3RK1408-8KG00-0AA2 Page 1 Product data sheet 3RK1408-8KG00-0AA2 AS-INTERFACE SLIMLINE MODULE S22.5, EARTH FAULT MONITORING, IP20,1 X 1INPUT, REMOTE RESET, 2 X SIGNAL OUTPUT, RELAY, 1A DC12 1A (2A MAX.) DC13 500MA (24V) CAGECLAMP, MODULE WIDTH 22.5 MM, NO AS-I ADDRESS REQUIRED AS-INTERFACE MONITORING ONLY General technical data: Design of the product ground-fault detection modules - modules with special functions Design of the electrical connection / of the inputs and outputs spring-loaded terminals AS interface / total current input / max 40 mA Earth fault 10% Uas-i <= Ugnd <= 90% Uas-i Addressing the module does not need its own AS-Interface address Signal range / low signal / lin / max 1.5 mA Signal range / high signal / Uin / min 10 V Signal range / high signal / lin / min 6 mA Current carrying capacity / DC-12 1A Current carrying capacity / DC-13 / 24 V 500 mA Current carrying capacity / DC-13 / 48 V 200 mA Operating cycles / DC-12 2000000 Rated operational voltage / DC / min 24 V Rated operational voltage / DC / max 48 V Rated temperature 25 °C AS interface / Connection / Polarity reversal protection built-in Date: 01/11/2008 subject to modifications © Copyright Siemens AG 2008 3RK1408-8KG00-0AA2 Page 2 Note 1 If repeaters are used, a ground fault detection module must be used for each AS-Interface segment (number of AS-Interface power supply units = number of ground fault detection modules) Note 2 Uaux should be protected by a 2 A slow fuse. The endurance of the relay can be increased if inductive loads are connected using freewheel diodes. Inputs: Status display: Certificates/approvals: Ambient conditions: Ambient temperature • during the operating phase • maximum 70 °C • minimum -25 °C • during storage • maximum 85 °C • minimum -40 °C Protection class IP IP20 Mechanical design: Width 22.5 mm Height 103 mm Depth 86 mm Type of fixing/fixation standard rail mounting/wall mounting Conductor cross-section • solid 2 x (0.25 - 1.5) mm² • finely stranded • with end sleeve 2 x (0,25 - 1) mm² • without end sleeve 2 x (0.25 - 1.5) mm² • AWG / solid or stranded Date: 01/11/2008 AWG 2 x (24 - 16) mm² subject to modifications © Copyright Siemens AG 2008 3RK1408-8KG00-0AA2 Page 3 last change: Technical Assistance: Date: 01/11/2008 10/31/2006 Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET) Fax: +49 (0) 911-895-5907 E-Mail: technical-assistance@siemens.com Internet: www.siemens.de/lowvoltage/technical-assistance subject to modifications © Copyright Siemens AG 2008