University of Manitoba PLUMBING Section 15400 Req # Page 1 PART 1 - GENERAL 1.1 DESCRIPTION .1 All drawings and all sections of the specifications shall apply to and form an integral part of this section. 1.2 COMMISSIONING .1 Refer to Section 01810 Quality Commissioning for the details of the commissioning process. 1.3 WORK PERFORMED BY THIS SECTION .1 Provide labour, material, equipment and services necessary for the supply, installation, and connection of the systems shown on the drawings and hereinafter specified. .2 Provide Municipal and Utility street services connections including water, sewers, gas, air, catch basins, manholes, and all other plumbing systems as indicated on the plans. .3 Terminate fire protection supply within building with shut-off valve. Further details of fire protection work are specified in Section 15500. .4 Provide make-up water connections to heating and cooling systems and trapped condensate drains from all cooling equipment. 1.4 QUALITY ASSURANCE AND REGULATORY COMPLIANCE .1 Execute work of this section only by registered apprentices and licensed tradespersons regularly employed in the installation of all gas, plumbing, drainage piping systems, site water supplies, and drainage services. 1.5 SUBMITTALS .1 Submit shop drawings for all equipment. PART 2 - PRODUCTS 2.1 GENERAL .1 Supply, install, and completely connect all plumbing fixtures shown on all drawings including Architectural and Mechanical drawings. Be responsible for protection of all material and equipment until Owner accepts building. .2 All fixtures including trim shall be CSA approved, free from flaws or blemishes, and subject to approval of Consultant. .3 All finished surfaces shall be clear, smooth, and bright, and guaranteed not to craze, discolour, or scale. .4 All fixtures shall be completely installed and connected to drain, vent, hot, tempered and cold water piping in approved manner. .5 All visible parts of trimmings of all fixtures, including faucets, shower heads, piping, escutcheons, wastes, strainers, traps, tail pieces, supplies, stops, etc. shall be heavily chrome-plated. This shall also apply to work at all NIC equipment and fixtures. .6 Except where specifically noted otherwise, supply and install screwdriver stop valve on hot and cold water supply to every fixture, in addition to valve or faucets on fixture itself. .7 Provide adequate supports for all piping, equipment, and fixtures. Have these built into surfaces with back-up plates where support is required. .8 Provide traps on drains and stops on supplies for all fixtures and equipment. .9 Provide domestic water, vent and waste connections to all equipment requiring plumbing services. This shall include NIC items shown on architectural and mechanical drawings. .10 Provide shut-off valves on water connections at each piece of equipment. .11 Connect water and drain to all heating and air-conditioning systems and equipment noted in the specifications or shown on the drawings. .12 Provide rough-in and connections to all miscellaneous equipment as required. .13 Provide fixtures complete with all required trim. .14 All exposed trim to be chrome plated. Fixtures to be white unless specified otherwise. February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 2 .15 .16 .17 .18 .19 .20 .21 .22 .23 .24 Provide individual stops on each fixture water supply. Provide C.S.A. traps in required sizes with cleanouts. All supplies to be flexible chrome plated copper tube type. Braided flexes or plastic tubing are not acceptable. Piping shall be pitched and valves installed to facilitate complete drainage of the system. All piping run within the building shall be concealed in the finished portions of the building in pipe spaces, ceilings, or furred chases and exposed only in mechanical rooms and where indicated on the drawings. No pipe shall pass in front of or interfere with any openings, doors, or windows or points of access. Headroom in front of openings and doors shall in no case be lower than the top of the opening. No pipe shall pass in front of or interfere with clearances around mechanical equipment. Piping shall not pass exposed through electrical rooms, voice/data rooms, or be erected over any switchboard or other electrical gear (except as may be required by local code for fire suppression). 50mm (2”) clearance shall be provided between insulated piping and other obstructions. No union shall be placed in a location that will be inaccessible. Unions shall be installed adjacent to all equipment to allow for repair and replacement. Flexible piping connections shall be provided at piping connections to all rotating mechanical equipment, and at piping connections to all equipment mounted on vibration isolators. Connectors shall have a pressure rating suitable for the piping systems in which they are installed. 2.2 ACID NEUTRALIZER .1 Acid neutralizer - electronic monitoring - on floor or flush with floor: SMS Series AN MODEL No.. Acid Neutralizer with SI-XLG Sediment Interceptor, polyethylene tank with gasketed 30mm (1½") thick combination poly and non-skid aluminium scoriated cover with stainless steel bolts, MJ inlet, outlet and vent connection, 300mm (12") inspection cover, probe assembly with electronic and appropriate length of coaxial cable to reach panel from tank. Control panel consisting of Model 47 Ph monitoring alarm panel 120V; 5A draw. Provide extensions 'E' (if required) to meet invert of pipe. Fill with initial charge of limestone neutralizing chips 2" (50mm) dia. size. Spec. Note: if sediment interceptor is required, add "WITH SI-XLG SEDIMENT INTERCEPTOR" Spec. Note - Use the following in Part 3 as required [This trade to provide 1" ID (25mm) conduit from 19mm (¾") FIPS tank adapter to PH control panel. If coaxial cable is required to be more than 50' (18M) provide a PH Signal Amplifier.] 2.3 AIR COMPRESSOR AND DRYER SYSTEM .1 Existing compressor capacity shall be verified before tying in new devices. .2 When after coolers are specified on air compressors, they shall be air-cooled or shall be cooled with recirculating process water. Water cooling through equipment to a drain is not permitted. .3 Compressed air piping above grade shall be Schedule 40, black steel conforming to ASTM A 53. Fittings shall be malleable screwed end. .4 Provide an intergral compressor, receiver, motor and aftercooler unit with integral controls. All components to have ULC or CSA labeled. .5 Compressor shall be capable of 7.9 ALPS (16.8 ACFM) at 1205 kPa (175 PSIG). The unit shall have removable cyclinders, 2 stage compression, finned copper intercooler, lubrication and a cast iron block. .6 Receiver shall be ASME rated and shall have a copacity of 300 litres (80 gallons). The receiver shall be mounted vertically, and the campressor pre-piped to sit on top. .7 Motor to be TEFC and all electrical devices and controls to be located behind spray tight gasketted panels. Unit to automatically start and stop to maintain a user specified operating pressure. .8 Provide an ASME pressure relief valve sized for the maximum volume of air at 825 kPa (120 PSI). Locate downstream of receiver. .9 Provide auto vent with an adjustable release time, at the bottom. .10 Provide a refrigerated air dryer sized to maintain maximum 3.9 ºC (39ºF) dew point. The unit shall be designed to operate up to the mazimum pressure of the compressor. The refrigerant shall be R134A, and the unit shall operate automatically when the compressor is delivering air. Ingersol rand SDR aircooled dryer. .11 Provide an air pressure gauge and regulator discharge from the dryer. Unit to be capable of being locked in position to prevent vandalism. February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 3 .12 .13 .14 .15 .16 Quick Couplers: ARO full bore 9.5mm (3/8”). Provide 1 on each piping drop. Hose Reels: Provide two hose reels with auto rewind and 6 m of 9.5mm (3/8”) hose. Locate 1 over each work bench in the auto shop. Provide a quick connect on the end of each hose. Dirt pockets to be 150 mm (6”) deep, complete with ball valves and threaded end caps. Lubricators to be provided at each outlet with polycarbonate bowls. Air Filters: Provide a small micron filter with a three valve bypass, removable cartrige and auto drain. 