Oradea - Universitatea "Lucian Blaga" din Sibiu

advertisement
FAULT CURRENT DISTRIBUTION COMPUTATION ON OVERHEAD
TRANSMISSION LINES
Senior lecturer Maria VINŢAN, PhD
University “L. Blaga” of Sibiu
School of Engineering
Department of Electrical Engineering and Electronics
E. Cioran Str. No. 4
Sibiu 550025, Romania
Phone/fax: 0269/212716
E-mail: maria.vintan@ulbsibiu.ro
Abstract: This paper presents an analytical method in
order to determine the ground fault current distribution
between neutral conductors and the earth, via the
towers, for transmission line ground networks.
Keywords: overhead transmission line, fault current distribution.
1. Introduction
that
When a ground fault occurs on an overhead
transmission line in a power network with effectively
grounded neutral, the fault current returns to the
grounded neutral through the tower structures, ground
return paths and ground wires. Ground fault current
due to a fault at any tower, apart from traversing
through it, will also get diverted in each portion to the
ground wires and other towers [10].
As a consequence, the step and touch voltages near
the faulted tower will be smaller then the values
obtained in the absence of the ground wires.
2. Ground fault current distribution
Figure 1 below shows the connection of a ground
wire connected to earth through transmission towers,
each transmission tower having its own grounding
electrode or grid, Z st . It is assumed that all the
transmission towers have the same ground impedance
and the distance between towers is long enough to
avoid the influence between there grounding
electrodes. The self impedance of the ground wire
connected between two grounded towers, called the
self impedance per span, it is Z cp . Considering the
d
same distance l d between two consecutive towers and
is the same for every span, then
Z cp
d
Z cp  Z cp l d , where Z cp represent the self
d
impedance of the ground wire in  / km . Z cp is
m
the mutual impedance between the ground wire and the
faulted phase conductor, per span.
Ground current due to fault at any tower, apart from
traversing through it, will also get diverted in portion to
the ground wire and other towers.
The current I n flowing to ground through the nth
tower, counted from the terminal tower where the fault
is assumed to take place, is equal with the difference
between the currents i n and i n 1 :
I n  i n  i n1
(1)
The loop equation for the n-th mesh give the following
relation:
I n Z st  I n1Z st  in Z cp  I d Z cp  0
d
d
(2)
Z cp
m , the coupling factor between the
 
Z cp
d
overhead phase and ground wire;
I d , the fault current.
-
Figure 1 Fault current distribution
Re-writing the equation (2) yields us:
( I n1  I n ) Z st
in 
 I d
Z cp
d
Similary:
( I n  I n1 ) Z st
i n1 
 I d
Z cp
d
(3)
substituting the solutions (6) and (13) in equation (1), it
will be obtained:
n
n
n

n

Ae
 Be
 ae (1  e )  be
(1  e
) (14)
Because these relations are the same for every value of
n, it will be obtained the next expressions:
(4)
A  a (1  e )

B  b(1  e )
The current in the ground wire will be then:

Substituting equations (3) and (4) in equation (1), for
the current in the faulted tower, will be obtained the
next equation, which is a second order difference
equation:
Z cp
d
In
 I n1  2 I n  I n1
(5)
Z st
According to [4], the sollution of this equation is:
n
n
I n  Ae
 Be
(6)
 could be obtained by substituting the solution (6) in
equation (5). For this purpose, n is substituting with
(n+1), respectively with (n-1) in equation (6):
 ( n1)
 ( n1)
I n1  Ae
 Be
(7)
 ( n1)
 ( n1)
I n1  Ae
 Be
(8)
The equation (5) became:
Z cp
 2


d
e e
 2  2( sh )
(9)
Z st
2
Because Z cp  Z st , it can be written:
d
 
Z cp
d
Z st
By substituting the equations (1) and (11) in equation
(2), it will be obtained the next equation with a
constant term:
Z cpd
Z st
 in 1  2in  in 1  I d
Z cpd
Z st
(12)
Similar with equation (5), the current in the ground
conductor is given by the next solution:
in  aen  be n  I d
(13)
a, b –arbitrary parameters.
Because of the link between currents i n and I n , the
arbitrary parameters A, B, a, b are not independent. By
(16)
en
e n

