CAPITAL DEVELOPMENT AUTHORITY MECHANICAL DIVISION-II PHASE-I SUBJECT: PROVIDING/INSTALLATION OF 750 KVA TRANSFORMER WITH HT PROTECTION PANELAT K BLOCK IBHQ PAK, SECT, BUILDING ISLAMABAD. S/NO 1. 2. 3. 4. 5. 6. 7. 01-02 25-493 25-444 25-123 25-145 25-181 25-177 DESCRIPTION Head-I MES 2009 Excavation as in Hard Soil up to 1.5M depth, in foundation and pipe trenches up to 1.5 M wide in shafts, wells and independent holes up to 30 Sq./m each and throw earth clear of edges of excavation within 10 m. Timbering to be paid extra (Trench over 1.5 M widths will be treated as areas) Vacuum circuit breaker (VCB) HT 11 KV panel floor mounting 400/630 A rating 20 KA complete with selector switches indicating lamp sheet steel cubicle factory assembled and duly painted single panel unit consisting of all accessories and protections of specified in Para 25.2.15.1 and Para 25.2.15.2 but one incoming and two outgoing (set of three) supply & fixing LT switch board with 1250 Amps MCCB incoming switch, complete with thermal over current release, adjustable magnetic short circuit release, shunt trip coil, CT ratio 1000/5, voltmeter and ammeter with selector switch, earth fault relays, complete with triple pole neutral common bus barinclup to 06 outgoing with neutral link 3 phase MCCB switches, switch board factory wired, steel sheet clad and painted installed complete incl making connections, supply & fixing Cable electric HT11 KV stranded copper conductor, XLPE insulated, extruded PVC bedded, steel wire armored and PVC sheathed overall, 3 core, 120mm2 laid in trenches complete with bricks sand (exclusive of cost of excavation) supply & fixing Cable electric LT, PVC insulated, PVC sheathed armored overall PVC 600/1000 volts with stranded copper conductor 300mm2, 3-1/2 core laid in trenches, complete with bricks, sand (exclusive of cost of excavation) supply & fixing Cable electric LT, 600/1000 V PVC insulated, PVC overall stranded copper conductor 240mm2, 3-1/2 core, unarmored laid in GI/RCC, pipe/duct (exclusive of cost of pipe/duct), supply & fixing QTY RATE UNIT AMOUNT 90CUM Rs.180.48 P/cum Rs.16243.2/- 01 No Rs.3507937.3 Each Rs.3507937.3 01 No Rs.974293.92 Each Rs.974293.92 25Mtr Rs.4343.61 P/Mtr Rs.108590.25 265 Mtr Rs.9014.73 P/Mtr Rs.2388903.45 47 Meter Rs.6602.73 P/Mtr Rs.310328.31 Rs.2643.01 P/Mtr Rs.232584.88 Cable electric LT, 600/1000 V PVC insulated, PVC overall stranded copper conductor 95mm2, 3-1/2 core, unarmored laid in GI/RCC, pipe/duct (exclusive of 88 cost of pipe/duct), supply & fixing Meter 8. 9. 25-175 24-753 Cable electric LT, 600/1000 Volts PVC insulated, PVC overall stranded copper conductor 50mm2, 3-1/2 core, unarmored laid in GI/RCC, pipe/duct (exclusive of cost of pipe/duct), supply & fixing S/F Distribution board steel sheet (16 BG) with hinged over having locking arrangement duly enameled painted suitable for housing different capacities of MCCBs etc. (as required). i. (DB size 3’x5’x1’= 15Sft=1.3935x2=2.787 Square Meter) ii. (DB size 5’x2’x1.5’= 7.5Sft=0.696x2=1.3935 Square Meter) iii. (DB size 3’x2.5’x0.66’= 7.5Sft=0.696 Square Meter) iv. (DB size 3’x4’x1’=12 Sft=1.11 Square Meter) MCCB TP, 500/660 volts, 50/60 cycles complete with thermal and magnetic trips, 500 to 600 Amps, (breaking capacity 25 KA) supply & fixing MCCB TP, 500/660 volts, 50/60 cycles complete with thermal and magnetic trips, 250 to 400 Amps, (breaking capacity 25 KA) supply & fixing MCCB TP, 500/660 volts, 50/60 cycles complete with thermal and magnetic trips, 125 to 225 Amps, (breaking capacity 18 KA) supply & fixing MCCB TP, 500/660 volts, 50/60 cycles complete with thermal and magnetic trips, 75 to 100 Amps, (breaking