Low Voltage Electricity Wiring Code CS-CSI-P1/C1 Table No. 10 LOW VOLTAGE ELECTRICITY WIRING CODE Three and Four Cores PVC Insulated, Steel Wire Armoured, PVC Sheathed and PVC Insulated, PVC Sheathed ( Unarmoured ) Cables mm² 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 Voltage Drop Per Ampere Per Meter mV 24 15 9.1 6 3.6 2.2 1.5 1 0.81 0.57 0.42 0.34 0.29 0.24 0.2 0.18 0.17 Current Rating For Cable Laid Directly In The Ground Ampere 14 20 26 33 50 65 73 87 104 123 150 170 190 215 250 280 315 Current Rating For Cable Run In Underground Pipe Or Trench Ampere 14 20 25 32 42 54 70 82 100 120 150 164 190 210 250 262 300 Current Rating For Cable Run In Air Within A Building Ampere 15 20 26 33 45 60 80 100 119 150 200 220 300 350 400 450 - Current Rating For Cable Run In Air On Exterior Of A Building Or Part Thereof Ampere 13 17 23 30 40 52 75 85 110 140 170 200 230 250 300 350 400 Note: For groups of cables covered under Tables Nos. 09 And 10 above, the single cable rating shall apply provided that when the cables are run in both horizontal and vertical planes, the minimum clearance between cables shall be 25 mm. Where it is not possible to comply with this then it shall be the responsibility of the Consultant / Contractor to seek advice from the Qatar General Electricity & Water Corporation “KAHRAMAA”. Double banking of cables run in the horizontal plane is not permitted. Table No. 11 Three And Four Cores XLPE Insulated, Steel Wire Armoured, PVC Sheathed Cables mm² 16 25 35 50 70 95 120 150 185 240 300 Voltage Drop Per Ampere Per Meter mV 2.6 1.5 1.2 0.87 0.61 0.45 0.36 0.29 0.24 0.2 0.18 Current Rating For Cable Laid Directly In The Ground Amperes 71 93 112 133 164 195 223 251 285 329 366 Current Rating For Cable Run In Underground Pipe Or Trench Amperes 65 84 100 123 151 182 210 235 266 308 350 Current Rating For Cable Run In Air Within A Building Amperes 81 110 150 170 208 255 300 350 400 476 550 Current Rating For Cable Run In Air On Exterior Of A Building Or Part Thereof Amperes 80 102 136 150 200 250 276 323 367 450 500 Note: For groups of cables covered under Table Nos. 11 the single cable rating shall apply provided that when the cables are run in both horizontal and vertical planes, the minimum clearance between cables shall be 25 mm. Where it is not possible to comply with this then it shall be the responsibility of the Consultant / Contractor to seek advice from the Qatar General Electricity & Water Corporation “KAHRAMAA”. Double banking of cables run in the horizontal plane is not permitted. X.L.P.E. cable shall not be used below 16 mm² cross section. Due to the difficulty of laying and bending 3 and 4 core 400 mm2 cables, special approval is required where use. Page 86 of 91 Issue : 0 16-10-2016 Unclassified