System Management / Field Installed Demand Controlled Ventilation / ComfortID Demand Controlled Ventilation / Sequence of Operations Note: The following is a sample of a typical sequence of operation that may be adapted for a particular project. This is provided as a suggestion on how to write a sequence of operation for a specific project. Consult your Carrier representative if the sample sequence requires alterations. 4.3.4 Demand Controlled Ventilation A. Overview: The HVAC system sequence of operation steps for normal thermal control is unchanged by incorporation of DCV. The CO2 sensors represent a third function that may override the normal thermal controls in some situations. The sequences included below discuss the ventilation functions only and must be added to the design’s description of thermal controls to create complete sequences of operation. B. Constant-Volume — Start-up Purge Cycle: 1. When the AHU starts, the outdoor air damper shall open, initiating a timed purge cycle. The out door air damper shall modulate to maintain the mixed airflow at ______ percent outdoor air. The outdoor air percentage shall be calculated as the following ratio: %OA = (MATº - RATº) / (OATº RATº). The purge period shall be adjustable and shall initially be set for ____minutes. 2. The AHU shall modulate its preheat control to maintain the discharge air temperature setpoint if the mixed air temperature falls below the AHU discharge air temperature setpoint. At the conclusion of the timed cycle, the outdoor air damper shall modulate closed to maintain the base ventilation rate of _____ percent outdoor air, and the demand controlled ventilation control algorithm shall be enabled. C. Constant-Volume — Single-Zone and Multi-Zone Applications: 1. All zones served by a given air-handling unit (AHU) shall be polled and the highest CO2 sensor reading shall be sent to the unit (outside air damper) controller. This CO2 reading shall be compared to the CO2 setpoint at the system controller. If the reading is below the CO2 setpoint, the AHU shall maintain the base ventilation rate at ____ percent outdoor air. If the reading is above the setpoint, the outdoor air damper controller shall modulate the dampers open utilizing a proportional-integral (PI) loop to reduce the CO2 concentration in the space. 2. The AHU shall modulate its preheat control to maintain the discharge air temperature setpoint if the mixed air temperature falls below the AHU discharge air temperature setpoint. Once the space CO2 level drops below the CO2 setpoint, the outside air dampers shall modulate to maintain the base ventilation rate. 3. If the AHU is equipped with economizer control and the economizer determines that it is beneficial to use outside air for cooling, the economizer shall override the demand controlled ventilation algorithm to modulate the dampers open to their maximum position. D. Variable-Air-Volume DCV Systems: 1. Each variable-air-volume zone controller shall monitor primary air flow, space temperature, air handler status and mode, supply air temperature (as applicable) and shall position its terminal damper based on its proportional-integral-derivative (PID) temperature control algorithm to maintain the desired zone temperature setpoint. Each zone controller shall include the inherent ability to override the temperature control loop and modulate the terminal’s damper with a proportional-integral (PI) loop, based on a CO2 sensor with its associated setpoint schedule, in conjunction with the normal temperature control loop. The zone controller shall be capable of maintaining a ventilation setpoint through a demand controlled ventilation (DCV) algorithm in conjunction with the air-handling unit to fulfill the requirements of ASHRAE standard, 62-1989 “Ventilation For Acceptable Indoor Air Quality” (including Addendum 62a-1990). 2. The DCV control function shall determine the zone ventilation airflow based on the CO2 zone sensor input signal. When the DCV function is enabled, the zone controller shall override (increase) the primary airflow in order to provide additional ventilation if the airflow is insufficient to meet the zone CO2 setpoint. The control algorithm shall use a proportional-integral (PI) algorithm to determine the required airflow in order to prevent the CO2 sensor reading from exceeding the desired zone setpoint. 3. Whenever the system air-handling unit (AHU) is operating, the system controller shall maintain the base ventilation rate (minimum ventilation rate) unless overridden by a pre-occupancy purge sequence or the DCV function. 4. All zone controllers working with a given AHU shall be polled and the highest CO2 sensor reading shall be sent to the system controller. This CO2 reading shall be compared to the system CO2 setpoint. If the reading is below the system CO2 setpoint, the AHU shall maintain the base ventilation rate. If the reading is above the setpoint, the AHU damper controller shall modulate the outside air dampers open using a proportional-integral (PI) loop to maintain the zone CO2 at the zone setpoint. 5. The system controller shall modulate the AHU preheat control to maintain the discharge air temperature setpoint if the mixed air temperature falls below the discharge air temperature setpoint. The outside air damper position shall close with a decreasing CO2 sensor signal down to the base ventilation rate. The zone controller shall contain a provision to operate modulating type heat to maintain the space temperature at the midpoint between the heating and cooling setpoints during DCV operation. The zone controller shall have the capability to define a maximum primary airflow limit (ventilation) to protect the zone from overcooling for those units that do not include local heating. DCV control shall be automatically suspended if the space temperature falls below the heating setpoint and the outdoor air damper shall return to the base ventilation position. 6. If the AHU is equipped with economizer control and the economizer determines that it is beneficial to use outside air for cooling, the economizer shall override the DCV algorithm to modulate the dampers open to their maximum position. 7. Operation shall be dependent upon the equipment mode of operation, so that the DCV function will only operate during occupied periods when the outdoor air damper is actively providing ventilation. DCV control shall be disabled if the CO2 sensor fails. E. Product Integrated Controllers: The unit controller shall have the capability to provide demand controlled Ventilation (DCV) function using the input signal from a CO2 sensor located in the conditioned space. Control functions shall include outdoor air damper modulation, monitoring, and alarm generation. The unit controller shall maintain an adjustable CO2 setpoint by overriding the mixed-air damper position and modulating the damper further open to provide the required ventilation. The DCV algorithm shall automatically limit the amount of outdoor air to prevent the mixed-air temperature from falling below 50ºF. The unit controller shall also have the ability to limit the maximum amount of outdoor air during DCV operation. If heating is available during DCV operation, the heating valve [face and bypass damper] shall modulate to maintain a minimum supply air temperature of 65ºF, if neither heating nor cooling is required by the space. If the space temperature exceeds an adjustable high limit value or falls below an adjustable low limit value, or if the space humidity exceeds the humidity setpoint, the algorithm shall disable any DCV damper override and maintain the normal minimum ventilation setpoint or to the configured mixed-air temperature setpoint until the space temperature and/or space relative humidity returns to normal.