2.4 AUXILLARY DOMESTIC WATER CONNECTION .1 National Fire Equipment Model 153 Wall Hydrant Connection, 1½” NPT female x 1½” male hose thread adapter, brass cap and chain, complete with brass escutcheon plate with raised lettering stating “WALL HYDRANT”. Water connection to be rated for a pressure of 300 psi. .2 Supply piping from hydrant shall be routed to incoming water service and connected upstream of premise isolation backflow device. .3 Install check valve and isolation valve on auxiliary water service pipe upstream of connection to permanent water service. 2.5 BACKFLOW PREVENTERS .1 Provide a backflow preventer on any piping supplying potable water to a heating, chilled water, condenser water, sprinkler or any process piping system where chemical treatment or anti-freeze solution is used or where chemicals are conveyed. Backflow preventers are to be compliant with the latest edition of CAN/CSA B64 as published by CSA. .2 Water service sizes ¾” and 1”: Union bronze body construction, stainless steel replaceable check, relief seats, shafts and bolts, rubber check valve and relief valve assemblies, bronze body quarterturn ball valves, bronze test cocks, bronze strainer. Unit to be equal to Watts C-U-909 QT-HW c/w Watts model 777 strainer. .3 Water service sizes 32mm (1¼”) to 50mm (2”): Bronze body construction, stainless steel replaceable check, relief seats, shafts and bolts, rubber check valve and relief valve assemblies, bronze body quarter-turn ball valves, bronze test cocks, bronze strainer. Unit to be equal to Watts 909 QT-HW, c/w Watts model 777 strainer. Provide union connections upstream and downstream of each backflow preventer. .4 Water service sizes 65mm (2½ ") and larger: Interior epoxy coated cast iron body with stainless steel internal parts, replaceable bronze seals, bronze relief valve with stainless steel trim, epoxy coated strainer, OS & Y resilient seated gate valves, bronze test cocks. Unit to be equal to Watts 909 QTHW, c/w Watts model 777 strainer. Provide union connections upstream and downstream of each backflow preventer. .5 65mm (2½ ") and larger: Reduced pressure zone assembly consisting of two independent torsion spring check modules, a differential pressure relief valve located between and below the two modules, two drip tight shut off valves and required torsion spring modules and relief valve to be contained within an accessible sleeve housing constructed from 304 schedule 40 stainless steel pipe with groove connections. Torsion spring checks shall have replaceable elastomer discs and in operation produce drip tight closure against the reverse flow of liquid caused by back pressure or back siphonage. Unit to be equal to Watts 957 OSY c/w model 77F-D1-FDA125 strainer c/w 408 OSY RW valve upstream of strainer. .6 Double check valve with intermediate atmospheric vent: Watts #9D continuous pressure type with intermediate atmospheric vent. Chrome plated where exposed in finished areas. .7 Hose bibb: 19mm (¾") #8 bronze body vacuum breaker with stainless steel internal parts. Chrome plated where exposed in finished areas. .8 Lab vacuum outlets: T & S Brass BL-4000-01 single cock or BL-4200-0 double cock units. .9 Backflow preventer drains: Pipe relief opening on backflow preventer to suitable drain. Diameter shall be a minimum of one pipe size larger than relief opening and be fitted with an approved air gap. .10 Provide minimum 32mm (1¼") clearance between backflow preventer body and adjacent structure (wall, ceiling, etc.) and equipment to facilitate removal. 2.6 BYPASSES .1 Bypasses shall be provided around all water meters, control valves, and pressure reducing stations. .2 Specified valves to be used in these applications. February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 4 2.7 CLEANOUTS .1 Line cleanouts: .1 Bibby 63900 series Line Cleanout, in cast iron pipe with taper thread cover secured to body with full size pipe opening. .2 Stack cleanouts: .1 Mifab C1460C1460 Stack Cleanout, in base of cast iron stacks with neoprene gasketed secured cover. .3 Floor cleanouts: .1 Provide cleanouts and covers as manufactured by Mifab and suitable for the specified floor finish. .2 All floor covers shall be set flush with the finished floor. .3 Covers shall be nickel bronze with V.P. screws as described below: .4 Exposed - standard M.J. or Bell and Spigot cleanout plug - no cover. .5 Concealed in non-accessible area - standard M.J. or Bell & Spigot cleanout plug with access door sized to suit. .6 Concrete floors - standard M.J. or Bell & Spigot cleanout plug with covers to suit floor finish equal to Mifab. Finished/unfinished with light traffic – C-1200-C-1-34 Finished/unfinished heavy traffic – C1200-C-4-34 Carpeted – C-1200-C-34-RCF Terrazzo – C-1200-C-34-US 2.8 DOMESTIC HOT WATER HEATERS .1 The installation shall include a steam hot water heating unit for winter use, and electric water heaters for summer use or other periods when steam is shut down on campus. .2 Provide where shown on the Drawings [and detailed in the equipment schedules], electric domestic hot water heater(s) with enamelled steel jacket over CFC free insulated [(l) gal. ] storage tank complete with [ ____ watt thermostatically controlled immersion heater], [storage tank and heater capacities as detailed in the equipment schedules] hose end drain valve, ASME rated relief valve and heavy duty anode rod as manufactured by Rheem/Ruud. Tank(s) of equivalent capacity and quality as manufactured by John Wood are also acceptable. 2.9 DOMESTIC HOT WATER HEATER - GAS FIRED FORCED DRAFT .1 Provide as shown on the Drawings, natural gas fired metal clad and insulated domestic hot water heater in size and capacity as described in the Equipment Schedules and with features as follows: .2 Constructed to ASME code Section IV and ULC requirements and hydro-statically tested at 190 psi minimum. Tank to be equipped with removable flange mounted modular energy package with a minimum diameter of 575mm (23"). Tank access to be by removal of this energy package. Provide an easily removable rear module access cover with a minimum diameter 575mm (23") for simplicity of tank access and energy package cleaning and maintenance. All fittings to be Type K copper. Only non-ferrous alloy tank connections to be provided. .3 Two operating thermostats set at 43.3C (110F) for lower and 48.90C (120F) for upper tanks respectively with maximum circulating water temperature in the plumbing system at 48.9C (140F). One temperature limiting device to prevent temperatures from exceeding 93.3C (200F). An ASME temperature and pressure relief valve set at 875 kPa (125 psi) and 98.9C (210F) maximum. .4 Unit insulation of heavy density fiberglass jacketed with segmented 22 gauge steel panels with factory baked enamel finish. Each panel to be interlocked for easy removal and replacement without causing damage. The entire water heater to rest on heavy duty skids. .5 Combustion chamber to be completely lined with copper. All fire tubes to be pure copper. .6 Forced draft power type burner with cast aluminium housing that provides an overfire pressure in the module and all heating surfaces. Burner motor with electrical power characteristics in keeping with project design power supply. .7 Start-up by factory authorized personnel. .8 Additional features: .1 Additional nickelshield module protection .2 Polyshield overcoating February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 5 .3 .4 .5 .6 .7 Dial thermometer and pressure gauges Low water cut-off Three-year warranty against defects and workmanship, corrosion and erosion for the energy module (to be submitted with shop drawings). Manufacturer's ten year warranty and service policy (to be submitted with shop drawings). Warranties to start on the date of acceptance by the Consultant. Acceptance will be granted on review and approval, by the Consultant, of start-up report. Refer to equipment schedules for capacity information. 