturer’s specifications. 5.3.14 In spaces with UTP cable terminations, the maximum bend radius for 4-pair cable shall not exceed four times the outside diameter of the cable and ten times for multi-pair cable. This shall be done unless this violates manufacturer specifications. 5.3.15 During the actual installation, bend radius on 4pair cable shall not exceed eight times the outside diameter of the cable and ten times for multi-pair cable. This shall be done unless this violates manufacturer specifications. 5.3.16 To avoid electromagnetic interference, all cable pathways must provide clearances of at least: Four (4) feet from large motors or transformers. One (1) foot from conduit and cables used for electrical power distribution. Five (5) inches from fluorescent lighting. Pathways should cross perpendicular to fluorescent lighting and electrical power cables or conduits. 6.0 Communications Building Power Distribution – Discussions shall take place with the Information Technology Department regarding the installation of a building UPS to supply back up power to All new IDF’s within the building.