Lightning and Surge Protection PowerPro BC (reducing follow-on current) PP BC TT 25/100 (/FM) Combined four-pole lightning current and Surge Protective Device meeting IEC and EN test class I+II; SPD type T1 T2 (BC) Used for lightning protective equipotential bonding in 3-phase + N ..... IEC TT-Power Net Systems • Combined 4-pole Surge Protective Device (SPD), fully pre-wired, makes installation of class II SPD in sub-distribution board probably unnecessary • Leakage current free! • Lightning current and SPD based on hermetically sealed gas filled spark-gaps • No blow-out vents, no safety distances for installation necessary • Highly resistant against danger TOV • Voltage protection level ≤ 2,5 kV • Lightning current test (10/350 µs) level 25 kA per phase, 100 kA for N-PE • Follow-on currents reducing • High insulation resistance Risol> 10 G Ω • Serial wiring with multifunctional screw terminal • Function control with potential-free remote signal contact (optional) Product description: This combined Lightning and Surge Protective 4-pole SPD type PP BC TT 25/100 and PP BC TT 25/100/FM, with remote signal contacts, connected in the so called 3+1 circuit, offer a complete solution for the protection of TT-Power Net Systems. Usually installed in main-distribution board at service entrance. Thanks to the use of the patented, hermetically sealed gas-filled isolating spark-gaps (inert gas) this SPD allows you to achieve a high-level discharge capacity without needing blow-out vents. This saves you from keeping the safety distance to adjoining electrical components usually necessary to avoid unwanted electric arcs and fire hazardous. As there is no risk of leakage currents, this SPD can also be installed before the electric power meter (acc. to TAB2000, installation rules of the Union of German Electric Works, VDEW). This device is capable to discharge lightning current surges of 25 kA (10/350 µs) per phase and total 100 kA (10/350 µs) between N-PE as well as self-extinguish main supply and reducing net Follow-on currents. The protective circuit is installed in an easy-to-handle compact housing with snap-on clips for 35 mm DIN rail mounting on both sides, equipped with multifunctional screw terminals for wire and bus-bar connections. Installation can be carried out either by parallel wiring via the multifunctional screw connection terminal (terminal L1´, L2´, L3´, and PE´) or else as serial V-wiring via the 2-pole bus-bar connection (L to L´ ). A built in potential-free hermetical sealed NC remote signal contact (/FM) is optional available. The wire connection can be made via a pluggable screw terminal block included to the SPD. Protects People and valuables Technical Data Application 4 pole Lightning Current and Surge Protective Device for TT3+1-Power Net Systems. To be installed at the boundary of LPZ 0B-1 or higher, acc the Lightning Protection Zone conception in IEC 62305 part 1-4 Type Order and part number IEC 61643-1 EN 61643-11 E DIN VDE 0675-6 11/98-A1 Nominal net voltage 50/60 Hz Rated voltage (max. continuous operating voltage) 50/60 Hz Insulation resistance Voltage protection level at 100% lightning impulse spark over voltage (1,2/50µs), 6kV Voltage protection level at Iimp 10/350µs Response time Lightning impulse current Iimp (10/350µs) Max impulse discharge current (8/20µs) Short-circuit withstand capability at max. pre-fuse Max. permissible line resp. back fuse F2 at parallel wiring Max. permissible line resp. back fuse F3 at serial V- wiring PP BC TT 25/100/FM 37 39 20 37 39 22 Un Uc Risol [V~] SPD class I+II T1 + T2 BC 230 / 400 [V~] 255 (275) [GΩ] > 10 Uas [kV] ≤ 2,5 Up tA [kV] ≤ 2,5 < 50 [ns] L1, L2, L3 – N: 25 12,5 160 N - PE: 100 50 2.500 Ipeak Q W/R [kA] [As] [kJ/Ω] Imax Ik [kA] 50 [kAeff] 50 t Operating temperature range PP BC TT 25/100 [A] 250 A gL/gG [A] 125 A gL/gG -40 … +85 [°C] Min. / Max. cross-sectional area [mm²] stranded 50 or flexible 35 with sleeve Min. / Recommended cross sectional area [mm²] 10 / 25 Recommended connection torque [Nm] 4,5 Max. cross-sectional area for remote signal contact [mm²] 1,5 AC 250V/ 0,5A Max. switching capacity of remote signal contact Polycarbonate (halogen free) UL 94-V0 / yellow Material of housing / colour IP 20 Protection degree (IEC/EN 60529) 35 mm DIN rail form C (DIN/EN 50 022) Mounting on Dimensions in mm / Diagram Application: Dimension 4x 2 modules á 17,5mm; acc. DIN 43880 If line or backup fuse (F1) ≤ 250 A gL/gG back up fuse (F2) is not forced. Parallel wiring for active lines 2-pole bus-bar connection Line or backup fuse (F3) ≤ 125 A gL/gG Serial wiring for active lines PP BC TT 25/100 (/FM) 09.09.2008 _pdf © 2008 by LEUTRON GmbH Subject to technical modifications and delivery possibilities LEUTRON GmbH Lightning and Surge Protection Humboldtstrasse 30-32 D-70771 Leinfelden-Echterdingen GERMANY Telephone +49 711 / 9 47 71-0 Fax +49 711 / 9 47 71-70 email: info@leutron.de www.leutron.de