B
 I d
1  e
1  e 
(17)
The boundary condition at the terminal tower of figure
1, which means that the fault current is given by the
sum between the current in the faulted tower and the
current in the first span of the ground wire, is:
I d  I 0  i1
(18)
This is the condition for n  0 . If the line is
sufficiently long so that, after some distance, the
varying portion of the current exponentially decays to
zero, A  0 and according to (6) and (17):
n
I n  Be
(19)
n
e
(20)
in  B
  I d
1 e
Substituting these expressions in (18), with n  0 for
I n and n  1 for i n , we get:

e
B
Id  B  B
  I d 
  I d (21)
1 e
1 e
For B we get:
(10)
According with the solution (6) which contains the
arbitrary parameters A and B, the current flowing to
ground through the succesive towers, has an
exponentiall variation. The arbitrary parameters A and
B will be obtained later, from the boundary conditions.
A similar equation is obtained for the current in the
ground conductor, by aplyaing equation (1) to the (n-1)
tower:
I n1  in1  in
(11)
in
in  A
(15)

2th

2 I (22)
 d
1  th
2
The current in the faulted tower will get the expression:
B  (1   )(1  e
) I d  (1   )
2th

2 I
(23)
 d
1  th
2
The current in the first span, counted from the faulted
tower, will be:


(24)
i1  I d  I 0  I d [e
  (1  e )]
The previous analysis of the distribution of ground
fault current, based on fault at the terminal tower, was
done without its connection to a substation grounding
grid (figure2). In this case, a portion of the total ground
fault current will flow through the substation ground
I 0  B  (1   )
resistance. If this resistance is
R p' , the previous results
will be valid except for replacement of I d with
'
'
I d  I d  I p , and thus the value of the current in the
faulted tower will be:
Figure 2 Fault current distribution
I 0  (1   )(1  e  ) I d'
(25)
'
The current I p through the substation grounding grid,
is given by the expression:
'
I p  Id
Z
'
R p  Z
(26)
'
'
In case the values of R p and Z  are known, I p can
'
be found out from (26) above. I d is given by the next
expression:
'
'
(27)
I d  I d  I p  I 0  i1
'
In the expressions above, R p will be substitute with
'
'
'
Z p  R p  Z cp , if will have to considere the
d
impedance of a small feeder between the grounding
grid and ground wire.
Now, it will be found the nth tower, as counted from
the terminal tower, where the current gets reduced to
1% then that traversing the terminal tower. From
equation (19):
Be
n

1
100
Bn
ln 100

 4,6
Z st
(28)
Z cp
d
Z cp
d
 0.03 , will get n=26.5, so it takes at least
For
Z st
26 towers from the fault to get a current reduced to 1%
then that traversing the terminal tower.
Taking into account this consideration, it is possible to
see if could be considered A=0 in the expressions of
the currents in ground wire and towers. The number of
the towers should be at least equal with the number
given by expression (28).
If the line can not be considered long enough,
regarding to (28), then parameters A and B will be
found from the boundary conditions.
'
It was noted with R p , respectively R p , the
resistances of the terminal stations (figure 3). The
stations are connected to the terminal towers, at the
both sides, through an extra span
between
Z cp' d , and the sum
Z cp' d and grounding grid of the stations
resistance
respectively
was
noted
with
Z p  R p  Z cp' d ,
Z p'  R p'  Z cp' d .
The boundary condition at the receiving end of the line
is:
Z st
'
I d  I p  I 0  i1  i1  I 0  I 0
(29)
'
Zp
At the sending end of the line we have:
I d  I p  i N 1
(30)
'
'
I N Z st  I p R p  i N 1Z cp  I d Z cp  0 (31)
d
d
Substituting I p from (31) to (30), we’ll get:
'
'
Z cp
Z cp
Z st
d
d
(32)
I d (1  
)  i N 1 (1 
)  IN
Rp
Rp
Rp
Substituting I 0 , I N , i N 1 and i1 into (31) and (32),
according to (6) and (17) and taking into account (15)
and (16), we’ll get two linear equations with respect to
a and b:
Figure 3 Fault current distribution



