STA.001.035.0041 Foil insulation electrical inspection and testing procedures House Address: _________________________________________________________________ Customer Details Name: ____________________________________ Contact: ___________________________ Insulation Details Installation Date: ____________________ Insulation Contract Number :_____________________ Electrical Inspection Details Electrical Contractor: ____________________________________ License No: _____________ Electrician performing work: _________________________________ License No: ______________ Completion Date: _______________________________ Duration: _____________________________ IMPORTANT SAFETY NOTICE: TEST BEFORE YOU TOUCH! Electrical tests outlined in this procedure are intended to ascertain that the foil insulation is not in contact with live parts of the electrical installation. Electrical testing inherently involves a degree of hazard and this procedure involves a number of steps to be undertaken in the listed sequence in order to minimise the risk of electric shock to any person (electrician or householder) present on the premises. Variations to the procedure are permitted provided that an assessment, taking into account specific site conditions, confirms an equivalent safety outcome. Reference should be made to AS/NZS3017 Electrical installations – Verification Guidelines, for further guidance on inspection and test practices. INSPECTION AND TESTING PROCEDURES DOCUMENTATION AND SAFETY ALERTS STEP 1: Preparation/Assessment. To alert of any electrical problems that may have arisen following the foil installation CONSULT the householder to confirm: Comments/Concerns Check when complete approximate age of house and the electrical installation; that foil insulation has been installed in the roof; if foil installer mentioned any electrical problems if any electrical faults (eg lights flickering, tingles from taps) have been observed since the roof was insulated acceptance that supply will be disconnected during Inspection/Test Conduct VISUAL CHECK: all isolators, circuit-breakers and fuses are ON if RCDs are installed at switchboard general condition of switchboard equipment location of aerial service connection to house (if applicable) Check/count exhaust fans/heat lamp fans combinations Walk through the house and turn lights, fans and other equipment in the roof space ON Comment: ____________________ Comment: ____________________ Comment: ____________________ Count: ____________________ Ensures that the circuits within the roof space are not interrupted by single or multi-way switches STEP 2: Risk Management To ensure that hazards specific to the installation are controlled Conduct RISK ASSESSMENT including factors: Comments/Concerns Check when complete STA.001.035.0042 electric shock hazard from potentially live foil type/condition of wiring excessive heat in roof space poor visibility in darkened space fall through ceiling Complete contractor’s safe work documents or attached assessment form to confirm risk control measure and to ensure that the work is performed to a safe system. It is expected that 2 electrical workers would be involved in the conduct of this test for live parts. ALERT: If risk considered unacceptable to proceed –complete Safety Incident Report identifying concern. Prepare and use Personal Protective Equipment (PPE) that would assist in avoiding contact with a ‘live’ surface including: insulated gloves, safety glasses and hard hat insulated mat and covers; cotton long sleeve shirt and long pants fibreglass ladder Additional PPE will be necessary where the roof space temperature is high eg cooling vests or collars STEP 3: Voltage Test Procedure This procedure is based on check that foil insulation may be ‘live’ and is based on 2 people. Before entering roof space conduct VOLTAGE TEST: Comments/Concerns install temporary independent earth, eg electrode driven into ground; connect a trailing lead from independent earth to terminal on voltage tester; check that voltage tester works correctly by connecting other lead to socket-outlet or switchboard equipment; without entering the roof space, and using insulating gloves, mat and covers to reduce risk of contact, connect other test lead from voltage tester to foil in the vicinity of the roof access point. Repeat the test for each switching configuration for circuits with multiple switches to ensure each ‘strap’ conductor is tested for contact with foil Independent earth and voltmeter is preferred as it does not depend on the foil being separated from earthed equipment. ALERT: If voltage detected, you must use alternative procedures outlined in Safety Incident Report to: make safe; identify cause; repair or disconnect; record and notify incident and action taken. Be aware that the cause may involve damage to the consumers mains and isolation will involve disconnection at service connection point. If no voltage detected, isolate all circuits by – turning the Main Switch OFF or removing service fuse(s) at external connection point;(if permitted by energy distributor) and turning OFF supplies from any alternate sources. Disconnection at service connection point will allow the subsequent IR test to include consumers main active Isolation Method used: _____________ STEP 4 Insulation Resistance Test Procedures This procedure follows the test that shows that foil insulation is not ‘live’. Conduct INSULATION RESISTANCE TEST : disconnect MEN link at switchboard; connect a trailing lead from one IR Tester terminal to the active conductor(s) at the load side terminals of the main switch or other isolated point; before entering the roof space, repeat the VOLTAGE TEST on the foil as a precautionary measure Checks that the active or neutral conductors are not in contact with the foil insulation by methods such as: - an alligator clip on the IR test lead connected to a continuous foil layer near the access point - a probe such as an insulated conduit with conductive end piece to enable contact with separate sections of foil Check when complete For accurate measurements of ‘touch voltage’ refer to AS/NZS3017 Voltage measurements: ____________________ ____________________ ____________________ STA.001.035.0043 enter roof space to the extent necessary to perform test; connect a probe from the other IR Tester terminal to each sheet of the foil; measure insulation resistance between active conductors and each sheet of foil and record; change trailing lead connection from active conductors to neutral conductors at neutral link; measure insulation resistance between neutral conductors and each sheet of foil and record. ALERT: If IR measurements are low (acceptable values are >1.0 MΩ), you must use alternative procedures outlined in Safety Incident Report to: make safe; identify cause; repair or disconnect; record and notify incident and action taken. IR measurements: Active /Foil___________________ IR measurements: Neutral/Foil__________________ NOTE: Low IR measurement between neutral and foil may indicate that foil is earthed. Disconnect the consumers main neutral and repeat IR test between circuit neutrals and foil and mains neutral and foil Low IR may mean foil fixings have penetrated cable and a safe procedure will need to be conducted to identify and record cause. If IR measurements are acceptable, restore supply to installation – remove IR tester trailing lead; reconnect MEN link and main neutral ; turn main switch ON; check that supply restored to customers equipment; repeat the VOLTAGE TEST on the foil before disconnecting independent earth. STEP 5: Visual inspection procedures Observations on foil insulation: fixed by metal staples or fasteners measures taken to avoid contact with electrical wiring and equipment appears to be acceptable standard or not halogen or incandescent downlights covered by foil or clear Check exhaust fans/combinations have clear airflow other concerns Record results of inspection/test and observations Comments/Concerns Check when complete Metal fixings (YES/NO): _________ Comment (YES/NO): ___________ Comment (YES/NO): ___________ Comment (YES/NO): ___________ Comment (YES/NO): ___________ Include photographs with Safety Incident Report to identify specific concerns Observations of electrical installation general condition; any immediately dangerous aspects encountered that should require installation to be disconnected/rectified If installation appears dangerous to use complete Safety Incident Report identifying concern, and rectify, disconnect or otherwise make safe. Comment: __________________________________ __________________________________ __________________________________ Attach notification of inspection/test in switchboard Attach notification of inspection/test in switchboard CERTIFICATION I certify that an electrical inspection and testing procedure, restricted to an assessment of the potential adverse affects of reflective foil insulation on the electrical installation, has been carried out on these premises in accordance with the nominated procedures. STA.001.035.0044 Electrician performing test: __________________________ License number _______________ Signature: _____________________________Date:___________________