Introduction System Schematic ADDRESSABLE SPUR CIRCUIT LOOP 1 ADRRESSABLE LOOP CONVENTIONAL SOUNDERS ~ ~ CONVENTIONAL SOUNDERS LOOPS 2-4 ~ CF3000 MODBUS OUTPUT TO BMS SYSTEM ~ CW9000 CTPR3000 ~ EC200 NC NC SITE MONITOR SYSTEM SITE GRAPHICS SYSTEM EC700 EXT 24V CFSFL01 LON-FO BACNET OUTPUT TO BMS SYSTEM EC650 EXT 24V ECO232 ECO232 NC FIBRE OPTIC UP TO MAX 126 NETWORK NODES LOCAL AREA NETWORK ~ NC NC EC400 CF1100/1200 ~ EC400 EXT 24V EC540 CF3000 Introduction Network Schematic • Max 126 nodes – Control Panels, Network Repeaters, Network Modules • Topology – – Fire rated RS485 screened twisted pair, ie, Draka 910234 1000m cable max of copper network between boosters • Data Available – Panel Number, Loop Number, Device No. / Desc / type, Zone No. / desc MODBUS OUTPUT TO BMS SYSTEM ~ CF3000 ~ CW9000 CTPR3000 ~ EC200 NC NC SITE MONITOR SYSTEM SITE GRAPHICS SYSTEM EC700 EXT 24V CFSFL01 LON-FO BACNET OUTPUT TO BMS SYSTEM EC650 EXT 24V ECO232 ECO232 NC FIBRE OPTIC UP TO MAX 126 NETWORK NODES LOCAL AREA NETWORK ~ NC NC EC400 CF1100/1200 ~ EC400 EXT 24V EC540 CF3000 Introduction Advanced Network Modules Range • NCDR – Dual Redundancy Network Card (V2) • CFSFL01/02 – LON (network) to Fibre Optic interface, max 15K FO length • EC400 – LON (network) to TCP/IP interface • EC540 – LON (network) booster, splits network and resends data to increase range • ECO232 – LON (network) to RS232: Site Graphics & Site Monitor • EC200 – LON (network) to BMS Gateway • EC650 – LON (network) to BACnet interface • EC700 – BMS Gateway to ModBus interface Standard Hardware Standard Network Card Connections • Cable – – Enhanced fire rated data cable, Max 1000m length Draka 910234 2 core twisted pair with screen • Screening – Connect screen to ground at one end only • Termination – Resistor termination 102 (2 x 51 ) per card • Radial Network – – Remove resistors at all network cards except the two ends 102 at each end = 51 across network • Ring Network – – Remove resistors at all network cards except one Link out 1 resistor leaving 51 across network NETWORK CONNECTIONS A-X, B-Y Y X B IN A OUT • EC540 Booster: – treat the network either side as separate networks TERMINATION RESISTORS RIBBON CABLE TO CONTROL PANEL Standard Hardware Standard Network Termination • Radial Network – – Remove resistors at all network cards except the two ends 102 at each end = 51 across network PANEL 1 OF 4 PANEL 2 OF 4 102 PANEL 3 OF 4 NONE PANEL 4 OF 4 NONE 102 Standard Hardware Standard Network Termination • Radial Network with Booster – – Remove resistors at all network cards except the two ends 102 at each end = 51 across network PANEL 1 OF 4 PANEL 2 OF 4 PANEL 3 OF 4 EC540 BOOSTER 24V SUPPLY 102 NONE 102 102 TO NEXT PANEL ETC Standard Hardware Standard Network Termination • Ring Network – – Remove resistors at all network cards except one Link out 1 resistor leaving 51 across network PANEL 1 OF 4 PANEL 2 OF 4 51 PANEL 3 OF 4 NONE PANEL 4 OF 4 NONE NONE Standard Hardware Standard Network Termination • Resistor Termination on network card – – 102 (2 x 51 resistor) To give 51 reading across network pair at any point • Radial Network – – Remove resistors at all network cards except the two ends 102 at each end = 51 across network • Ring Network – – A B 51 51 LEAVE ALL RESISTORS INTACT A B Remove resistors at all network cards except one Link out 1 resistor leaving 51 across network All (102) 51 One (51) None (no resistor) A B A O/C CUT HERE TO REMOVE FROM CIRCUIT 51 B 51 S/C SOLDER LINK ACROSS ONE RESISTOR Terminal Mounted 102 SOME DEVICES MAY NOT HAVE INBUILT RESISTORS Advanced Hardware NCDR: Network Card Dual Redundancy • Dual Network Channels • Cable – – Enhanced fire rated data cable, Max 1000m length Draka 910234 2 core twisted pair with screen • Screening – SCREEN CONNECTIONS Connect screen to ground at one end only • Termination – As per standard network card, but for each channel NETWORK 2 CONNECTIONS IN-OUT NETWORK 1 CONNECTIONS IN-OUT OUT IN Y X B OUT A IN TERMINATION RESISTORS RIBBON CABLE TO CONTROL PANEL Advanced Hardware NCDR: Network Card Dual Redundancy • Dual Network Channels – – – Network 1 and Network 2 Automatic Switching in event of fault Network Protocol V2 option must be selected PANEL 1 OF 4 51 PANEL 2 OF 4 51 PANEL 3 OF 4 NONE NETWORK CHANNEL 1 NETWORK CHANNEL 2 PANEL 4 OF 4 NONE NONE Advanced Hardware CFSFL01/02: Lon (Network) to Fibre Optic Interface • Single or Dual Channel – Requires 2 for a dual network • Fibre – – – – Single Mode x 2 (Tx & Rx) 9/125 micron 15Km max SC Type connectors 24V DC 0V FIBRE CONNECTIONS SCREEN NETWORK A NETWORK B Advanced Hardware CFSFL01: Lon (Network) to Fibre Optic Interface • Single Channel network • Radial, ring or part network PANEL 1 OF 4 24V DC PANEL 2 OF 4 102 PANEL 3 OF 4 NONE 2 x SINGLE MODE FIBRE PANEL 4 OF 4 NONE 102 24V DC Advanced Hardware CFSFL01: Lon (Network) to Fibre Optic Interface • Single Channel network • Radial, ring or part network PANEL 1 OF 4 24V DC PANEL 2 OF 4 102 NONE PANEL 3 OF 4 24V DC 1021 2 x SINGLE MODE FIBRE PANEL 4 OF 4 24V DC 102 24V DC Advanced Hardware CFSFL02: Lon (Network) to Fibre Optic Interface • Dual Channel network • Radial, ring or part network PANEL 1 OF 4 24V DC PANEL 2 OF 4 102 24V DC PANEL 3 OF 4 102 24V DC 2 x SINGLE MODE FIBRE PANEL 4 OF 4 102 24V DC 102 Advanced Hardware CFSFL01/2: Lon (Network) to Fibre Optic Interface • Many possible combinations PANEL 3 OF 7 102 PANEL 1 OF 7 PANEL 5 OF 7 102 PANEL 2 OF 7 PANEL 4 OF 7 PANEL 6 OF 6 PANEL 7 OF 7 24V DC 24V DC 24V DC 24V DC 24V DC 102 102 102 102 102 CFSFL01 or CFSFL02 CFSFL02 CFSFL02 CFSFL02 CFSFL01 or CFSFL02 2 x SINGLE MODE FIBRE Advanced Hardware EC400: Lon (Network) to TCP/IP Interface • Network via PC network / internet / etc – Requires 2 for a dual network • Use Hyper Terminal for configuration – IP address • Inbuilt Web Server for IP configuration – – IP address Passwords PROGRAMMING NETWORK CONNECTION ETHERNET CONNECTION 24V DC Advanced Hardware EC400: Lon (Network) to TCP/IP Interface • Requires fixed IP address • Useful for facilities management PANEL 3 OF 3 24V DC PANEL 1 OF 3 PANEL 2 OF 3 24V DC NETWORK NETWORK Advanced Hardware EC540: Lon (Network) Booster • Extend radial network length – Effectively splits a network into multiple networks – Requires 2 for a dual network • Max 5 per network – Any more may cause transmission delays 24V DC NETWORK CONNECTION Advanced Hardware EC540: Lon (Network) Booster • Radial Network – Terminate network either side of booster PANEL 1 OF 3 PANEL 2 OF 3 PANEL 3 OF 3 24V DC 102 NONE 1000M MAX 102 102 102 1000M MAX Advanced Hardware EC0232: Lon (Network) to RS232 Interface • PC connection • No network address required • Versions – – – EC0232: Site Monitor, Site Graphics, EC0232PAVA: EVAX HMX PAVA EC0232PAVA3D: EVAX HMX PAVA 3 minute time delay Advanced Hardware EC0232: Lon (Network) to RS232 Interface • Typical Example PANEL 1 OF 2 SITE GRAHICS OR SITE MONITOR PANEL 2 OF 2 EC0232 102 102 1000M MAX Advanced Hardware EC200: Lon (Network) to BMS Gateway • Translation for BMS connection • Requires EC700 Advanced Hardware EC700: BMS Gateway to MODbus interface • Translation for BMS connection • Requires EC700 • Verify requirement spec as protocol implementation may vary Advanced Hardware MODbus Interface • Typical Example PANEL 1 OF 2 PANEL 2 OF 2 EC200 EC700 MODBUS SYSTEM 102 102 1000M MAX Advanced Hardware EC650 to BACnet interface • Translation for BMS connection • Direct network connection • Verify requirement spec as protocol implementation may vary Advanced Hardware BACnet Interface • Typical Example PANEL 1 OF 2 PANEL 2 OF 2 EC650 BACNET SYSTEM 102 102 1000M MAX Network Standard Network Setup • At each control panel – – – Number of panels on network Panel Address E.g., Panel 1 of 4 • Network Response (to commands received) – – – – – – Silence Reset Evacuate Fire Fault Pre Alarm • Network Filter – Select which Panels to respond to Operation Fault Finding a Network • Lon Network Error – – – Check ‘panel address and totals’ settings Check network termination Check network cable insulation and continuity readings • Misc – – Hard reset panel, then clear watchdog fault with soft reset Generate fire or fault and check transmission and reset