ZNS Series Ceiling‑mount Horn Strobes

advertisement
Fire Alarm Systems | ZNS Series Ceiling‑mount Horn Strobes
ZNS Series Ceiling‑mount Horn Strobes
▶ Pre‑wire the base and test the circuit wiring before the
ceilings are covered
▶ Select continuous or temporal (Code 3) horn tones and
90 dBA or 95 dBA
▶ Select 24 V filtered DC (VDC) or unfiltered
Full‑Wave‑Rectified (Vrms) input voltage
▶ Select candela settings of 15/30/75/95 cd and
115/177 cd
The Cooper Wheelock ZNS Series Horn Strobes provide a
selectable continuous or Code 3 horn tone when connected
directly to the Fire Alarm Control Panel (FACP). They also
provide a synchronized Code 3 horn tone and strobe when
used with an FACP that incorporates the Wheelock
synchronization protocol, a Wheelock Synchronization
Module, or the Wheelock Power Supply. The ZNS Horn
Strobes can be field set for high (HI) or low (LO) dBA sound
output. Strobes are designed to flash at 1 flash per second
minimum over their Regulated Voltage Range.
The ZNS Horn Strobes are designed for use with either 24 V
filtered DC (VDC) or unfiltered Full‑Wave‑Rectified (Vrms)
input voltage. All inputs are polarized for compatibility with
standard reverse polarity supervision of circuit wiring by an
FACP.
The ZNS Series Horn Strobes, like all Cooper Wheelock Z
Series appliances, are designed for easy installation. The
universal two-wire base allows a continuity check of the
entire NAC circuit before any appliances are attached and
allows the appliances to be installed after all finish work has
been completed. The appliances simply snap onto the
universal bases.
Region
Certification
USA
UL
UCST: Audible Signal Appliances, General
Signal (UL464)
CSFM
7125-0785: 142
Installation/Configuration Notes
Compatible Products
The following products are compatible with the ZNS Series
Horn Strobes:
Category
Product ID
Product Description
Control Panels
D70221
Conventional FACP
D7024
Conventional FACP
D70242
Addressable FACP
D91243
Addressable FACP
D80243
Analog FACP
D10024A3
Analog FACP
SM‑12/24‑R
Synchronization module (red)
DSM‑12/24‑R
Dual synchronization module (red)
PS‑24‑8MC
Power supply with built-in synchronization protocol
Modules
Power Supply
Certifications and Approvals
Cooper Wheelock holds these Listings and Approvals.
ULSZ: Audible Signal Appliances (UL464)
1
The D7022 must be set for 24 V operation.
www.boschsecurity.com
2 | ZNS Series Ceiling‑mount Horn Strobes
2 When used with a D7039 Multiplex Expansion Module, the
Mechanical Properties
D7024 becomes an addressable fire alarm control panel
(FACP).
Dimensions:
3
4.8 in. x 4.8 in. x 2.9 in.
(122 mm x 122 mm x 74 mm)
For synchronization, use the SM or DSM modules with
these control panels and set the synchronization module for
24 VDC operation.
Power Requirements
Mounting Considerations
Voltage
Type
The ZNS Horn Strobes snap onto the pre-installed ZBASE
Two-wire Base. The ZBASE Two-wire Base flush mounts on
single-gang, double-gang, 4 in. square, 4 in. octal, and 3.5 in.
octal back boxes.
Horn and Strobe Current Draw2
Volume
Setting
DC:
Wiring Considerations
The wiring terminals on the ZBASE Two-wire Base accept
two appliance wires with diameters between 12 AWG
(2.3 mm) and 18 AWG (1.2 mm) at each terminal.
RMS:
Current Draw
High:
15 cd: 82 mA, 30 cd: 124 mA,
75 cd: 209 mA, 95 cd: 275 mA,
115 cd: 350 mA, 177 cd: 4 77 mA
Low:
15 cd: 71 mA, 30 cd: 114 mA,
75 cd: 201 mA, 95 cd: 261 mA,
115 cd: 306 mA, 177 cd: 429 mA
High:
15 cd: 141 mA, 30 cd: 204 mA,
75 cd: 312 mA, 95 cd: 411 mA,
115 cd: 491 mA, 177 cd: 681 mA
Low:
15 cd: 124 mA, 30 cd: 184 mA,
75 cd: 301 mA, 95 cd: 397 mA,
115 cd: 469 mA, 177 cd: 659 mA
Parts Included
Quant.
Component
Voltage (input)
1
Horn Strobe
Nominal:
24 VDC or Vrms
1
Two-wire base
Range:
16 V to 33 V
1
Dust cover
2
2
Hardware packs
1
Literature pack
Current Draw is the same for the Continuous Horn and
Code 3 Horn Settings.
Ordering Information
Technical Specifications
Audible Patterns and Ratings1
Pattern
Continuous:
Code 3:
Volume Setting
Sound Output1
High:
87 dBA
Low:
81 dBA
High:
82 dBA
Low:
76 dBA
1
Sound output is a minimum UL rating based on sound
power measurements at a distance of 10 ft (3 m) in a
reverberant test room per UL464.
Environmental Considerations
Environment:
Indoor, dry
Relative Humidity:
93±2% maximum, non‑condensing
Temperature (operating):
+32°F to +120°F (0°C to +49°C)
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems Inc. 2008 | Data subject to change without notice
T4436610827 | Cur: en-US, V2, 28 Jan 2008
ZNS‑MCC‑FR Multi‑candela Ceiling‑mount
Horn Strobe (red)
ZNS-MCC-FR
ZNS‑MCC‑FW Multi‑candela Ceiling‑mount
Horn Strobe (white)
ZNS-MCC-FW
ZNS‑MCCH‑FR High‑candela Ceiling‑mount
Horn Strobe (red)
ZNS-MCCH-FR
ZNS‑MCCH‑FW High‑candela
Ceiling‑mount Horn Strobe (white)
ZNS-MCCH-FW
Accessories
ZBASE Two‑wire Base
Universal base for all ZNH Series Horns, ZRS
Series Strobes, and ZNS Series Horn Strobes.
ZBASE
PS‑24‑8MC Power Booster Power Supply
PS-24-8MC
Asia-Pacific:
Bosch Security Systems Pte Ltd
38C Jalan Pemimpin
Singapore 577180
Phone: +65 6319 3450
Fax: +65 6319 3499
apr.securitysystems@bosch.com
www.boschsecurity.com
Represented by
Download