Room Cooling - APC Partner Central

advertisement
Cooling Product Positioning
Baseline Positioning
Regional Comparisons may vary based on climate
Cooling Product Portfolio
Addressing any Critical Cooling Problems
From the Network
Closet to the Data
Center
Chillers and
Heat Rejection
Air Distribution
Room Cooling
Close Coupled
Cooling
Schneider Electric
2
Choosing one of the Core Products
Room Cooling
Uniflair
Close Coupled Cooling
InRow
Schneider Electric
EcoBreeze
Chillers and Heat Rejection
Uniflair Chillers
3
Solutions to Address Any Density
InRow + Thermal containment
InRow
Ecobreeze + Thermal containment
Room + Raised Floor + Active Floor +
Containment
Room + Active Air
Distribution
Room +
Raised Floor
0
5
10
12
15
20
25
>25
Density kW / Rack
Schneider Electric
4
Cooling Product Positioning
 Financial
o First Cost
o Operating Cost
o 3 Year TCO (Operating + First Cost)
 Facility Constraints (Existing Data Centers)
o Out of Capacity
o Stranded Capacity
o Out of Space
 Qualitative Criteria
o Predictability
o Flexibility
o Scalability
Schneider Electric
5
Financial Comparison
 Data Center Sizes – 60, 120, 480, 1200 kW
 Rack Density – 3, 6, 12, 20 kW per Rack (120 CFM/kW)
 Raised Floor Air Distribution for Room Cooling – 100 Euro/ m2 ($8/ft2)
o Raised Floor Pricing range from 30 Euro / m2 to 400 Euro / m2($50/ft2)
o Does not consider fire suppression under floor ($4-$10/ft2)
 Drop Ceiling for Room Cooling Hot Aisle Containment – 36 Euro / m2
($4/ft2)
o Based on RSMeans Cost Works Data Base – Typical Drop Ceiling
o Does not consider fire suppression in drop ceiling range ($4-$10/ft2)
 Active Floor for Room Cooling with CAC and raised floor for high density
(12 and 20 kW per rack)
 Piping costs based on RSMeans Cost Works Data Base – Steel Piping
 Cost of Energy = 0.1 Euro / kWh
 EcoStream Analysis Tool used to determine airflow required for each
scenario
Schneider Electric
6
Key Outputs from financial comparison
 Benefits of using containment systems
 Efficiency and Operating cost differences
 First Cost Impact based on size of facility
 Overall 3 Total cost to make recommendations on where to start
“This is a Guide, NOT a Gospel”
Schneider Electric
7
Benefits of Containment – Row Cooling
Operating Cost
First Cost
 Reduced number of units operating at
elevated utilization (increased fan speed)
 Fixing the number of cooling units
between open and HAC further increases
efficiency
 Increased Capacity and Improved
Capture Index
 Reduced Equipment and Installation
costs
740000
1.55
1.50
5%
Row
Relative Cost
1.45
Row HAC
1.40
1.35
1.30
1.25
7%
1.20
1.15
1.10
Cooling System Annual Energy (kWh)
1.60
720000
700000
7%
680000
660000
1%
Row
Row HAC
640000
620000
600000
3 kW
6 kW
12 kW
20 kW
Includes cost of piping, chiller, containment, and
installation of cooling units
3 kW
6 kW
12 kW
20 kW
Includes Unit fan power, chiller, and pumps
Based on 480 kW data center. Location: St. Louis, MO, USA
Schneider Electric
8
Benefits of Containment – Room Cooling
First Cost
Operating Cost
 Higher first cost of adding
containment to room cooling
 Room Cooling with no raised floor
and Hot Aisle Containment (HAC)
most cost effective solution.
 HAC no raised floor ROI over raised floor
1.35
o 3 kW per Rack = 4.3 years
o 6 kW per Rack = 2.5 years
920000
Room HAC w/ raised floor
1.25
6%
1.15
10%
7%
1.10
1.05
1.00
Cooling System Annual Energy (kWh)
Room CAC w/ Active Floor
6%
Relative Cost
 CAC with raised ROI over raised floor
Room raised floor
1.30
1.20
o 3 kW per Rack = 3 years
o 6 kW per Rack = 1.5 years
Room w/Raised Floor
Room CAC w/Active Floor
Room HAC w/Raised Floor
870000
12%
Effect of Active
Air Distribution
820000
770000
4%
720000
670000
3 kW
6 kW
12 kW
Includes cost of piping, chiller, containment, and
installation of cooling units
20 kW
3 kW
6 kW
12 kW
20 kW
Includes Unit fan power, chiller, and pumps
Based on 480 kW data center. Location: St. Louis, MO, USA
Schneider Electric
9
Containment Recommendations
 Always use containment for optimal TCO
o Payback is immediate with close coupled cooling
o 3 year ROI for Room Based Cooling improves with density
 Hot Aisle Containment preferred approach for new data center builds
o Improved Efficiency of the Cooling System
o Flexibility to keep data center cool.
