Lon (Network)

advertisement
Introduction
System Schematic
ADDRESSABLE SPUR CIRCUIT
LOOP 1
ADRRESSABLE
LOOP
CONVENTIONAL SOUNDERS
~
~
CONVENTIONAL
SOUNDERS
LOOPS 2-4
~
CF3000
MODBUS OUTPUT
TO BMS SYSTEM
~
CW9000
CTPR3000
~
EC200
NC
NC
SITE MONITOR
SYSTEM
SITE GRAPHICS
SYSTEM
EC700
EXT
24V
CFSFL01
LON-FO
BACNET OUTPUT
TO BMS SYSTEM
EC650
EXT
24V
ECO232
ECO232
NC
FIBRE OPTIC
UP TO MAX 126 NETWORK NODES
LOCAL AREA NETWORK
~
NC
NC
EC400
CF1100/1200
~
EC400
EXT
24V
EC540
CF3000
Introduction
Network Schematic
• Max 126 nodes
–
Control Panels, Network Repeaters, Network Modules
• Topology
–
–
Fire rated RS485 screened twisted pair, ie, Draka 910234
1000m cable max of copper network between boosters
• Data Available
–
Panel Number, Loop Number, Device No. / Desc / type, Zone No. / desc
MODBUS OUTPUT
TO BMS SYSTEM
~
CF3000
~
CW9000
CTPR3000
~
EC200
NC
NC
SITE MONITOR
SYSTEM
SITE GRAPHICS
SYSTEM
EC700
EXT
24V
CFSFL01
LON-FO
BACNET OUTPUT
TO BMS SYSTEM
EC650
EXT
24V
ECO232
ECO232
NC
FIBRE OPTIC
UP TO MAX 126 NETWORK NODES
LOCAL AREA NETWORK
~
NC
NC
EC400
CF1100/1200
~
EC400
EXT
24V
EC540
CF3000
Introduction
Advanced Network Modules Range
• NCDR
–
Dual Redundancy Network Card (V2)
• CFSFL01/02
–
LON (network) to Fibre Optic interface, max 15K FO length
• EC400
–
LON (network) to TCP/IP interface
• EC540
–
LON (network) booster, splits network and resends data to increase range
• ECO232
–
LON (network) to RS232: Site Graphics & Site Monitor
• EC200
–
LON (network) to BMS Gateway
• EC650
–
LON (network) to BACnet interface
• EC700
–
BMS Gateway to ModBus interface
Standard Hardware
Standard Network Card Connections
• Cable
–
–
Enhanced fire rated data cable, Max 1000m length
Draka 910234 2 core twisted pair with screen
• Screening
–
Connect screen to ground at one end only
• Termination
–
Resistor termination 102  (2 x 51 ) per card
• Radial Network
–
–
Remove resistors at all network cards except the two ends
102  at each end = 51  across network
• Ring Network
–
–
Remove resistors at all network cards except one
Link out 1 resistor leaving 51 across network
NETWORK
CONNECTIONS
A-X, B-Y
Y
X
B
IN
A
OUT
• EC540 Booster:
–
treat the network either side as separate networks
TERMINATION
RESISTORS
RIBBON CABLE TO
CONTROL PANEL
Standard Hardware
Standard Network Termination
• Radial Network
–
–
Remove resistors at all network cards except the two ends
102  at each end = 51  across network
PANEL 1 OF 4
PANEL 2 OF 4
102 
PANEL 3 OF 4
NONE
PANEL 4 OF 4
NONE
102 
Standard Hardware
Standard Network Termination
• Radial Network with Booster
–
–
Remove resistors at all network cards except the two ends
102  at each end = 51  across network
PANEL 1 OF 4
PANEL 2 OF 4
PANEL 3 OF 4
EC540
BOOSTER
24V SUPPLY
102 
NONE
102 
102 
TO NEXT
PANEL ETC
Standard Hardware
Standard Network Termination
• Ring Network
–
–
Remove resistors at all network cards except one
Link out 1 resistor leaving 51 across network
PANEL 1 OF 4
PANEL 2 OF 4
51
PANEL 3 OF 4
NONE
PANEL 4 OF 4
NONE
NONE
Standard Hardware
Standard Network Termination
• Resistor Termination on network card
–
–
102  (2 x 51  resistor)
To give 51 reading across network pair at any point
• Radial Network
–
–
Remove resistors at all network cards except the two ends
102  at each end = 51  across network
• Ring Network
–
–
A
B
51 
51 
LEAVE ALL
RESISTORS INTACT
A
B
Remove resistors at all network cards except one
Link out 1 resistor leaving 51 across network
All (102)
51 
One (51)
None (no resistor)
A
B
A
O/C
CUT HERE TO REMOVE
FROM CIRCUIT
51 
B
51 
S/C
SOLDER LINK ACROSS
ONE RESISTOR
Terminal Mounted
102 
SOME DEVICES MAY NOT
HAVE INBUILT RESISTORS
Advanced Hardware
NCDR: Network Card Dual Redundancy
• Dual Network Channels
• Cable
–
–
Enhanced fire rated data cable, Max 1000m length
Draka 910234 2 core twisted pair with screen
• Screening
–
SCREEN
CONNECTIONS
Connect screen to ground at one end only
• Termination
–
As per standard network card, but for each channel
NETWORK 2
CONNECTIONS
IN-OUT
NETWORK 1
CONNECTIONS
IN-OUT
OUT
IN
Y
X
B
OUT A
IN
TERMINATION
RESISTORS
RIBBON CABLE TO
CONTROL PANEL
Advanced Hardware
NCDR: Network Card Dual Redundancy