Z 
Z 
 I (1   )  a 1  (1  e ) st   b 1  (1  e  ) st 
'
'
 d

Zp 
Zp 
 



'



Z cp

N  
 Z st 
N  
d
e (1 
)  (1  e )
 be
e (1 
 I d (1   )  ae


Rp
Rp 





'
Z cp
 Z st
d
)  (1  e )
Rp
Rp
(33)




 Z st
a1  1  (1  e )
(33) gives:
b2  b1

a  I d (1   )
a1b2  b1a 2


b  I (1   ) a1  a 2
d

a1b2  b1a 2

(34)
 Z st
)
'
Zp

a2  e
and taking into account (15) and (16) we’ll have:
b2  b1


(1  e )
 A  I d (1   )
a1b2  b1a 2


 B  I (1   ) a1  a 2 (1  e  )
d

a1b2  b1a 2

b1  1  (1  e
'
Zp
'

Z cp
 Z st 
d
e (1 
)  (1  e )

Rp
Rp 
N  



(35)
where a1 , b1 , a 2 , b2 are:
N  
b2  e
e (1 


'

Z cp
 Z st 
d
)  (1  e )
Rp
Rp 

For the current in the faulted tower we’ll get the next
expression (obtained for n  0 in all expressions,
including a 2 , b2 ):
 b2  b1
a1  a 2