2.10 FLOOR DRAINS .1 Provide cast iron body floor drains with nickel bronze strainers, clamping ring, drainage flange, weep holes, and reversible collars. Drain shall be capable of withstanding area use. .2 Drains shall be as manufactured by Ancon or Zurn, and in accordance with the following: .1 Floor drains – Watts FD-100-C-A .2 Funnel floor drains – Watts FD-100-C-EG. .3 Hub drains – Watts FD-100-C-DD. .4 Shower drains – Watts FD-100-C-F. .5 Elevator sump drain – Watts BV-600 – with bronze backwater valve .6 Rack washer drain – Watts FS-=740-3-22 2.11 FUEL OIL STORAGE TANK .1 Provide standard domestic type fuel oil storage tank, 1,136.5L (250 Imp. Gal.). .2 Capacity: Complete with legs, and all required tapings for fill, vent, and suction lines as shown on the drawings; coated with one coat red oxide primer; manufactured to U.L.C. - S602 latest edition and as required by Authorities. Approximate dimensions - 600 mm wide x 1200 mm high x 1800 mm long (24" x 48" x 72"). .3 Standard of Acceptance: Westeel Rosco 2.12 GAS DETECTION UNIT .1 Provide Macurco CD-2, 12-24V input electronic gas detection unit complete with relay and solenoid controlled gas shut off valve to be mounted down-stream of the Instructor’s control valve. Mount gas detection unit one foot below highest point of ceiling. Provide gas detection units in all new rooms with gas turrets. .2 Electrical to provide dedicated 120V power supply to gas detection unit c/w transformer (120V – 24V DC). Review installation with authority having jurisdiction. 2.13 GREASE INTERCEPTORS .1 Grease interceptor - flush with floor type: Smith Series 8000-AC-35 Grease Interceptor, duco coated inside and outside CR steel enzyme type, removable baffles, aluminium gasketed cover with lock and lift ring, flow control device, deep seal trap with cleanout and bottom debris trapping leg. Flow rating of 35 GPM (132LPM) and grease capacity for 70 pounds (32KG). Provide extension 'E' (if required) to meet invert of pipe. Where interceptor is suspended, provide 'S' suspension with waterproofing flange adequately supported from structure. .2 Grease interceptor - on floor type: Smith Series 8100-AC-35 for on-floor low rough-in, duco coated inside and outside CR steel enzyme type, removable baffles, aluminium gasketed cover with lock and lift ring, flow control device, deep seal trap with cleanout and bottom debris trapping leg. Flow rating of 35 GPM (132LPM) and grease capacity for 70 pounds (32KG). 2.14 HOSE BIBBS .1 HB-1 HOSE BIBBS – INTERIOR: .1 Waltec #27W-833 12mm (½") chrome plated with flange and 76065 hose end vacuum breaker. .2 HB-2 HOSE BIBBS – EXTERIOR: .1 Provide 20mm (¾") non-freeze wall faucet with nickel bronze face and box, adjustable wall flange, vacuum breaker and operating key. Length to suit wall thickness. Install 600mm (24”) above finished grade. .2 Standard of Acceptance: Watts HY-725-VB February 27, 2015 University of Manitoba PLUMBING Section 15400 Req # Page 6 .3 .4 .5 HB-3 INTERIOR WASHDOWN: .1 Watts 912HP, 20mm (¾") size wall faucet with ¼ turn ceramic disc cartridge, nickel bronze face and box, wall flange, operating key and vandal proof lock assembly and self-draining vacuum breaker. HB-4 EXTERIOR GROUND HYDRANT: .1 Smith series 5810HNB 20mm (¾") non-freeze with bronze face and box, operating key and self-draining vacuum breaker. Length to suit frost depth. W-1 WASHING MACHINE HOT/COLD SUPPLY: .1 Symmons ‘Eliminator’ #W-600-X single lever operated valve, hose end outlets, copper liner, service stops, 12mm (½”) H & CW connection, 38mm (1½”) drain outlet, provide ‘P’ Trap cast brass, 38mm (1½”) concealed in wall. 2.15 HOT WATER DISPENSER .1 Provide instant electric hot water dispenser where shown on the drawings and as specified. .2 Dispensers shall be equal to Emerson InSinkerator TranScape H-Wave-SS model. .3 Capacity; 2.5 litres storage, 14 litres per hour of 90ºC water. .4 Unit to have self-closing valve and adjustable thermostat. .5 Electrical: 120 Volts, 750 watts, 6.25 amp with 3-prong plug .6 Unit to have 3 year warranty and have chrome finish. 2.16 HYDRO-PNEUMATIC TANK .1 Provide a Well-X-Trol Model #WX-4xxC pressurized diaphragm type hydro-pneumatic tank as manufactured by Amtrol Incorporated. .2 Suitable and approved for use on a potable water system, ASME certified for a working pressure of 860 kPa (125 psig). .3 Tanks to have replaceable, full acceptance bladders. .4 Capacities: Drawdown - litres (gallons) Operating pressures - kPa (psi) Size - WX-000 2.17 MANHOLES AND CATCHBASINS .1 Manholes 900mm (36”) diameter pre-cast concrete as manufactured by Supercrete or approved equal. Provide frames and covers in accordance with current local standards. See detail drawings. Where diameter of incoming or leaving pipe exceeds 600mm (24”) use 1500mm (60”) diameter manhole. .2 Catchbasins as detailed on the drawings or pre-cast type as manufactured by Supercrete, with grates, frames, and traps conforming to municipal requirements. 2.18 OIL INTERCEPTORS .1 Zurn # Z-885-200 –CB polyethylene oil interceptor size 600, polyethylene 6mm (¼”) thick body, c/w heavy-duty Dura coated steel frame and 6mm (¼”) thick steel diamond plate covers with heavy-duty top frame and reinforced steel cover, black acid resistant coated top, 757-L (200-gallon) capacity, with extension to suit invert depth from trench drain, with 100mm (4”) inlet and outlet connections. .2 Oil interceptor with secondary chamber - flush with floor: Smith Series 8500-SC-TPT-35 Oil Interceptor With Secondary Chamber, duco coated inside outside CR steel, removable sediment basket, baffles, gasketed cover, with lock and lift rings integral flow control device, automatic draw-off double vent connection, deep seal trap with cleanout and bottom debris trapping leg. Flow rating of 35 GPM (125LPM). Provide extension 'E' (if required) to meet invert of pipe. (TPT - trap primer tapping). Provide 2" (50mm) connecting piping between the interceptor and secondary chamber and two 2" (50mm) vents to roof. All to manufacturer's and local code requirements. 2.19 PLUMBING FIXTURES AND BRASS Note: All components to be installed as per manufacturer specifications, e.g. electronic flush valves to be installed c/w vertical mounted electrical boxes, etc. for any other clarifications contact U of M Plumbing Shop. February 27, 2015 University of Manitoba PLUMBING Req # Section 15400 Page 7 1. (WC-1) WALL MOUNTED FLUSH VALVE WATER CLOSET: Crane 3446 Placidus vitreous china, siphon jet closet bowl with elongated rim and self-draining jet, bolt caps 1½” top spud. (6 litre) - American Standard as equal Vision/Aquanar 2031-0 electronic flush valve complete with 1” angle stop, vacuum breaker, flush tube, 6 volt DC plug-in transformer supplied with each unit, slow closing solenoid, 12-hour automatic flush and manual over-ride button. Integral sensor to be mounted above open-seat height to ensure sensing beam is not blocked at any time. Transformer is to be mounted in pipe shafts where applicable, otherwise in ceiling space. Sloan as equal. Our standard installation includes a sensor-controlled flush valve. However, if a standard flush valve is to be used for this fixture, use Crane 402VB Presto exposed chrome plated flush valve with anti-siphon device, vandal resistant cap, oscillating handle, vacuum breaker, cast wall flange with setscrew, and escutcheon. - Sloan Royal #111 as equal. Bemis open front elongated seat less cover and white colour # 1955CT. c/w stainless steel bolt/nut and washer. - Centoco as equal Zurn CarriersZ-1203 Single Horizontal - Z-1204 Single Vertical Z-1203-ND4 Double Horizontal Z-1204-ND4 Double Vertical Ancon/Watts Carriers as equal 2. (WC-2) WALL MOUNTED FLUSH VALVE WATER CLOSET – UNIVERSAL ACCESS: Crane 3446 Placidus vitreous china, siphon jet closet bowl