Cable Type Power Cable
Number of Core 4 core single insulated cable
Proposed Brand SAMA Kebel
Location to be used Station, Depot building
Used in KTMBProject No
Used in Other Railway Project No
Specification
System tech Spec
System tech Spec
Clause
Description
Comply
Yes
Sub Contractor
Comment/Remark
No
13.13.4
The Contractor shall supply and install all telecommunications wires and
cables between the equipment and distribution frames/ shelves, all wiring
associated with power supplies, both AC and DC and all wiring associated
with earthing. Every cable must be indelibly labelled/ sign written not further
than 150mm from each end with a legend that uniquely and easily identifies
its function, local and far end connections. Factory terminated and tested
cabled should be used wherever possible to limit the possibility if faulty
connections.
Yes
noted
13.13.5
Power supply wiring cables (both AC and DC) shall be of single core insulated
copper conductors confirming to BS 6004. AC mains cables must carefully
segregated from all others by being insulated in separate (or divided) trunking
where conduits are not used. DC power supply cabling shall have the following
colour code:
Positive (earth) - black
Negative - blue
AC power shall be taken from a local isolator or fused spur.
Yes
- comply with IEC 60502-1
- PVC cable with rated voltage 600/1000V
- Conductor material : Plain annealed copper wire same
with bs 6004