2011 Addison 100% Outside Air and Dehumidification Management This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air - What is it ? • Referred to as “Make-up Air” – Unit operates continually during occupied mode – Replaces exhausted air – No mixture with return air – Totally changing load • Summer design (High temperature and high humidity) • Winter design (Cold temperature) This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Why 100% Outside Air? • Ventilation standards indicating recommended air changes for a variety of space usages and occupancy have been established by ASHRAE. The ventilation requirements for a given structure or space are based either on desired number of air changes or the number of occupants. • The amount of outside air fresh air required for each change per hour equals the amount of inside air that must be removed from the space during the same time span. • CFM= Area of space / Minutes of air changes This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Ventilation Requirements (continued) • • • • • • College classroom 8 air changes Hospitals 9-17 air changes Kitchens 10-20 air changes Schools 8-12 air changes Theaters 5-10 air changes Factory Buildings 10-15 air changes 20-30 cfm/person 40-50 cfm/person 40-50 cfm/person 30-35 cfm/person 10-15 cfm/person 25-30 cfm/person This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Applications of Make-Up Air •Return Air Ducts –Typically will not affect space conditions – May not require Reheat – Control is not as critical •Direct to Space –Usually applied to large areas •(Auditoriums, Kitchens, Corridors) – More precise control is necessary – Reheat is required for control This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air “Supply Air Properties” • Unit discharge air properties – Main purpose – positively impact building humidity • Lowest dew point possible – Ideally close to room (neutral) conditions • Typically between 68 -72 degrees • Not to overcool or overheat space – Below 70% RH per ASHRAE standards This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Dew Point Comparison Reheating to Neutral Air DRY BULB TEMPERATURE - °F 70°F DEW POINT 72°F 75°F RELATIVE HUMIDITY – RH % 45°F 40.6 37.9 34.3 50°F 49 45.8 41.4 55°F 58.9 55.1 49.8 60°F 70.6 65.9 59.6 65°F 84.2 78.6 71.1 This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Air Control • Leaving Air Control – Hot Gas Reheat • Cycling Control • Modulating Control • Room Control – Hot Gas Reheat • Cycling in conjunction with a reheat thermostat • Modulating in conjunction with a reheat sensor This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100 % Outside Air - Room Reheat Control T T Reheat Control - room thermostat in series with discharge thermostat (neutral or cold air) This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Compressors Usage • Single Compressor -- Single Circuit – Used when low dew point in required – Dehumidifies all the air all of the time • Dual Circuits – Single Compress each circuit – Used when leaving air conditions are not critical – Air will bypass lag circuit and then mix with lead circuit • Dual Circuits – Two compressors (Tandem) each circuit) – Lag compressor cycles based on suction pressure. – Four (4) stage operation – Large Tonnage This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison “Refrigeration” Control • Hot Gas Bypass – Modulates to match the evaporator load – Evaporator freeze protection – Suction pressure activated • Hot Gas Reheat – Raises leaving air temperature to room neutral conditions – Cycling with discharge air thermostat – Modulating with sensor. • Liquid Subcool Coil – Raises leaving air temperature – Subcools liquid – Two (2) degrees of subcool equals one (1) percent increase in evaporator capacity This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Standard Cycling Hot Gas Reheat This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Hot Gas Reheat Plus Sub-Cooling This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Hot Gas Reheat Using Digital Scroll This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Example • • Summer design – 1800 cfm – 92/75 ambient – Leaving air • 55 deg Dew Point • 65 deg leaving air temperature Winter design – 0 degree ambient – Leaving air (minimum 70 deg) This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Summer Design w/Reheat Supply Temp. 55.0/55.0 Ambient 92/75 Leaving Air 79.7/64.1 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Summer Design w/Reheat Plus Liq. Sub-cool 66.1/59.4 Supply Temp. 52.2 D.P. Ambient 92/75 Leaving Air 90.5/67.7 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Summer Part Load w/Reheat Supply Temp. 53.9 D.P. Ambient 75/75 Leaving Air 86.1/64.3 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Part Load w/Reheat Plus Liq. Sub-cool 65.7/58.8 Supply Temp. 50.8 D.P. Ambient 75/75 Leaving Air 94.0/67.1 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Summer Part Load w/Reheat Supply Temp. 48.8/48.8 Ambient 70/70 Leaving Air 79.5/61.2 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Part Load w/Reheat Plus Liq. Sub-cool 59.9/54.3 Supply Temp. 48.1 D.P. Ambient 70/70 Leaving Air 83.1/64.3 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Summer Part Load w/Reheat Supply Temp. 46.8/46.8 Ambient 65/65 Leaving Air 73.7/63.8 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Part Load w/Reheat Plus Liq. Sub-cool 55.8/51.5 Supply Temp. 47.0 D.P. Ambien t 65/65 Leaving Air 79.4/61.0 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Summer Part Load w/Reheat Supply Temp. 51.4/51.4 Ambient 60/60 Leaving Air 64.3/56.2 10 ton 1800cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Part Load w/Reheat Plus Liq. Sub-cool 55.2/52.1 Supply Temp. 50.4 D.P. Ambient 60/60 Leaving Air 72.6/57.4 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison 100% Outside Air Winter Design Conditions 175,000 BTUH Furnace Ambient 0 Leaving Air 72 10 ton 1800 cfm This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Recap • Do No Harm – Dehumidify to 55 0 Dew Point or less. – Reheat to Room Neutral. – Temper to Room Neutral – Possible humidify when ambient temperatures are below 35 0 This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Energy Conservation Wheel Applications • Require exhaust air from the building • Require defrost in most areas • Total Unit EER can exceed 25 on some water source heat pump applications This document is intended to assist licensed professionals in the exercise of their professional judgment. 2011 Addison Dedicated Outdoor Air Load Reduction Example: ASHRAE Design Conditions for Atlanta, GA Cooling Mode 100% OA w/ Energy Conservation Wheel Cooling Dehum. Cooling Dehum. Evaporator Discharge Air (enthalpy) (db / wb) (enthalpy) 93.9 / 74.8 38.22 ----52.0 / 52.0 21.43 82.0 / 76.4 39.91 ----52.0 / 52.0 21.43 Total Capacity MBH 327.62 360.63 Sensible Capacity MBH 199.26 142.67 Latent Capacity MBH 128.36 217.96 93.9 / 74.8 38.22 80.7 / 67.0 31.50 52.0 / 52.0 21.43 196.58 -40.0% 136.49 -31.5% 60.09 -53.2% 82.0 / 76.4 39.91 77.1 / 67.6 32.02 52.0 / 52.0 21.43 206.61 -42.7% 119.37 -16.3% 87.24 -60.0% Outdoor Air ECW Supply Air Loads based on: • 4250 cfm supply and exhaust airflow • 48” Energy Conservation Wheel • 75F/ 50%RH summer exhaust air • 70F / 30%RH winter exhaust 100% OA (db / wb) (enthalpy) (db / wb) Heating Mode Outdoor Air ECW Supply Air Unit Supply Air (db) (db) (db) 0 --70 Heating Capacity MBH 321.30 •Source: www.novelaire.com (graphic) This document is intended to assist licensed professionals in the exercise of their professional judgment. 0 48.8 70 97.31 -69.7% 2011 Addison for your attention This document is intended to assist licensed professionals in the exercise of their professional judgment.