with elongated rim and self-draining jet, bolt caps 1½” top spud. Unit to be installed at 410 mm (16”) finished floor to rim. (6 litre) - American Standard as equal Vision/Aquanar 2031-0-T36-22 electronic flush valve complete with 1” angle stop, vacuum breaker, flush tube, 6 volt DC plug-in transformer supplied with each unit, slow closing solenoid, 12-hour automatic flush and manual over-ride button. Integral sensor to be mounted above open-seat height to ensure sensing beam is not blocked at any time. Transformer is to be mounted in pipe shafts where applicable, otherwise in ceiling space. Sloan as equal. Long flush tube & wall bracket. Our standard installation includes a sensor-controlled flush valve. However, if a standard flush valve is to be used for this fixture, use Crane 402VB Presto exposed chrome plated flush valve with anti-siphon device, vandal resistant cap, oscillating handle, vacuum breaker, cast wall flange with setscrew, and escutcheon. – Sloan Royal #111 as equal. Bemis open front elongated seat with cover and white colour #7650T. c/w stainless steel bolt/nut and washer. – Centoco as equal Zurn CarriersZ-1203 Single Horizontal - Z-1204 Single Vertical Z-1203-ND4 Double Horizontal Z-1204-ND4 Double Vertical Ancon/Watts Carriers as equal 3. (WC-3) FLOOR MOUNTED FLUSH VALVE WATER CLOSET Crane 3325 Whirlton vitreous china, siphon jet closet bowl with elongated rim and self-draining jet, bolt caps, 1½” top spud. (6 litre) - American Standard as equal Vision/Aquanar 2031-0 electronic flush valve complete with 1” angle stop, vacuum breaker, flush tube, 6 volt DC plug-in transformer supplied with each unit, slow closing solenoid, 12-hour automatic flush and manual over-ride button. Integral sensor to be mounted above open-seat height to ensure sensing beam is not blocked at any time. Transformer is to be mounted in pipe shafts where applicable otherwise in ceiling space. Sloan as equal Our standard installation includes a sensor-controlled flush valve. However, if a standard flush valve is to be used for this fixture, use Crane 402VB Presto exposed chrome plated flush valve with anti-siphon device, vandal resistant cap, oscillating handle, vacuum breaker, cast wall flange with setscrew, and escutcheon. – Sloan Royal #111 as equal. Bemis open front elongated seat less cover and white colour #1955CT. c/w stainless steel bolt/nut and washer. – Centoco as equal February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 8 4. (WC-4) FLOOR MOUNTED FLUSH VALVE WATER CLOSET – UNIVERSAL ACCESS: Crane 3816 Hymont Jr., vitreous china, 410mm (16”) high, siphon jet closet bowl with elongated rim and self-draining jet. 38mm (1½”) top spud, bolt caps. (6 litre) - American Standard as equal Vision/Aquanar 2031-0-T36-22 electronic flush valve complete with 1” angle stop, vacuum breaker, flush tube, 6 volt DC plug-in transformer supplied with each unit, slow closing solenoid, 12-hour automatic flush and manual over-ride button. Integral sensor to be mounted above open-seat height to ensure sensing beam is not blocked at any time. Transformer is to be mounted in pipe shafts where applicable otherwise in ceiling space. Long flush tube & wall bracket. Our standard installation includes a sensor-controlled flush valve. However, if a standard flush valve is to be used for this fixture, use Crane 402VB Presto exposed chrome plated flush valve with anti-siphon device, vandal resistant cap, oscillating handle, vacuum breaker, cast wall flange with setscrew, and escutcheon. – Sloan Royal #111 as equal. Bemis open front elongated seat with cover and white colour #7650T. c/w stainless steel bolt/nut and washer. – Centoco as equal 5. (WC-5) FLOOR MOUNTED FLUSH TANK WATER CLOSET Crane Cranada II #31183 vitreous china, siphon jet, whirlpool action, close-coupled closet combination with elongated rim bowl and lined tank. (6 litres) – Kohler Cimarron as equal #K-11451 (4.8 litres) Bemis open front elongated seat, less cover, elongated, white colour #1955CT. c/w stainless steel bolt/nut and washer. – Centoco as equal Flexible 9mm x 300mm (3/8” x 12”) WC # 1-12DLC Brass Craft chrome plated copper supply. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 6. (WC-6) FLOOR MOUNTED FLUSH TANK WATER CLOSET – UNIVERSAL ACCESS Crane 3813 Hymount Jr. vitreous china, siphon jet, close-coupled combination with elongated rim bowl, 16” high self-draining jet – bolt caps – lined tank. (6 litre) – Kohler Cimarron as equal #K-11451 (4.8 litres) Bemis open front elongated seat with cover, white colour #7650T. c/w stainless steel bolt/nut and washer. – Centoco as equal Flexible 9mm x 300mm (3/8” x 12”) WC # 1-12DLC Brass Craft chrome plated copper supply. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 7. (UR-1) URINAL Crane Cromwell #7397 (3.8 litres) Top Spud vitreous china washout, wall hung urinal with flushing rim, C4004 stainless steel strainer, and C1206 hanger. Outlet connection to be C4036 I.P.S. (No PVC urinal flanges to be used). - American Standard as equal – Washbrook #AF6500 Vision/Aquanar 2131-0 electronic urinal flush valve complete with ¾ angle stop, vacuum breaker, flush tube, 24 volt plug-in transformer supplied with each unit, integral sensor, slow closing solenoid. Transformer is to be mounted in pipe shafts where applicable otherwise in ceiling space. Sloan as equal Our standard installation includes a sensor-controlled flush valve. However, if a standard flush valve is to be used for this fixture, use Crane 451 VB c/w integral vacuum breaker, vandal resistant cap and cast wall flange with set screw. - Sloan Royal 186-1 as equal Zurn Carrier – Z-1222 – Ancon/Watts as equal 8. (L-1) VANITY (COUNTER-TOP) LAVATORY Kindred OV-1821/6 18 gauge 18-10 stainless steel drop-in vanity basin with front overflow. Basin to be fully undercoated, 4” punching. Vision/Aquanar 1870-P-D-4-M4 electronic lavatory supply fitting complete with heavy cast brass chrome-plated high-rise spout with integral sensor, (only manufacturer supplied, faucet assembly braided stainless steel flex may be used), in-line filter, 24 volt plug-in transformer supplied with each unit, slow closing solenoid. Transformer is to be mounted under counter top – for alternate location contact U of M Plumbing Shop. Sloan as equal Our standard installation includes a sensor-controlled faucet set. However, if a standard faucet set is to be used for this fixture, used Crane P 1050 one-piece centre set, lavatory supply fitting with chain lug, water economy aerator, 4” centres 5 rib handles. Only cast brass (Crane P 3902) chrome plated lavatory P.O. plug with open strainer 32mm (1¼”) tailpiece, locknut and gasket. Only cast brass (Crane P 4002) 32mm (1¼”) chrome plated adjustable P-Trap with clean out. February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 9 Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 9. (L-2) VANITY (COUNTER-TOP) LAVATORY UNIVERSAL ACCESS Franke OV1821/5 – 5” deep, 18-gauge, 18-10 stainless steel drop-in vanity basin with front overflow. Basin to be fully undercoated, 4” punching. Vision/Aquanar 1870-P-D-4-M4 electronic lavatory supply fitting complete with heavy cast brass chrome-plated high-rise spout with integral sensor, (only manufacturer supplied, faucet assembly braided stainless steel flex may be used), in-line filter, 24 volt plug-in transformer supplied with each unit, slow closing solenoid. Transformer is to be mounted under counter top – For alternate location contact U of M Plumbing Shop. Sloan as equal Our standard installation includes a sensor-controlled faucet set. However, if a standard faucet set is to be used for this fixture, used Crane P 1030 one-piece centre set, lavatory supply fitting with aerator and 2¾” mini-blade handles. Only cast brass (Crane P 3906) 32mm (1¼”) chrome plated offset waste assembly with open grid strainer. Drain line to be insulated. True Bro Lav. Guard – kit # 103 Only cast brass (Crane P 4002) 32mm (1¼”) chrome plated adjustable P-Trap with clean out. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 10. (L-3) WALL-HUNG LAVATORY Crane 1-412V Harwich, vitreous china wall hung lavatory with 4½” high integral back, front overflow. 20” x 18” complete with 4” centres. Vision/Aquanar 1870-P-D-4-M4 electronic lavatory supply fitting complete with heavy cast brass chrome-plated high-rise spout with integral sensor, (only manufacturer supplied, faucet assembly braided stainless steel flex may be used), in-line filter, 24 volt plug-in transformer supplied with each unit, slow closing solenoid. Transformer is to be mounted under basin – for alternate location contact U of M Plumbing Shop. Sloan as equal Our standard installation includes a sensor-controlled faucet set. However, if a standard faucet set is to be used for this fixture, used Crane P 1030 one-piece 4” centre set, lavatory supply fitting with aerator and 2¾” mini-blade handles. Only cast brass (Crane P 3902) chrome plated lavatory P.O. plug with open strainer 32mm (1¼”) tailpiece, locknut and gasket. Only cast brass (Crane P 4002) 32mm (1¼”) chrome plated adjustable P-Trap with clean out. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 Zurn H.D. floor support concealed carrier.# Z-1231 – Ancon/Watts as equal Our standard installation includes a floor mounted fixture carrier to withstand rough treatment. This requires attention by the Architectural designer. However, in the case where standard use is expected, use a Crane C1201 concealed wall carrier. (To be used only with the U of M written permission). 11. (L-4) WALL-HUNG LAVATORY – UNIVERSAL ACCESS: Crane 1-412V Harwich, vitreous china wall hung lavatory with 4½” high integral back, front overflow. 20” x 18” complete with 4” centres. Vision/Aquanar 1870-P-D-4-M4 electronic lavatory supply fitting complete with heavy cast brass chrome-plated high-rise spout with integral sensor, (only manufacturer supplied, faucet assembly braided stainless steel flex may be used), in-line filter, 24 volt plug-in transformer supplied with each unit, slow closing solenoid. Transformer is to be mounted under basin – for alternate location contact U of M Plumbing Shop. Sloan as equal Our standard installation includes a sensor-controlled faucet set. However, if a standard faucet set is to be used for this fixture, use Vision/Encore KN83-4104-CE1 or CE4 one-piece 4” centre set, lavatory supply fitting with aerator and 2¾” mini-blade handles. Only cast brass (Crane P 3906) 32mm (1¼”) chrome plated offset waste assembly with open grid strainer. Drain line to be insulated. True Bro Lav. Guard – kit # 103 only cast brass (Crane P 4002) 32mm (1¼”) chrome plated adjustable P-Trap with clean out. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 Zurn H.D. floor support concealed carrier. # Z-1231 – Ancon/Watts as equal Our standard installation includes a floor mounted fixture carrier to withstand rough February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 10 treatment. This requires attention by the Architectural designer. However, in the case where standard use is expected, use a Crane C1201 concealed wall carrier. (To be used only with the U of M written permission). 12. S-1 STAINLESS STEEL SINK: Franke LBS6808-P-1/3 18 gauge, Type 304, 18-10 stainless steel – 20” x 20½” x 8” deep, fully undercoated, single bowl stainless steel sink with back ledge. Vision/Encore KN41-8108-SE1 5 rib fluted handle, sink supply fitting with cover plate and 7¾” long spout, aerator. 1½” DWV cop. x cop. rough brass, P-Trap with clean out. (chrome traps required in exposed areas) Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 13. S-2 STAINLESS STEEL SINK – UNIVERSAL ACCESS: Franke ALBS6805P-1/3 18 gauge – Type 304, 18-10 stainless steel – 20” x 20½” x 5” deep, fully undercoated, single bowl stainless steel sink with back ledge and 3½” crumb cup and offset rear waste. Vision/Encore KN41-8108-SE4 lever handle, sink supply fitting with cover plate and 7¾” long spout, aerator. 1½” DWV cop. x cop. rough brass, P-Trap with clean out. (chrome traps required in exposed areas) Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 14. S-3 TWO COMPARTMENT SINK Franke LBD6408-P-1/3, 18 gauge - Type 304, 18-10 stainless steel - 31¼” x 20¼” x 8” deep fully undercoated, two-compartment sink with spillway, back ledge, 3½” crumb cups and offset rear waste. Vision/Encore KN41-8108-SE1 lever handle, sink supply fitting with one-piece cover plate 7¾” long spout, aerator. 1½” DWV cop. x cop. rough brass, P-Trap with clean out. (chrome traps required in exposed areas) Continuous waste to be DWV copper pipe and fittings c/w brass tail pieces and brass slip nuts. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 15. S-4 LABORATORY HAND WASH SINK – WALL HUNG – UNIVERSAL ACCESS Franke WHB1617/316-3/3, 316 stainless steel – 17” x 16” x 6” deep overall size, single compartment wall hung sink with back ledge. Vision/Aquanar 1876-P-D-4-M4 electronic lavatory supply fitting complete with heavy cast brass chrome-plated high-rise spout with integral sensor, (only manufacturer supplied, faucet assembly braided stainless steel flex may be used), in-line filter, 24 volt plug-in transformer supplied with each unit, slow closing solenoid. Transformer is to be mounted under sink – for alternate location contact U of M Plumbing Shop. Sloan as equal 1½” DWV lab waste material (e.g. fuseal) P-Trap with clean-out Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 16. S-5 HANDWASH SINK – WALL HUNG – UNIVERSAL ACCESS Franke WHB1617/304-3/3, 304 stainless steel - 17” x 16” x 6” deep overall size, single compartment wall hung sink with back ledge. Vision/Aquanar 1876-P-D-4-M4 electronic lavatory supply fitting complete with heavy cast brass chrome-plated high-rise spout with integral sensor, (only manufacturer supplied, faucet assembly braided stainless steel flex may be used), in-line filter, 24 volt plug-in transformer supplied with each unit, slow closing solenoid. Transformer is to be mounted under sink – for alternate location contact U of M Plumbing Shop. Sloan as equal 1½” DWV cop. x cop. P-Trap with clean-out (chrome traps required in exposed areas) Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 17. S-6 SERVICE SINK: Fiat SB-3636, 900 x 900 x 150 (36” x 36” x 6”) high terrazzo mop service basin complete with February 27, 2015 University of Manitoba PLUMBING Req # Section 15400 Page 11 stainless steel caps on all sides not against a wall. Sink to have maximum 150mm (6”) high side to allow floor wash machines to be drained easily. Sink shall be places in a bed of grout as per Manufacturer’s instructions to avoid cracks due to uneven floors. Vision/Aquanar KC77-5147 VY6 (less pipe support) sink supply fitting with pail hook and brace to wall above spout hose end, backflow preventer, cross handles and index buttons. Flexible hose c/w S.S. bracket to assist in filling the machines and pails. #832AA Watts No. 7 dual check back flow preventer with union fittings and water service isolation valve. Install and connect to housekeeping chemical dispenser. #7U-2 18. S-7 LAUNDRY SINK: Fiat FLTD-II floor mounted twin compartment moulded sink with metal stand. Vision/Encore KN41-8108 SE-1 sink (faucet with 8” centre, aerator) 1½” DWV cop. x cop. P-trap c/w clean-out Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 19. S-8 HOSPITALITY SINK: Franke LBS1308P-1/2 - single bowl back ledge stainless steel sink with crumb cup strainer. Vision/Encore KN83-4102-RE1 gooseneck supply. c/w 3” blade handles 1½” DWV cop. x cop. P-trap c/w clean-out (chrome traps required in exposed areas) Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 20. S-9 STAINLESS STEEL LAB SINK: Franke 18 gauge LBS6808-316-1/3, 20½” x 20” x 8” deep 316 stainless steel single compartment sink with back ledge and 3½” crumb cup. Brass to be Delta W6740-9 8” centreset gooseneck spout with 4½” blade handles with colour coded indexing. Spout to be locked solid and straightforward to prevent vandalism. 