 Cold Aisle Containment – Retrofit for existing data center
o Flexibility to adapt to existing room cooling systems
o Active floor to assist with cold air distribution from raised floor to ensure
sufficient air flow is available in contained aisle.
o Efficiency Gains Require elevating room temperature
Schneider Electric
10
Efficiency – 6kW/rack
Annual Partial PUE
Small Medium Large
EcoBreeze - Modular
Air Economizer with IEC
InRow with
Free Cooling Chiller
(0-200kW)
(201-1MW)
(Over 1MW)
1.142
1.140
1.145
17%
18%
12%
Annual Cooling Energy Variation (*)
+
1.172
1.171
1.165
12%
Annual Cooling Energy Variation (*)
Uniflair with
Free Cooling Chiller
•
•
•
•
•
+
1.195
1.173
1.172
Location Based on St. Louis, MO USA using annualized average power consumption
100% IT loads for Small =120 kW, Medium = 480 kW, and Large = 1,200 kW
Based on 6 kW per Rack using Hot Aisle Containment
Packaged Air Cooled Free Cooling Chillers with Intelligent Free Cooling
Comparisons will vary based on Geographic Location
Schneider Electric
11
Efficiency – 12kW/rack
Annual Partial PUE
Small Medium Large
EcoBreeze - Modular
Air Economizer with IEC
InRow with
Free Cooling Chiller
(0-200kW)
(201-1MW)
(Over 1MW)
1.142
1.140
1.145
17%
17%
16%
Annual Cooling Energy Variation (*)
+
1.171
1.169
1.172
14%
Annual Cooling Energy Variation (*)
Uniflair with
Free Cooling Chiller





+
1.198
1.173
1.171
Location Based on St. Louis, MO USA using annualized average power consumption
100% IT loads Small =120 kW, Medium = 480 kW, Large = 1,200 kW
Based on 12 kW per Rack using Hot Aisle Containment
Packaged Air Cooled Free Cooling Chillers with Intelligent Free Cooling
Comparisons will vary based on Geographic Location
Schneider Electric
12
First Cost – 6kW/rack
CAPEX Comparison
Small Medium Large
EcoBreeze - Modular
Air Economizer with IEC
InRow with
Free Cooling Chiller
Uniflair with
Free Cooling Chiller





+
+
(0-200kW)
(201-1MW)
(Over 1MW)
1.38
1.24
1.05
1.06
1.16
1.22
1
1
1
Location Based on St. Louis, MO USA using average market cost
based on the following IT loads Small =120 kW, Medium = 480 kW, Large = 1,200 kW
Based on 6 kW per Rack using Hot Aisle Containment
Packaged Air Cooled Free Cooling Chillers with Intelligent Free Cooling
Comparisons will vary based on Geographic Location
Schneider Electric
13
First Cost – 12kW/rack
CAPEX Comparison
Small Medium Large
EcoBreeze - Modular
Air Economizer with IEC
InRow with
Free Cooling Chiller
Uniflair with
Free Cooling Chiller





+
+
(0-200kW)
(201-1MW)
(Over 1MW)
1.41
1.30
1.11
1.05
1.16
1.23
1
1
1
Location Based on St. Louis, MO USA using average market cost
based on the following IT loads Small =120 kW, Medium = 480 kW, Large = 1,200 kW
Based on 12 kW per Rack using Hot Aisle Containment
Packaged Air Cooled Free Cooling Chillers with Intelligent Free Cooling
Comparisons will vary based on Geographic Location
Schneider Electric
14
1 MW
500kW
Room Cooling
EcoBreeze
Room Cooling
Uniflair
Close Coupled
InRow
200kW
Large
Small
Medium
3 Year TCO
0
5
10
12
15
Density kW / Rack
20
25
>25
 Location Based on St. Louis, MO USA. Includes complete cost of cooling system including
chillers, piping, containment, etc..