• Dual Network Channels
–
–
–
Network 1 and Network 2
Automatic Switching in event of fault
Network Protocol V2 option must be selected
PANEL 1 OF 4
51
PANEL 2 OF 4
51
PANEL 3 OF 4
NONE
NETWORK CHANNEL 1
NETWORK CHANNEL 2
PANEL 4 OF 4
NONE
NONE
Advanced Hardware
CFSFL01/02: Lon (Network) to Fibre Optic Interface
• Single or Dual Channel
–
Requires 2 for a dual network
• Fibre
–
–
–
–
Single Mode x 2 (Tx & Rx)
9/125 micron
15Km max
SC Type connectors
24V DC
0V
FIBRE
CONNECTIONS
SCREEN
NETWORK A
NETWORK B
Advanced Hardware
CFSFL01: Lon (Network) to Fibre Optic Interface
• Single Channel network
• Radial, ring or part network
PANEL 1 OF 4
24V DC
PANEL 2 OF 4
102
PANEL 3 OF 4
NONE
2 x SINGLE MODE FIBRE
PANEL 4 OF 4
NONE
102
24V DC
Advanced Hardware
CFSFL01: Lon (Network) to Fibre Optic Interface
• Single Channel network
• Radial, ring or part network
PANEL 1 OF 4
24V DC
PANEL 2 OF 4
102
NONE
PANEL 3 OF 4
24V DC
1021
2 x SINGLE MODE FIBRE
PANEL 4 OF 4
24V DC
102
24V DC
Advanced Hardware
CFSFL02: Lon (Network) to Fibre Optic Interface
• Dual Channel network
• Radial, ring or part network
PANEL 1 OF 4
24V DC
PANEL 2 OF 4
102
24V DC
PANEL 3 OF 4
102
24V DC
2 x SINGLE MODE FIBRE
PANEL 4 OF 4
102
24V DC
102
Advanced Hardware
CFSFL01/2: Lon (Network) to Fibre Optic Interface
• Many possible combinations
PANEL 3 OF 7
102
PANEL 1 OF 7
PANEL 5 OF 7
102
PANEL 2 OF 7
PANEL 4 OF 7
PANEL 6 OF 6
PANEL 7 OF 7
24V DC
24V DC
24V DC
24V DC
24V DC
102
102
102
102
102
CFSFL01 or
CFSFL02
CFSFL02
CFSFL02
CFSFL02
CFSFL01 or
CFSFL02
2 x SINGLE MODE FIBRE
Advanced Hardware
EC400: Lon (Network) to TCP/IP Interface
• Network via PC network / internet / etc
–
Requires 2 for a dual network
• Use Hyper Terminal for configuration
–
IP address
• Inbuilt Web Server for IP configuration
–
–
IP address
Passwords
PROGRAMMING
NETWORK
CONNECTION
ETHERNET
CONNECTION
24V
DC
Advanced Hardware
EC400: Lon (Network) to TCP/IP Interface
• Requires fixed IP address
• Useful for facilities management
PANEL 3 OF 3
24V DC
PANEL 1 OF 3
PANEL 2 OF 3
24V DC
NETWORK
NETWORK
Advanced Hardware
EC540: Lon (Network) Booster
• Extend radial network length
–
Effectively splits a network into multiple networks
–
Requires 2 for a dual network
• Max 5 per network
–
Any more may cause transmission delays
24V DC
NETWORK
CONNECTION
Advanced Hardware
EC540: Lon (Network) Booster
• Radial Network
–
Terminate network either side of booster
PANEL 1 OF 3
PANEL 2 OF 3
PANEL 3 OF 3
24V DC
102
NONE
1000M MAX
102
102
102
1000M MAX
Advanced Hardware
EC0232: Lon (Network) to RS232 Interface
• PC connection
• No network address required
• Versions
–
–
–
EC0232: Site Monitor, Site Graphics,
EC0232PAVA: EVAX HMX PAVA
EC0232PAVA3D: EVAX HMX PAVA 3 minute time delay
Advanced Hardware
EC0232: Lon (Network) to RS232 Interface
• Typical Example
PANEL 1 OF 2
SITE GRAHICS OR
SITE MONITOR
PANEL 2 OF 2
EC0232
102
102
1000M MAX
Advanced Hardware
EC200: Lon (Network) to BMS Gateway
• Translation for BMS connection
• Requires EC700
Advanced Hardware
EC700: BMS Gateway to MODbus interface
• Translation for BMS connection
• Requires EC700
• Verify requirement spec as protocol implementation may vary
Advanced Hardware
MODbus Interface
• Typical Example
PANEL 1 OF 2
PANEL 2 OF 2
EC200
EC700
MODBUS
SYSTEM
102
102
1000M MAX
Advanced Hardware
EC650 to BACnet interface
• Translation for BMS connection
• Direct network connection
• Verify requirement spec as protocol implementation may vary
Advanced Hardware
BACnet Interface
• Typical Example
PANEL 1 OF 2
PANEL 2 OF 2
EC650
BACNET
SYSTEM
102
102
1000M MAX
Network
Standard Network Setup
• At each control panel
–
–
–
Number of panels on network
Panel Address
E.g., Panel 1 of 4
• Network Response (to commands received)
–
–
–
–
–
–
Silence
Reset
Evacuate
Fire
Fault
Pre Alarm
• Network Filter
–
Select which Panels to respond to
Operation
Fault Finding a Network
• Lon Network Error
–
–
–
Check ‘panel address and totals’ settings
Check network termination
Check network cable insulation and continuity readings
• Misc
–
–
Hard reset panel, then clear watchdog fault with soft reset
Generate fire or fault and check transmission and reset
Download