1½” DWV lab waste material (e.g. fuseal) P-trap with clean-out c/w 1½” x 3” stainless steel tail piece with brass slip joint nut. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 21. S-10 STAINLESS STEEL LAB SINK – UNIVERSAL ACCESS: Franke 18 gauge ALB56805/316-1/3, 20½” x 20” x 5” deep 316 stainless steel single compartment sink with back ledge and 3½” crumb cup and offset waste. Brass to be Delta W6740-9 8” centreset gooseneck spout with 4½” blade handles with colour coded indexing. 1½” DWV lab waste material (e.g. fuseal) P-trap with clean-out c/w 1½” x 3” stainless steel tail piece with brass slip joint nut. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 22. S-11 LAB SINK – COLD WATER ONLY: Franke 20 gauge - Oval (3” x 6”) # OC6/316 Type 316 - Round – (6”) # RC6/316 Type 316 Brass to be Delta W6600-9 with gooseneck spout and two arm lab handles 1½” DWV lab waste material (e.g. fuseal) P-trap with clean-out c/w 1½” x 3” stainless steel tail piece with brass slip joint nut. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 23. S-12 KINDERGARTEN ART SINK: Architectural Metal Industries 1025-C, 27” x 22½” x 13½ x 9” deep, inside dimensions 24” x 18”, right-side ledge, 316 stainless steel single compartment art room sink with 3½” crumb cup. Vision/Encore KN41-8108 SE1 sink supply fitting with one-piece cover plate 7¾” long spout aerator. Zurn Z-11 80 solids interceptor. Flexible 9mm x 300mm (3/8” x 12”) Basin # 1-12AC Brass Craft chrome plated copper supplies. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) # 211-13-31 Kindergarten sinks to be supplied with tempered hot water. Provide tempering valve sized for February 27, 2015 University of Manitoba PLUMBING Section 15400 Req # Page 12 system water demand and locate in locked cabinet. 24. WF-1 WASHFOUNTAIN: Acorn 4 station Quad-Lav 46" #3604-SO-PDM-MXP-BF Precast, terrazzo construction, structurally reinforced, ground, polished and finished with clear epoxy coating. Colour to be selected by Architect. Dimensions: 46" wide, 26" deep, 41" high. Rim height: 34"; clearance under rim; 29.5". Preassembled bowl module to consist of receptor with backsplash and sprayhead, equipped with supply manifold, factory pre-piped and tested. Integral sprayhead to be equipped with four spray nozzles capable of delivering 0.5 GPM (0.03 l/s) each. Valving to include combination stop and check valves and strainer and a thermostatic mixing valve, 12mm (1/2") supply inlets. Pedestal to consist of stainless steel mounting panel and precast terrazzo side panels. Front access panel of heavy gauge stainless steel to have vandal resistant closure. Control: sensor operated with 24 VAC transformer, 12 AMP on a universal mount. 25. SH-1 SHOWER: Powers - Hydro Guard T/P Series e700 Model #E707G2000 temperature and pressure compensating valves, Low Flow 1.5 gpm Chrome Plated Showerheads, Deluxe Arm & Flange, c/w integral stops – Moen as equal. 26. SH-2 SHOWER – UNIVERSAL ACCESS: Powers – Hydro Guard T/P Series e420 Universal Access Model #E420S12G21YW Combination Tempering Valves c/w Dome Lever (ADA Compliant) Low Flow 1.5 gpm Chrome Plated Showerheads, Deluxe Arm & Flange, 24” Chrome ADA Wall Grab Bar System, Concealed Diverting Valve, In-Line Vacuum Breaker and integral stops – Moen as equal. 27. SH-3 SHOWER: Powers – Hydro Guard T/P Series e420 Model #E420S1200070W Combination Tempering Valves c/w Dome Lever (ADA Compliant), Professional, Vinyl Hose, 24” Slide Bar, In-Line Vacuum Breaker and integral stops – Moen as equal. 28. SH-4 SHOWER: Powers – Hydro Guard ESPTM Pushbutton Sensor Shower for Single Shower Application Model #447-3-00-IC-N0-0-0 and comes with 444-119 Transformer. Pushbutton shower systems rely on Piezo Sensor Technology, Thermostatic Valve #LMC490 required (to temper water) c/w Institutional (141381) Showerhead and integral stops – Moen as equal. 29. MV-1 MIXING VALVE: Powers Model # ES-P-SF-LM490-BTSRC HYDROGUARD Master Tempering Fixture Series LM 490 Bottom Inlets/Top Outlet – Semi-Recessed Cabinet. Valve Supply MV-2 MIXING VALVE: Powers Model # ES-P-SF-LM490-BTRC HYDROGUARD Master Tempering Fixture Series LM 490 Bottom Inlets/Top Outlet – Recessed Cabinet. Valve Supply 30. 31. W-1 WASHING MACHINE SUPPLY: Symmons Laundry-Mate – Supply and Drain Fixture W-600 Series Model # W-600-X Supply and Drain Fixture with ½ inch sweat union all connections and 1½ inch drain connections c/w service stops. 1½” DWV cop.x cop.P-trap c/w clean-out 32. G-1 GAS/Air/Vacuum/Steam Turrets: Delta-Teck Commercial W6220 ball valve hose cocks. 33. EW-1 EMERGENCY EYEWASH: .1 Haws Model 7360BTWC eye/face wash with 280 (11”) diameter stainless steel bowl, twin plastic wash heads with flip covers and push handle, anodized aluminum mounting bracket and trap, and a fully serviceable in-line strainer. February 27, 2015 University of Manitoba PLUMBING Section 15400 Req # Page 13 .2 .3 .4 .5 .6 34. Supply: 12mm (½"). 32mm (1¼”) tailpiece and trap assembly. For single fixtures, provide a Leonard TA-300-STSTL-REC thermostatic mixing valve complete with check valves to maintain water supply temperature within +/- 3°F (1.1°C) of set point. Set at 95°F (35°C). Mixing valve to provide shut off if cold water supply fails to prevent scalding. Unit to be installed in 250mm x 300mm x 165mm (10” x 12” x 6½”) deep stainless steel enclosure cabinet with full height piano hinge and keyed lock. Haws shower blending valve for multiple eye or face wash fixtures. Blending valve shall have fail-safe back up and liquid thermal thermostats with tamper resistant control adjustment. System to shut off all incoming hot water should cold water supply fail. Redundant thermostatic elements provide tempering even when one element fails. Should the hot water supply become interrupted, or the thermostatic elements fail, the valve will go into cold water bypass flow. Twin thermostatic elements respond independently to changes in incoming hot and cold water temperatures to maintain outlet temperatures to within 5°F (2.5°C). Varying conditions can be up to a 30°F (16°C) change in hot water temperature, 30°F (16°C) change in cold water temperature, and a 50% drop in inlet supply pressure. Factory set at 90°F (32°C). The valve is constructed of bronze, brass, copper and stainless steel, and contains easy to replace thermostatic cartridges. System to include 3 temperature gauges for performance monitoring, 1¼" IPS inlet and outlet; maximum inlet pressure is 125 PSI. Inlets can be attached from top or bottom. Provide isolation check valves for both supplies. Provide 250mm x 300mm x 165mm (10” x 12” x 6½”) deep stainless steel enclosure cabinet with full height piano hinge and keyed lock, full recessed or semi-recessed as shown on drawings. EW - 2 EMERGENCY EYEWASH & DELUGE SHOWER: .1 Haws Model 8300 combination unit features a 10" ABS plastic showerhead and twin ABS plastic anti-surge eyewash heads. .2 Unit to be complete with a stainless steel pull rod and a stay-open shower valve. .3 Activation for the eyewash to be by either stainless steel push flag or foot treadle assembly. Pedestal mounting to include a hot dipped galvanized steel pipe. .4 Supply: 1¼" IPS, Waste: 1¼" IPS. .5 Emergency equipment models are certified by CSA to meet the ANSI Z358.1 - Standard for Emergency Eyewash and Shower Equipment. .6 For single fixtures, provide a Leonard TA-300-STSTL-IT thermostatic mixing valve thermostatic mixing valve complete with check valves to maintain water supply temperature within +/- 1.1°C (3°F) of set point. Set at 95°F (35°C). Mixing valve to provide shut off if cold water supply fails to prevent scalding. Unit to be installed in 250mm x 300mm x 165mm (10” x 12” x 6½”) deep stainless steel enclosure cabinet with full height piano hinge and keyed lock, full recessed or semi-recessed as shown on drawings. .7 Provide Leonard TM-850-STSTL-IT mixing valve for multiple eye or face wash fixtures and emergency deluge showers with flows up to 60 GPM or Leonard TM-5125-STSTL- IT mixing valve for multiple eye or face wash fixtures