 Row, Room, and EcoBreeze Products work from low to high density when using
containment
 Some Scenarios are close and climate will impact 3 year cost based on Economizer hours
for EcoBreeze
Schneider Electric
15
• Drive to be Green and reduce CO2
• Highest Efficiency
1 MW+
Large
Typical Applications
• Flexibility of Raised Floor
• Room Level Control
• Co-location
500kW
Medium
EcoBreeze
200kW
Small
Uniflair
InRow
0
5
10
12
15
• Scalability with ISX
• Predictability at the rack and
row level
• High Density Zones in Larger
Data Centers
20
25
>25
Density kW / Rack
 Overlap in the typical applications due to a mix of decision factor
 Predictability, Modularity, Scalability, Flexibility, Green
Schneider Electric
16
Existing Data Center – Where to Start
IT Load to be
Deployed
Low Density
0-6 kW per Rack
High Density
> 6 kW per Rack
Out of Capacity
Stranded Capacity /
Existing room cooling
Add Room Cooling
Cold Aisle Containment
Close Coupled
Cooling Zone for Rack
Expansion or Existing
Racks
(See White Paper 134)
Cold Aisle Containment
+ Active Floor
Air Removal Unit or
Vertical Exhaust
Duct(VDE)
EcoBreeze May be challenging for Existing Facilities and will need careful evaluation
Schneider Electric
17
Product Trade-Offs - Uniflair
 Benefits
o Flexibility to handle racked and non-racked IT equipment
o Easily Deploy in existing raised floor environments
o Integrated redundancy on the electrical sections with double power
supply
o Possibility to optimize the airflow based on the operating conditions
(AFPS)
o Low first cost
o Complete integration with the Uniflair chillers with dynamic optimization
of the operating parameters
o Cooling equipment is located on perimeter of the room or in corridors
outside of the data center
o Build to order units – configurable to specific customer requirements
UniFlair
 Considerations to Implementation
o Typically installed with raised floor
o Supplemental air distribution and fans systems may be required to
address high density
o Requires space and provisions to connect to heat rejection system
(Chiller, condenser, cooling tower, fluid cooler, ect..) located in
mechanical room or outdoors.
Schneider Electric
18
Product Trade-Offs - InRow
 Benefits
o Predictable airflow patterns as a result of close coupling easily enables
higher densities
o Rack inlet temperature control ensures temperatures to servers are
maintained 7x24x365
o Redundancy and capacity sharing between units using Active Response
Controls
InRow
o Integrated redundancy on the electrical sections with double power supply
o Integrated cooling module as part of ISX for modular, scalable, and
manageable data center
o Independent of a raised floor
o Flexibility for floor mount or overhead installation to address facility
constraints
o Standardized units typically available in stock for quick delivery
 Considerations to Implementation
o Cooling equipment adjacent to IT equipment - water or refrigerant in the
row
o Typically requires more cooling units increasing connection points & cost
o Requires space and provisions to connect to heat rejection system
(Chiller, condenser, cooling tower, fluid cooler, ect.) located in mechanical
Schneider room
Electric or outdoors.
19
Product Trade-Offs - Chillers
 Benefits
o Complete package solution with integrated free-cooling system and
onboard hydronic module
o Integrated redundancy on the refrigerant, hydraulic and electrical
sections (integrated ATS, double pump/s…)
o Complete integration with the Uniflair units with dynamic optimization of
the operating parameters
o Self optimization of all the installed chillers
o Build to order units – configurable to specific customer requirements
o Containerized cooling module: completely integrated free-cooling
solution in a fully equipped (hydraulical&electrical) container
Chillers
 Considerations to Implementation
o Requires clearances around the unit for maintenance
o Low temperatures installations operate with glycol mixtures
o Installation and sizing of interconnecting piping, valves, and other
hydronic systems is required.
Schneider Electric
20
Product Trade-Offs - EcoBreeze
 Benefits
o
o
o
o
Highest efficiency – maximizes free cooling hours in most climates
No additional heat rejection systems required
Located outside of the data center freeing up white space
Built in modularity allows scalability of cooling capacity with demand.
 Considerations to Implementation
EcoBreeze
o requires space outdoors next to the building or on a roof in close
proximity to the data center
o Must accommodate space for supply and return duct systems within
the building to and from the data center
Schneider Electric
21
Summary
 Schneider-Electric has a complete offer of cooling solutions to address
any IT environment from the Network Closet to the Data Center
 For optimal 3 Year TCO
o InRow for Smaller IT Loads
o Uniflair room cooling for Medium IT Loads
o EcoBreeze for Large IT Loads
 There are many criteria and trade-offs that need to be considered for
the customer best cooling solution
Schneider Electric
22
Download