capacity 5 KA) supply & fixing Bus bar chamber 600/610 mm long steel sheet/cast iron with hinged cover with hard dawn copper bus bar mounted on well insulated with micanite or other approved insulation material frames, complete with mains and branch cable socket and terminals enamel paint inside and black outside, 500 volts, 500A, 4 bars, 400mm height 175-225mm depth supply & fixing Current transformers (CT) ratio 25/5A for LT panel supply & fixing 97 Meter Rs.1375.25 P/Mtr Rs.133399.25 5.99 Square Meter Rs.13923.66 Square Meter Rs.83402.72 02 No’s Rs.59061.90 Each Rs.118123.8 03 No’s Rs.35712.42 Each Rs.107137.26 11 No’s Rs.15508.97 Each Rs.170598.67 08 No’s Rs.5677.61 Each Rs.45420.88 03Nos Rs.12338.36 Each Rs.37015.08 06 No’s Rs.883.59 Each Rs.5301.54 Thimble / cable socket for single core cable 185mm2 to 300mm2 supply & fixing 60 No’s Rs.454.70 Each Rs.27282/- 10. 24-396 11. 24-395 12. 24-394 13. 24-393 14. 24-466 15. 16. 25-439 25-442 24-652 17. 18. 24-653 24-654 Thimble / cable socket for single core cable 95mm2 to 150mm2 supply & fixing Thimble / cable socket for single core cable 16mm2 to 70mm2 supply & fixing 50 No’s 80 No’s Rs.270.36 Rs.81.11 Each Each Rs.13518/Rs.6488.8 19. 24-12 13 Points Rs.1193.10 P/Points Rs.15510.3 20. 21. 22. 28-129 28-153 25-469 02 No’s 02 No’s 02 No’s Rs.3000.00 Rs.2830.00 Rs.13460.09 Each Each Each Rs.6000/Rs.5660/Rs.26920.18 23. 25-312 One Fan point, one light point, one bell point, controlled by one switch, wiring complete with PVC single core cable 1.5mm2 in concealed PVC conduit, supply & fixing Celling fan but (Supreme) 56” (1400 mm) Sweep. Exhaust fan metal body but 24” (600 mm). Special earth for transformers HT and LT switchgear for areas having water table more than 3 Meters depth, supply & fixing Phase indicating sign, red, blue or yellow as required. supply & fixing 05 No’s Rs.96.45 Each Rs.482.25 Head-I MES-2009 Total: -Rs. 8,341,142.04 S/NO 24. DESCRIPTION NON SCH 1 0 NON SCH 26. NON SCH RATE UNIT 01 Job Rs,1661200/- AMOUNT Head-II NON SEHUDEL ITEMS Providing, installation, making CC foundation MS moving channel, testing and commissioning of indoor mounted transformer complete with all standard and optional components as specified and accessories complete in all respect as required at site and as approved by engineer in charge. With the following. 1 2 3 4 5 6 7 8 9 25. QTY SPECIFICATIONS:- (PEL / SIEMENS Make) Rated KVA 750 KVA Voltage ratio 11000/415V Frequency 50Hz/3 Phase Type of Cooling ONAN Insulation class A Tapping Voltage (+) 2.5, 5% (-) 2.5, 5,7.5 Bil 95 KV Vector Group dyn 11 Temperature rise above ambient temperature Oil= 60 Deg C Winding = 65 Deg C Arcing Horn / Spark gaps Each Rs, 1661200/- Providing, installation Bus bar chamber 1000 mm (04 bars) and 400 mm (08 bars) long steel sheet/cast iron with hinged cover with hard dawn copper bus bar mounted on well insulated with micanite or other approved insulation material 01 Job Rs.14109/P/job Rs.14109/frames, complete with mains and branch cable socket and terminals enamel paint inside and black outside, 600 volts, 600A, 400mm height 175-225mm depth as required at site and as approved by engineer in charge. Providing installation of digital volt meter (07 no’s), digital ampere meter (07 no’s), digital power factor meter(04 no’s) selector switch(14 no’s) for HT, LT and 01JOB Rs.32352/P/JOB Rs.32352/on distribution panel with all respects testing and commission as per entire satisfaction of engineer in charge. Head-II NON Schedule items Total:-Rs.1,707,661/- Total MES Schedule Items & Non Schedule Items SUB-ENGINEER (K BLOCK) ASSISTANT-DIRECTOR-I Rs.10,048,803/- DY-DIRECTOR (MECH-II)