and emergency deluge showers with flows up to 120 GPM. Fail safe back up: Liquid thermal thermostats with tamper resistant control adjustment. System shuts off all incoming hot water should cold water supply fail. Redundant thermostatic elements provide tempering even when one element fails. Should the hot water supply become interrupted, or the thermostatic February 27, 2015 University of Manitoba PLUMBING Req # Page 14 .8 elements fail, the valve will go into cold water bypass flow. Twin thermostatic elements respond independently to changes in incoming hot and cold water temperatures to maintain outlet temperatures to within 5°F (2.5°C). Varying conditions can be up to a 30°F (16°C) change in hot water temperature, 30°F (16°C) change in cold water temperature, and a 50% drop in inlet supply pressure. Factory set at 80°F (26°C). The valve is constructed of bronze, brass, copper and stainless steel, and contains easy to replace thermostatic cartridges. System includes 3 temperature gauges for performance monitoring, 1¼" IPS inlet and 1¼" or 1½" outlet (depending on model selected); maximum inlet pressure is 125 PSI. Inlets can be attached from top or bottom. Isolation check valves are included for both supplies. Provide factory stainless steel enclosure cabinet with full height piano hinge and keyed lock, full recessed or semi-recessed as shown on drawings. 35. GI-1 GREASE INTERCEPTOR: Watts series GI-135L epoxy coated inside and outside fabricated steel grease interceptor with flow rating of 35 GPM and grease capacity of 70 lbs. Unit shall include one piece removable multi-weir baffle assembly, code approved deep seal trap, cover securing handles, powder or liquid injection port, stainless steel calibrated orifice plate and recessed “non-skid” rectangular cover. Zurn as equal. 36. DF-1 WALL MOUNTED DRINKING FOUNTAIN/BOTTLE FILLING STATION: EZH2O System Cooler/Bottle Filling Station Kit Elkay Model # EZS8WSLK – Refrigerated/Filterless 1½” DWV cop. x cop. P-trap c/w clean-out and 1½” MIP with 1½” with 1¼” brass slip nut for fixture connection Flexible 9mm x 300mm (3/8” x 12”) Basin #1-12AC Brass Craft chrome plated copper supply. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) #211-13-31 37. DF-2 WALL MOUNTED DRINKING FOUNTAIN/BOTTLE FILLING STATION - UNIVERSAL ACCESS: EZH2O System Cooler/Bottle Filling Station Sit Elkay Model # EZS8WSLK – Refrigerated/Filterless 1½” DWV cop. x cop. P-trap c/w clean-out and 1½” x 1¼” brass slip nut for fixture connection Flexible 9mm x 300mm (3/8” x 12”) Basin #1-12AC Brass Craft chrome plated copper supply. Dahl mini ball valve chrome angle stop (1/2” x 3/8”) #211-13-31 38. SDS-1 SINK DRAINAGE SYSTEM Complete under counter sink drainage system including: .1 .2 .3 .4 .5 .6 .7 2.20 Section 15400 Goulds Model SP035V, 1/3 HP, 3/8” solids handling pump 7-gallon polyethylene basin 2” threaded bent 1 ½” threaded inlet and discharge 1 ½” schedule 40 PVC internal discharge pipe. Tank to be 16” diameter x 14 ½” high Unit to be Goulds Model SDS2 sink drainage system/Little Giant as equal. PRESSURE RELIEF AND REGULATING VALVES .1 Where indicated or performance specified on the drawings, provide pressure relief and regulating valves as follow - also refer to Section 15050. .2 All pressure relief valves must have operating handles/levers as per Code requirements. .3 Acceptable Manufacturers: Watts, Singer, Honeywell, Braukmann, Wilkins, Conbraco. .4 For natural gas, provide CGA approved pressure regulating valves as manufactured by Fisher or February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 15 Canadian Meter. 2.21 PUMPS .1 Domestic water recirculation, pressure booster and sump pumps: Refer to pump schedule and Section 15700. 2.22 ROOF DRAINS .1 Provide cast iron large body drains with deck clamp, waterproofing flange, self-locking metal dome, and flow control device where flow control is allowed. .2 Standard of Acceptance: Ancon RD-100, Zurn Z-121. 2.23 SKATING RINK HYDRANT .1 National Fire Equipment Ltd., 38mm (1½”) ISR No. 153 complete with hydrant plate, plain adapter, cap and chain. Refer to drawings for location and piping arrangement. 2.24 SUMP PITS .1 Sump pits covers shall be constructed as follows; .1 Cover: 9.5mm (3/8”) Type 304 stainless steel checker plate. .2 Frame: 38mm x 38mm x 8mm (1½” x 1½” x 5/16”) Type 304 stainless steel. .3 Cover to be bolted to frame with ¾” long #10 flush head stainless steel bolts. Tap threads in frame angle. .4 Cover to be provided with a flush mounted stainless steel lifting handles. .5 Covers that exceed 1 meter (40”) in any direction shall require structural bracing. 2.25 TRAP SEAL PRIMERS .1 P.P.P. INC. Model PO-500 Automatic Trap Seal Primer Valve, serving individual or remote area drains with 12mm (½") NPT (M to F) connections with strainer and integral back flow preventer and vacuum breaker. Complete with YS-8 Supply Tube. .2 Where possible, tap into the flush tube of a local water closet flush valve for trap seal priming. Provide soft copper tubing and where exposed, use chrome plated copper tubing. .3 Electronic trap priming manifold: P.P.P. INC model [PT-4, PT-8, PT-12, PT-16, PT-20 or PT] -173624, Electronic Trap Priming Manifold, where four or more traps requiring priming are within 100 feet proximity to each other, the unit shall supply a minimum of 10 oz. (0.10L) of water per opening, once in each 24 hour period based on a system pressure of 60 PSI (42KPA). Factory assembled with a bronze body ball valve, water hammer arrestor, solenoid valve, atmospheric vacuum breaker and A type L copper manifold. Electronic single point power connection 120V 1 AMP Draw, manual override switch, and a 24 hour timer. 2.26 WATER FILTERS .1 Provide water filter on incoming cold water piping to each drinking fountain. .2 Unit to be wall-mounted and be complete with upstream isolation valve. .3 Filter to be Aqua-Pure Model AP200 dirt/rust/sediment & taste/odour water filter with dual action filtering process. First stage to be cellulose fibre prefilter; final stage to be activated carbon. Filtration rating to be 5 microns. .4 Pipe size to be 3/8” with 2 gpm cold water capacity. Housing to be pressure tested, high-impact plastic and be complete with wall mounting bracket. The filter & cartridge are to be rated for a maximum of 100°F. .5 Filter to be provided with one installed AP217, 5 micron dirt/rust, chlorine, taste & odour reduction filter cartridge. .6 Provide two spare cartridges. 2.27 WATER HAMMER ARRESTORS .1 Provide Zurn Z-1700 pre-manufactured shock absorbers in all areas as specified below and as required to manage water hammer in systems. .2 Size according to manufacturer's recommendations to eliminate water hammer and shock from piping systems. .3 Provide water hammer arrestors on hot and cold water supplies to all quick valves, solenoids, and February 27, 2015 University of Manitoba PLUMBING Req # Page 16 .4 .5 2.28 Section 15400 plumbing fixtures, and locate in an upright position between the last two fixtures on a line, or horizontally at the end of line closest to supply source. Shock absorbers shall also be installed at the following locations or where indicated on the drawings: - Top of each riser in buildings over one story. - End of horizontal runs except where such runs end with a riser over one story. - Fixture groupings not serviced by the above. - Water hammer arrestors shall be installed on cold water piping to rooms where flush valves are used. - Any quick-acting automatic valves supplying equipment shall also have water hammer arrestors installed. On projects exceeding five stories in height provide water hammer arrestors on domestic water risers. Locate arrestors at the end of riser opposite supply source. Arrestor shall be two pipe sizes larger than the riser is at the connection point, not exceeding the largest pipe size diameter in the riser. WATER SOFTENER .1 Provide a commercial quality domestic water softener with mineral tank, brine tank, automatic regeneration control with timer to ensure operation at an off-hour. .2 Mineral tank to be rated for 960 kPa (100 psi) and constructed of tank steel with plastic liners or fibre glass. .3 Provide initial salt charge for testing and leave system regenerated and fully charged at the time of takeover by the Owner. .4 Pipe in series with domestic hot water system supply piping and provide isolation and by-pass valves. .5 Automatic brine control with dial adjustment. .6 Capacity: .1 Flow: Continuous operation at 75 l/min. (gpm) at 60 kPa [psi]. .2 Softening: 7.8 kg (grams) per 27 kg (lb) salt maximum. .3 General Electric Model Autotrol 255 PART 3 – EXECUTION 3.01 CLEAN-UP .1 Leave systems operating with all areas of work clean to acceptance of Consultant. 