Cable Type Power Cable Number of Core 4 core single insulated cable Proposed Brand SAMA Kebel Location to be used Station, Depot building Used in KTMBProject No Used in Other Railway Project No Specification System tech Spec System tech Spec Clause Description Comply Yes Sub Contractor Comment/Remark No 13.13.4 The Contractor shall supply and install all telecommunications wires and cables between the equipment and distribution frames/ shelves, all wiring associated with power supplies, both AC and DC and all wiring associated with earthing. Every cable must be indelibly labelled/ sign written not further than 150mm from each end with a legend that uniquely and easily identifies its function, local and far end connections. Factory terminated and tested cabled should be used wherever possible to limit the possibility if faulty connections. Yes noted 13.13.5 Power supply wiring cables (both AC and DC) shall be of single core insulated copper conductors confirming to BS 6004. AC mains cables must carefully segregated from all others by being insulated in separate (or divided) trunking where conduits are not used. DC power supply cabling shall have the following colour code: Positive (earth) - black Negative - blue AC power shall be taken from a local isolator or fused spur. Yes - comply with IEC 60502-1 - PVC cable with rated voltage 600/1000V - Conductor material : Plain annealed copper wire same with bs 6004 Page 1 of 1