 
I 0  A  B  I d (1   )
(1  e ) 
(1  e ) 
a b b a

a1b2  b1a 2
 1 2 1 2

3. Numerical results
In this section, based on the analytical model
presented above, are presented numerical results.
For the circuit from figure 1, considering a fault at
the terminal tower, the numerical results for the fault
current distribution are presented in figure 4a). Fault
current was considered to be 1000A, Z cp  2 and
d
Z st  1,5 . Those results were obtained by
neglecting the mutual coupling between the phase
conductor and the ground wire.
In [3] are presented numerical results, obtained with
complex matricial methods. For the same values and
neglecting the mutual coupling, the numerical results
presented in figure 4b), are the same with those
obtained with the method presented here.
Figure 5 presents the numerical results obtained in
the case of mutual coupling. It was considered
  0,292 , which correspond to a steel ground wire of
with 70mm2, radius 0.473cm, placed at 24.4m above the
earth’s surface.
(36)
The distance between ground wire and phase
conductor is 3.05m. It can be seen that in the absence
of mutual coupling, the fault current will flow through
the ground, through a smaller number of towers then in
the mutual coupling presence [2], [8].
Figure 6 presents the numerical results taking into
account that the line is not long enough to consider in
the current expressions A=0.
Line impedances per one span was considered to be
Z cp  0.193  and Z st  10  , and the line has 20
d
towers. It was considered an ACSR ground wire of
160/95 mm2, and a diameter of d=18,13mm. The
mutual coupling was considered to be   0,3553 .
The disposition of the line conductors is presented
in figure 7. The faulted phase was considered to be the
the furthest one from the ground conductor, since the
lowest coupling will produce the highest tower voltage.
For the fault current was considered the value
I d  5000 A .
a)
b)
Figure 4) Computation results
Figure 5 Computation results
Stâlpul nr. 0
Stâlpul nr. 1
Stâlpul nr. 2
Stâlpul nr. 3
Stâlpul nr. 4
Stâlpul nr. 5
I0=292,2A
I1=254,6A
I2=221,9A
I3=193,4A
I4=168,7A
I5=147,3A
Ust=2922,5V
Ust=2546,1V
Ust=2218,9V
Ust=1934,4V
Ust=1687,3V
Ust=1472,8V
i1=3726,7A
i2=3472,1A
i3=3250,2A
i4=3056,8A
i5=2888A
Stâlpul nr. 6
Stâlpul nr. 7
Stâlpul nr. 8
Stâlpul nr. 9
Stâlpul nr. 10
Stâlpul nr. 11
Stâlpul nr. 12
Stâlpul nr. 13
Stâlpul nr. 14
Stâlpul nr. 15
Stâlpul nr. 16
Stâlpul nr. 17
Stâlpul nr. 18
Stâlpul nr. 19
Stâlpul nr. 20
I6=128,7A
Ust=1286,7V
I7=112,5A
Ust=1125,4V
I8=98,6A
Ust=985,9V
I9=86,5A
Ust=865,4V
I10=76,2A
Ust=761,5V
I11=67,2A
Ust=672,4V
I12=59,6A
Ust=596,3V
I13=53,2A
Ust=531,6V
I14=47,7A
Ust=477,3V
I15=43,2A
Ust=432,1V
I16=39,5A
Ust=395,3V
I17=36,6A
Ust=366,1V
I18=34,4A
Ust=344V
I19=32,8A
Ust=328,5V
I20=31,9A
Ust=319,3V
Figure 6 Computation results
i6=2740,8A
i7=2612,1A
i8=2499,6A
i9=2401A
i10=2314,4A
i11=2238,3A
i12=2171A
i13=2111,4A
i14=2058,2A
i15=2010,5A
i16=1967,3A
i17=1927,8A
i18=1891,2A
i19=1856,8A
i20=1823,9A
Figure 7 Disposition of line conductors
4. Conclusions
This paper describes an analytical procedure in order
to determine the ground fault current distribution in case
of a fault at the terminal tower, where the grounding grid
of a substation is connected to the ground wire.
It was considered an overhead transmission line with
one ground wire, connected to the ground at every tower
of the line and the fault appear at the terminal tower.
There were obtained the expressions of the currents
flowing to ground through the towers and the currents in
every span of the ground conductor. These currents are
varying exponentially and in their expressions there are
two arbitrary parameters. For the long lines case, one of
these parameters could be zero. It was established the
minimum number of towers that fulfil this request. For
References
1.
2.
Buta A.: Transportul şi distribuţia energiei electrice
(Transport and Distribution of Electrical Energy),
“Politehnica” University of Timişoara, 1991
Endrenyi J: Analysis of Transmission Tower
Potentials during Ground Faults, IEEE Transactions
on Power Apparatus and Systems, Vol.PAS-86,
No.10, October 1967
lines with a smaller number of towers, both the
parameters will be determined. Based on the boundary
conditions, there were obtained these parameters.
The mutual impedance between the ground conductor
and the faulted phase conductor, reduces the total circuit
impedance. In these conditions, the fault current will be
higher if the mutual impedance is neglected. From the
model presented above, it can be seen that, due to the
mutual coupling, the fault current is reduced with (1   ) .
It also can be seen that in the absence of mutual
coupling, the fault current will flow through the ground,
through a smaller number of towers then in the mutual
coupling presence.
3.
4.
Goci H. B., Sebo S. A.: Distribution of Ground Fault
Currents along Transmission Lines - an Improved
Algorithm, IEEE Transactions on Power Apparatus
and Systems, Vol.PAS-104, No.3, March 1985
Rudenberg R.: Fenomene tranzitorii în sistemele
electroenergetice (Transient Phenomenas in Power
Systems), Editura tehnică, Bucureşti, 1959, Traducere
din limba engleză
5.
6.
7.
Şora C.: Bazele Electrotehnicii (Fundamentals of
Electrotechnics), Editura didactică şi pedagogică,
Bucureşti, 1982
Toader D., Hărăguş Şt., Toaxen V. – An Improved
Method for the Neutral Point Grounding in a
Distribution Network, Proceedings of the IASTED
International Conference on Power and Energy
Systems, Spain, 2000
Verma R., Mukhedkar D.: Ground Fault Current
Distribution in Sub-Station, Towers and Ground
Wire, IEEE Transactions on Power Apparatus and
Systems, Vol.PAS-98, No.3, May/June 1979
Vinţan M., Bogdan M. – Transmission Power
Potentials during Ground Faults, Proceedings of the
11th International Symposium on System Theory
SINTES – 11, vol. 2, pg. 553-556, ISBN 973-8043415-5, 2003, Craiova, Romania
9. Vinţan M. – Determinarea distribuţiei curentului de
scurtcircuit monofazat în reţelele electrice de înaltă
tensiune, Teză de doctorat, Timişoara 2003
10. Vinţan M. – Scurtcircuitul monofazat în reţelele
electrice, ISBN 973-685-647-X, Editura MatrixRom,
Bucureşti, 2003
8.
Download