3.02 DOMESTIC WATER METER .1 Co-ordinate and bear all costs in providing a Building water meter and make installation in accordance with municipal requirements and University standards. .2 Provide pulse initiator relays on the water meter compatible with the Building Automation system requirements to record consumption. Co-ordinate with Section 15900. .3 Provide water meters for other systems where shown and sized on the drawings, e.g., for cooling tower and heating/cooling systems make-up. Provide pulse initiator relays on these meters that are compatible with the EMCS - co-ordinate with Section 15900. 3.03 EQUIPMENT INSTALLATION .1 Install all material according to Manufacturer's instructions. .2 Ensure all components are accessible. .3 Provide copper (plastic if outdoors) condensate drains with unions and traps from all equipment with cooling coils. Consult equipment Manufacturer for information on operating negative static pressure in the drain pan area or air handling unit and size accordingly. .4 Install catch basins and manholes in accordance with municipal standards and the detail drawings. .5 Fuel Oil System: Install storage tank and all piping in accordance with Provincial codes relating to the handling of flammable liquids. Install and connect the day tank near the stand-by generator such that piping from the pumping circuit and between the generator connection and the tank do not interfere with access to the stand-by generator. Do not run oil piping across the floor, but along walls February 27, 2015 University of Manitoba Req # PLUMBING Section 15400 Page 17 wherever possible. Connect the oil piping to the engine connections as directed by Division 16. 3.04 EXISTING SERVICE CONNECTIONS .1 Connect new water and waste to existing lines. Modify as required to facilitate interconnection. 3.05 FIXTURE INSTALLATION .1 Install all fixtures, drains, cleanouts, brass, and specialities to Manufacturer's requirements. .2 Connect fixtures complete with supplies and drains, separately trapped, supported level and square. .3 Provide chrome plated piping for all exposed water supply, waste and vent connections complete with CP escutcheons. .4 Provide supports to set fixtures square and level. .5 Obtain Consultant's acceptance of mounting heights of all wall-mounted fixtures. .6 Fixtures mounted on glazed tile surfaces: Provide ground faces to finished surfaces. .7 Install water hammer arrestors for each fixture or group of fixtures. .8 Cleanout fittings and associated chrome cover plates at sinks to be installed above flood level rim of fixture being served. 3.06 NATURAL GAS SERVICE .1 Provide pulse initiator relays with zener barriers as supplied by Alpha Controls (416-477-2133) on the gas meter compatible with the Building Automation system requirements to record consumption. .2 Barriers to be Hoffman Model S604NF-5 NEMA 4 rated CSA/UL listed enclosure complete with right side mount compression glands (IE-0.25") containing R. Stahl IS positive barriers, Model 8901/31158/150/00. .3 Co-ordinate with Section 15900 3.07 PIPE INSTALLATION .1 General: Install straight, parallel and close to walls and ceilings, with specified pitch. Use standard fittings for direction changes. .2 Install groups of piping parallel to each other on trapeze hangers. Space piping to permit application of insulation, identification, and service access. .3 Install eccentric reducers in horizontal piping to permit drainage and eliminate air pockets. .4 Where pipe sizes differ from connection sizes of equipment, install reducing fittings close to equipment. Reducing bushings are not permitted. .5 Install brass and copper pipe and tubing free from surface damage. Replace damaged pipe or tubing where damaged. .6 Ream ends of pipes and tubes before installation. .7 Lay copper tubing so that it is not in contact with dissimilar metal and will not be kinked or collapsed. .8 Provide non-toxic lubricant or Teflon tape applied to male thread on all threaded connections. .9 Clean ends of pipes or tubing and recesses of fittings to be brazed or soldered. Assemble joints without binding. .10 Install flanges or unions to permit removal of equipment without disturbing pipe systems. This includes all piping connections to all equipment including condensate drain lines. .11 Sanitary and storm drainage: Run piping to main sewers with uniform grade. .12 Provide washroom groups and branch take-offs from mains with isolating gate valves. Install stop valve in each fixture supply. .13 Provide hose end ball valves for complete system drainage. .14 Indirectly connect all drains and overflow lines from cooling towers to the sanitary sewer only. 3.08 PLANTER DRAINS .1 Provide 12mm (1/2") gravel or crushed stone around dome of drain in accordance with manufacturer's instructions. 3.09 POTABLE WATER DISINFECTION .1 Potable water supply systems: .1 Thoroughly flush and disinfect (chlorinate) water supply systems in accordance with February 27, 2015 University of Manitoba PLUMBING Req # Section 15400 Page 18 .2 .3 .4 .5 municipal requirements. Flush domestic water piping with a sufficient flow to produce a velocity of 1 metre per second for ten minutes, or until all foreign materials have been removed and the flushed water is clear. Provide connections and pumps as required. Open and close valves, hydrants, and service connections to ensure thorough flushing. When flushing has been completed, introduce a strong chlorine solution into the piping and ensure that it is distributed throughout the entire domestic water system. Disinfect the piping in accordance with AWWA C601-68. The rate of chlorine application to be proportional to the rate of water entering the pipe. The point of chlorine application to be close as possible to the point of filling the piping and to occur simultaneously. Operate valves, hydrants and similar appurtenances while chlorine solution is in the piping. Flush piping of chlorine solution after 24 hours. Arrange and pay for water quality tests to be performed by an independent testing laboratory acceptable to the Consultant as follows: .1 Test for chlorine residuals at extreme ends of all piping systems. After a chlorine residual of not less than 50 ppm has been achieved in all parts of the system, let the system stand for 24 hours. After this period, take further samples to ensure that there is still not less than 10 ppm of chlorine residual throughout the system. .2 When chlorine residuals of 10 ppm have been maintained for a minimum of 24 hours, flush the system and refill to put the system into service. 3.10 SPECIALITIES INSTALLATION .1 Floor drains: Provide with trap primers connected to nearest cold water flush valve, or to automatic primer or flush tank. Prime all floor drain traps. .2 Provide, for all floor drains located within air handling unit plenums, deep P-Traps with 100mm (4") water seal minimum. .3 Non-freeze wall hydrant: Install 360 mm (14") above finished grade (unless otherwise noted) and with inside shut-off valve. 3.11 TESTING .1 Test piping in accordance with procedures outlined in Section 15050. .2 Ensure that insulated piping and equipment installed in concealed places is tested and inspected prior to permanent concealment. END OF SECTION 15400 February 27, 2015